HomeMy WebLinkAboutResponse to Comments 011626City of Little Rock Planning and Development
Planning Commission Hearing/January 8, 2026
Applicant Comments for Proposed Development
Applicant responses are due no later than Thursday, December 11, 2025. Please
submit revised site plans, if applicable, along with written responses from
Development Staff and “Other Departments.” Please submit responses to
comments to: tthrower@littlerock.gov & agoldman@littlerock.gov
RE: Z-7648-A
Two Moon Properties, LLC – PD-R
SWC of Charles Bussey Avenue & Park Lane
Development Staff Comments:
1. Provide building elevations for proposed single-family residences and multi-family
building.
2. The proposed single-family residences and multi-family units shall not be operated
as short-term rental (STR) prior to approval by the Planning Commission.
3. How will trash be collected for multi-family apartment building?
4. Residential signs must comply with Section 36-551of the City’s Zoning Ordinance
(signs permitted in residential one- and two-family zones).
5. Any lighting must be low-level and directed away from adjacent properties.
6. Any fencing or wall erected must comply with Section 36-516 of the City’s Zoning
Ordinance.
7. The propose quadplex typically requires a minimum of six (6) off-street parking
spaces.
Page 1 of 3
LITTLE ROCK PLANNING COMMISSION AGENDA
1/8/2026
PUBLIC WORKS ENGINEERING COMMENTS
1. S-2010 Kanis Park Commercial
1. A cul de sac design is recommended for SU-60 vehicles and fire trucks for easier maneuverability
and turnaround from the south driveway.
2. LRFD should be consulted for their preferred design for fire access.
2. S-2011 Laycee Trails
1. The development is required to provide stormwater detention in conformance with the Little
Rock Drainage Manual.
3. Z-10243 Rezoning from O1 to O-3, East side John Barrow Rd & S. of Labette Dr.
1. Driveway locations and widths do not meet the traffic access and circulation requirements of
Sections 30-43 and 31-210 for arterial streets. Driveway spacing on an arterial street is 300 ft
from intersections and other driveways and 150 ft from side property lines.
2. The development is required to provide stormwater detention in conformance with the Little
Rock Drainage Manual.
4. Z-10231 Rise and Reveal Sobriety House SUP, 6601 Juniper Road
1. No comments
5. Z-10242 Incura Rehabilitation Clinic CUP, 1000 S. Rodney Parham Rd
1. Portions of the property are located within the regulatory floodplain, Zone AE. In future
improvements to the property is subject to conformance with the City of Little Rock floodplain
regulations.
6. Z-7154-A ACTS Senior Village PCD, SEC of John Barrow Rd & W. 40th St.
1. The proposed private street east of the pop up spaces should be designed and constructed as a minor
commercial street of 31 ft width, with commercial street pavement and base course thickness.
2. Right-of-way dedications and half street construction should conform with Master Street Plan for
minor commercial streets on W. 40th St. and W. 42st St. adjacent to the proposed non-residential use. City
code allows the dedications and street construction to conform with the residential street standard adjacent
to residential uses.
3. Future bus stop locations and designs are required to be approved by LR Public Works and Rock
Region Metro prior to installation.
7. Z-7648-A Two Moon Properties PD-R, SWC Charles Bussey Ave & Park Lane
1. A width of at least 20 ft must be provided for 2-way traffic for the proposed interior driveways
accessing the residential structures.
2. A 20 feet radial dedication of right-of-way is required at the intersection of Charles Bussey St. and Park
Page 2 of 3
Lane.
3. Park Lane is classified on the Master Street Plan as a residential street. A dedication of right-of-way 25
feet from centerline will be required.
4. Repair or replace any curb, gutter, sidewalk and access ramps that are damaged and not in compliance
with ADA recommendations in the public right-of-way prior to occupancy.
8. Z-10232 Hines PD-R 3 Marigold Drive
1. Colonel Glenn Rd is classified on the Master Street Plan as a principal arterial street. A dedication of
right-of-way 55 feet from centerline will be required.
2. A 20 feet radial dedication of right-of-way is required at the intersection of Col. Glenn Rd. and
Marigold Drive.
3. Marigold Drive is classified on the Master Street Plan as a commercial street. A dedication of right-of-
way 30 feet from centerline will be required.
4.With site development, provide design of Col. Glenn Rd conforming to the Master Street Plan.
Construct one-half street improvement to Col. Glenn Rd including 5-foot sidewalks with planned
development. The new back of curb should be placed 29.5 from the existing striped centerline. If
construction is not allowed by ARDOT, a payment in-lieu of construction should be obtained for the cost
of the construction of the street improvements.
5.With site development, provide design of Marigold Drive conforming to the Master Street Plan.
Construct one-half street improvement to Marigold Drive including 5-foot sidewalks with planned
development. The new back of curb should be placed 15.5 ft from the existing striped centerline.
9. Z-5963-H Brodie Creek Subdivision Cell Tower Rev, PD-R
1. Bowman Road is proposed to be widened to a 5 lane arterial street in the near future. Plans and right-
of-way are currently being assembled. The proposed tower should be located to not obstruct the proposed
street widening. Provide a plan showing the cell tower location in relation to the proposed street
widening. Contact David Hopkins, PW Civil Engineering Manager, at 501-371-4812 for assistance in
locating the proposed street widening.
2.A special Grading Permit for Flood Hazard Areas will be required per Sec. 13-55 prior to construction.
3. No development is permitted within the floodway. In accordance with Section 31-176, floodway areas
must be shown as floodway easements or be dedicated to the public. In addition, a 25 foot wide drainage
and access easement is required adjacent to the floodway boundary.
10. Z-7500 K Hamilton Station Apartments PD-R, N of 14524 Cantrell Rd
1. A special Grading Permit for Flood Hazard Areas will be required per Sec. 13-55 prior to construction.
2. The minimum Finish Floor of all proposed inhabitable structure are required to be elevated to at least 1
ft higher than the base flood elevation and required to be shown on the site plan.
3. No development is permitted within the floodway. In accordance with Section 31-176, floodway areas
must be shown as floodway easements or be dedicated to the public. In addition, a 25 foot wide drainage
and access easement is required adjacent to the floodway boundary.
4. Provide additional information detailing the uses of the east and west proposed driveways. Will
tenants use both driveways for typical access or is one driveway for secondary fire access only.
5.The development is required to provide stormwater detention in conformance with the Little Rock
Drainage Manual.
6. Manual opening gates shall not be locked with a padlock or chain and padlock unless they are capable
of being opened by means of forcible entry tools or when a key box containing the keys to the lock is
installed at the gate location.
7. Locking device specifications shall be submitted for approval by the fire code official
8. Electric gate operators, where provided, shall be listed in accordance with UL 325.
9. Gates, intended for automatic operation shall be designed, constructed and installed to comply with
requirements of ASTM F 2200.
Multi-Family Residential Developments
As per Appendix D, Section D106.1 of the 2021 Arkansas Fire Prevention Code Vol. 1. Projects having
more than 100 dwelling units. Multiple-family residential projects having more than 100 dwelling units shall
be equipped throughout with two separate and approved fire apparatus access roads.
Exception: Projects having up to 200 dwelling units may have a single approved fire apparatus
access road when all building, including nonresidential occupancies are equipped throughout with approved
automatic sprinkler systems installed in accordance with Section 903.3.1.1 or 903.3.1.2
As per Appendix D, Section D106.2 of the 2021 Arkansas Fire prevention Code Vol. 1. Projects having
more than 200 dwelling units. Multiple-family residential projects having more than 200 dwelling units shall
be provided with two separate and approved fire apparatus access roads regardless of whether they are
equipped with an approved automatic sprinkler system.
One- or Two-Family Residential Developments.
As per Appendix D, Section D107.1 of the Arkansas Fire Prevention Code Vol. 1, One- or Two-Family
dwelling residential developments. Developments of one- or two-family dwellings where the number of
dwelling units exceeds 30 shall be provided with two separate and approved fire apparatus access roads, and
shall meet the requirements of Section D104.3.
Exceptions:
1. Where there are more than 30 dwelling units on a single public or private fire apparatus access
road and al dwelling units are equipped throughout with an approved automatic sprinkler system
in accordance with Section 903.3.1.1, 903.3.1.2 or 903.3.1.3 of the Arkansas Fire Code, access
from two directions shall not be required.
2. The number of dwelling units on a single fire apparatus access road shall not be increased unless
fire apparatus access roads will connect with future development, as determined by the fire code
official.
Contact Chief Davbram Flowers at (501) 918-3780, Capt. Tony Rhodes at (501) 918-3757, Fire Marshal Derek
N Ingram (501) 918-3756, or Fire Marshal Evan Johnson (501) 765-1646.
Z-7648-A Two Moon Properties, LLC - PD-R SWC Charles Bussey Avenue &
Park Lane
Must Comply with Arkansas Fire Prevention Code 2021 edition
All projects submitted for zoning approval must comply with the Arkansas Fire
Prevention Code, 2021 Edition, including any comments or requirements
provided by the Little Rock Fire Marshal's Office, prior to acceptance.
Maintain Access:
Fire Hydrants.
Maintain fire apparatus access roads at fire hydrant locations as per Appendix D of the 2021 Arkansas Fire
Prevention Code Vol. 1 Section D103.1 Access road width with a hydrant. Where a fire hydrant is located
on a fire apparatus access road, the minimum road width shall be 26 feet, exclusive of shoulders.
Grade
Maintain fire apparatus access roads as per Appendix D of the 2021 Arkansas Fire Prevention Code Vol. 1
Section D103.2 Grade. Fire apparatus access roads shall not exceed 10 percent in
grade except as approved by the fire chief. If the grade exceeds 10 percent,
approval will be denied and the applicant must submit request to be reviewed by
Fire Chief for Approval.
Loading
Maintain fire apparatus access road design as per Appendix D of the 2021 Arkansas Fire Prevention Code Vol.
1 Section D102.1 Access and loading. Facilities, buildings or portions of buildings hereafter constructed shall
be accessible to fire department apparatus by way of an approved fire apparatus access road with an asphalt,
concrete or other approved driving surface capable of supporting the imposed load of fire apparatus weighing
at least 75,000 pounds.
Z-10232 Hines-PD-R 3 Marigold Drive
Must Comply with Arkansas Fire Prevention Code 2021 edition
All projects submitted for zoning approval must comply with the Arkansas Fire
Prevention Code, 2021 Edition, including any comments or requirements
provided by the Little Rock Fire Marshal's Office, prior to acceptance.
Maintain Access:
Fire Hydrants.
Maintain fire apparatus access roads at fire hydrant locations as per Appendix D of the 2021 Arkansas Fire
Prevention Code Vol. 1 Section D103.1 Access road width with a hydrant. Where a fire hydrant is located
on a fire apparatus access road, the minimum road width shall be 26 feet, exclusive of shoulders.
Grade
Maintain fire apparatus access roads as per Appendix D of the 2021 Arkansas Fire Prevention Code Vol. 1
Section D103.2 Grade. Fire apparatus access roads shall not exceed 10 percent in
grade except as approved by the fire chief. If the grade exceeds 10 percent,
approval will be denied and the applicant must submit request to be reviewed by
Fire Chief for Approval.
Loading
Maintain fire apparatus access road design as per Appendix D of the 2021 Arkansas Fire Prevention Code Vol.
1 Section D102.1 Access and loading. Facilities, buildings or portions of buildings hereafter constructed shall
be accessible to fire department apparatus by way of an approved fire apparatus access road with an asphalt,
concrete or other approved driving surface capable of supporting the imposed load of fire apparatus weighing
at least 75,000 pounds.
Commercial and Industrial Developments – 2 means of access. - Maintain fire apparatus access roads as
per Appendix D of the 2021 Arkansas Fire Prevention Code Vol. 1
Section D104.1 Buildings exceeding three stories or 30 feet in height. Building or facilities exceeding 30
feet or three stories in height shall have at least two means of fire apparatus access for each structure.
Section D104.2 Building exceeding 62,000 square feet in area. Buildings or facilities having a gross
building area of more than 62,000 square feet shall be provide with two separate and approved fire apparatus
access roads.
Exception: Projects having a gross building area of up to 124,000 square feet that have a single
Please submit plans for water facilities and/or flre protection system to Central Arkansas Water for
review. Plan revisions may be required after additional review. Contact Central Arkansas Water
regarding procedures for installation of water facilities and/or flre service. Approval of plans by the
Arkansas Department of Health Engineering Division and Little Rock Fire Department is required.
If there are facilities that need to be adjusted and/or relocated, contact Central Arkansas Water.
That work would be done at the expense of the developer.
Due to the nature of this facility, installation of an approved reduced pressure zone backfiow
preventer assembly (RPZ) is required on the domestic water service. This assembly must be
installed prior to the flrst point of use. Central Arkansas Water (CAW) requires that upon installation
of the RPZA, successful tests of the assembly must be completed by a Certifled Assembly Tester
licensed by the State of Arkansas and approved by CAW. The test results must be sent to CAW's
Cross Connection Section within ten days of installation and annually thereafter. Contact the Cross
Connection Section at 377-1226 if you would like to discuss backfiow prevention requirements for
this project.
Fire sprinkler systems which do not contain additives such as antifreeze shall be isolated with a
double detector check valve assembly. If additives are used, a reduced pressure zone backfiow
preventer shall be required.
Z-7648-A – Two Moon Properties, LLC – PD-R, SWC Charles Bussey and Park Ln. - All Central
Arkansas Water requirements in effect at the time of request for water service must be met
Please submit plans for water facilities to Central Arkansas Water for review. Plan revisions may be
required after additional review. Contact Central Arkansas Water regarding procedures for
installation of water facilities. Approval of plans by Central Arkansas Water, the Arkansas
Department of Health Engineering Division and Little Rock Fire Department is required.
If there are facilities that need to be adjusted and/or relocated, contact Central Arkansas Water.
That work would be done at the expense of the developer.
Additional flre hydrant(s) will be required. Contact the Little Rock Fire Department to obtain
information regarding the required placement of the hydrant(s) and contact Central Arkansas Water
regarding procedures for installation of the hydrant(s).
Z-10232 – Hines – PD-R, 3 Marigold Dr. - All Central Arkansas Water requirements in effect at the
time of request for water service must be met.
Please submit plans for water facilities and/or flre protection system to Central Arkansas Water for
review. Plan revisions may be required after additional review. Contact Central Arkansas Water
regarding procedures for installation of water facilities and/or flre service. Approval of plans by the
Arkansas Department of Health Engineering Division and Little Rock Fire Department is required
A Capital Investment Charge based on the size of meter connection(s) will apply to this project in
addition to normal charges. This fee will apply to all connections including metered connections off
the private flre system.