HomeMy WebLinkAboutPC Minutes 111825November 13, 2025
ITEM NO.: 17 FILE NO.: Z-10211
NAME: GT Auto Sales – PD-C
LOCATION: 10401 Helm Drive
DEVELOPER:
David Perez (Owner)
10401 Helm Drive
Mabelvale, AR 72103
SURVEYOR/ENGINEER:
Richardson Engineering, PLLC (Agent)
325 W. South Street
Benton, AR 72015
AREA: 3.5 acre NUMBER OF LOTS: 1 FT. NEW STREET: 0 LF
WARD: 7 PLANNING DISTRICT: 15 CENSUS TRACT: 41.05
CURRENT ZONING: R-2
VARIANCE/WAIVERS:
None requested.
A. PROPOSAL/REQUEST/APPLICANT’S STATEMENT:
The applicant proposes to rezone a 3.5 acre site from R-2 to PD-C to allow for the
development of an auto sales lot.
B. EXISTING CONDITIONS:
The site contains an existing building utilized for an auto sales and body shop.
Properties in the general area contain a mixture of zoning and uses.
November 13, 2025
ITEM NO.: 17 (cont.) FILE NO.: Z-10211
2
C. NEIGHBORHOOD NOTIFICATIONS:
All owners of property located within 300 feet of the site and all neighborhood
associations registered with The City of Little Rock were notified of the public
hearing.
D. ENGINEERING COMMENTS (PLANNING):
1. Any new development shall be permitted and receive all reviews to ensure all
codes, specifications, ADA and ordinances are met.
2. All streets, sidewalks and drainage shall comply with City of Little Rock
Standards and Specifications.
3. Handicap Parking shall include one van stall 11ft wide with a 5ft minimum aisle.
4. Per Sec. 36-508. - Pavement requirements every parcel of land which after the
effective date of this chapter is changed to a parking area, automobile, other
vehicle or trailer sales or storage area or automobile or motor vehicle service
station, garage or other vehicle use area shall be paved where subject to
wheeled traffic. The minimum pavement requirement shall be one and one-half
(1½) inches asphaltic concrete hot mix with a five-inch compacted base or a
double surface treatment with a five-inch compacted base or a four-inch
concrete slab and shall have appropriate bumper guards where needed.
Asphalt roofing and by-products of its manufacture are expressly prohibited as
a base course or as surfacing material on parking lots and/or drives.
Low impact development (LID) facilities and techniques are allowed to be used
for parking lot design and construction, unless conditions make LID infeasible
as determined by the director of public works or his/her designee. LID
techniques for parking lot design include, but are not limited to, pervious
surfacing and bioretention swales. Pervious surfacing may be an option for all
or a portion of the vehicular use area depending on the use, soil conditions and
associated vehicular traffic. Pervious surfacing includes, but is not limited to,
paving blocks, pervious concrete and porous asphalt. The surface of the
vehicular use area shall be maintained to comply with the approved plan.(Code
1961, Ch. 43, § 8-101(i); Ord. No. 21,079, § 1, 8-4-15)
5. Contact Planning and Development Dept., Engineering Division at 501-371-
4817 or at 501-918-5348 for inspections of any work in the public right-of-way
prior to placement of concrete or asphalt or for on-site clarification of
requirements prior to commencing work. Failure to do so can result in removal
of any improperly placed concrete or asphalt at the expense of the owner or
contractor.
6. Hauling of cut and/or fill material on or off project sites over municipal streets
require approval prior to a grading permit being issued. Contact Public Works
Traffic Engineering at 621 S. Broadway 501-379-1800 with any questions or
for more information.
November 13, 2025
ITEM NO.: 17 (cont.) FILE NO.: Z-10211
3
7. Damage to public and private property due to hauling operations or operations
of construction related equipment from a construction site shall be repaired by
the responsible party prior to the issuance of a certificate of occupancy.
8. A drainage study showing all hydrologic calculations for the site and all
hydraulic calculations for the proposed storm sewer pipe system, swales and
ditches, culverts, detention ponds, outlet structures, and inlets is required per
City’s stormwater management and drainage manual. For final drainage
report, sign, date, and seal the report per AR State Board of Professional
Engineers and Professional Surveyors rules Article 12, Section B (1) (a).
Provide engineer's certification statement saying this drainage report was
conducted by yourself or directly under your supervision and attesting to the
accuracy of the information within this report.
9. For final drainage report, sign, date, and seal the report per AR State Board of
Professional Engineers and Professional Surveyors rules Article 12, Section B
(1) (a).
Provide engineer's certification statement saying this drainage report was
conducted by yourself or directly under your supervision and attesting to the
accuracy of the information within this report.
10. Provide ADA accessible route from the public right of way to the proposed
development in accordance with 36 CFR Part 1191 Section F206.2.1, “… at
least one accessible route shall be provided within the site from accessible
parking spaces and accessible passenger loading zones, public streets and
sidewalks, and public transportation stops to the accessible building or facility
entrance they serve.”
11. A grading permit must be obtained prior to initiation of work. Grading permits
are issued by the Planning and Development Dept. at 723 West Markham
Street after approval of sediment and erosion control plans, grading and
drainage plans, land survey, drainage study, and soil loss calculations per
City’s stormwater management and drainage manual. Contact Planning and
Development Dept., Engineering Division at 501-371-4817 or at 501-918-5348
or Permits@littlerock.gov to schedule an appointment for issuance or to answer
any questions. Permit cost is based on total project area at $100.00 for the
less than ½ acre, $200.00 for ½ to 1 acre, and $200.00 for the first acre and
$100.00 for each additional acre for project greater than 1 acre.
ENGINEERING COMMENTS (PUBLIC WORKS):
1. Mabelvale Pike Rd is classified on the Master Street Plan as a minor arterial
street. A dedication of right-of-way 45 feet from centerline will be required;
2. Due to the proposed use of the property, the Master Street Plan specifies that
Helm Dr. for the frontage of this property must meet commercial street
standards. Dedicate right-of-way to 30 feet from centerline.
3. Repair or replace any curb, gutter, sidewalk and access ramps that are
damaged and not in compliance with ADA recommendations in the public right-
of-way prior to occupancy.
November 13, 2025
ITEM NO.: 17 (cont.) FILE NO.: Z-10211
4
4. With site development, provide design of Helm Drive conforming to the Master
Street Plan. Construct one-half street improvement to Helm Drive including 5-
foot sidewalks with planned development to a width of 15.5 ft from center of
street to new back of curb.
5. Show the proposed location of the stormwater detention pond. Maintenance
of the detention pond and all private drainage improvements is the
responsibility of the developer and/or local property owners’ association and
detailed in the bill of assurance.
6. If permitted the south gravel driveway should be constructed with a concrete
apron from the edge of street pavement to the property line.
7. Damage to public and private property due to hauling operations or operation
of construction related equipment from a nearby construction site shall be
repaired by the responsible party prior to issuance of a certificate of occupancy.
8. Obtain permits prior to doing any street cuts or curb cuts. Obtain barricade
permit prior to doing any work in the right-of-way. Contact Traffic Engineering
at (501) 379-1805 (Travis Herbner) for more information.
E. UTILITIES/FIRE DEPARTMENT/PARKS/COUNTY PLANNING:
Little Rock Water Reclamation Authority: No comments received.
Entergy: No comments received.
Summit Utilities: No comments.
AT & T: No comments received.
Central Arkansas Water:
1. Provide a15’ utility easement on the West side of the property for the existing
12’ DI main.
Fire Department:
Must Comply with Arkansas Fire Prevention Code 2021 edition
All projects submitted for zoning approval must comply with the Arkansas
Fire Prevention Code, 2021 Edition, including any comments or
requirements provided by the Little Rock Fire Marshal's Office, prior to
acceptance.
Maintain Access:
Fire Hydrants.
Maintain fire apparatus access roads at fire hydrant locations as per Appendix D
November 13, 2025
ITEM NO.: 17 (cont.) FILE NO.: Z-10211
5
of the 2021 Arkansas Fire Prevention Code Vol. 1 Section D103.1 Access road
width with a hydrant. Where a fire hydrant is located on a fire apparatus access
road, the minimum road width shall be 26 feet, exclusive of shoulders.
Grade
Maintain fire apparatus access roads as per Appendix D of the 2021 Arkansas Fire
Prevention Code Vol. 1 Section D103.2 Grade. Fire apparatus access roads
shall not exceed 10 percent in grade except as approved by the fire chief. If
the grade exceeds 10 percent, approval will be denied, and the applicant
must submit request to be reviewed by Fire Chief for Approval.
Loading
Maintain fire apparatus access road design as per Appendix D of the 2021
Arkansas Fire Prevention Code Vol. 1 Section D102.1 Access and loading.
Facilities, buildings or portions of buildings hereafter constructed shall be
accessible to fire department apparatus by way of an approved fire apparatus
access road with asphalt, concrete or other approved driving surface capable of
supporting the imposed load of fire apparatus weighing at least 75,000 pounds.
Commercial and Industrial Developments – 2 means of access. - Maintain fire
apparatus access roads as per Appendix D of the 2021 Arkansas Fire Prevention
Code Vol. 1
Section D104.1 Buildings exceeding three stories or 30 feet in height.
Buildings or facilities exceeding 30 feet or three stories in height shall have at least
two means of fire apparatus access for each structure.
Section D104.2 Building exceeding 62,000 square feet in area. Buildings or
facilities having a gross building area of more than 62,000 square feet shall be
provided with two separate and approved fire apparatus access roads.
Exception: Projects having a gross building area of up to 124,000 square
feet that have a single approved fire apparatus access road when all
buildings are equipped throughout with approved automatic sprinkler
systems.
D104.3 Remoteness. Where two fire apparatus access roads are required, they
shall be placed a distance apart equal to not less than one half of the length of the
maximum overall diagonal dimension of the lot or area to be served, measured in
a straight line between accesses.
30’ Tall Buildings - Maintain aerial fire apparatus access roads as per
Appendix D of the 2021 Arkansas Fire Prevention Code Vol. 1 Section D105.1
– D105.4
D105.1 Where Required. Where the vertical distance between the grade
plane and the highest roof surface exceeds 30’, approved aerial fire apparatus
access roads shall be provided. For the purposes of this section the highest roof
surfaces shall be determined by measurement to the eave of a pitched roof, the
November 13, 2025
ITEM NO.: 17 (cont.) FILE NO.: Z-10211
6
intersection of a roof to the exterior wall, or the top of the parapet walls, whichever
is greater.
D105.2 Width. Aerial fire apparatus access roads shall have a minimum
unobstructed with of 26’, exclusive of shoulders, in the immediate vicinity of the
building or portion thereof.
D105.3 Proximity to building. At least one of the required access routes
meeting this condition shall be located within a minimum of 15 feet and a maximum
of 30 feet from the building and shall be positioned parallel to one entire side of the
building. The side of the building on which the aerial fire apparatus access road is
positioned shall be approved by the fire code official.
D105.4 Obstructions. Overhead utility and power lines shall not be located
over the aerial fire apparatus access road or between the aerial fire apparatus road
and the building. Other obstructions shall be permitted to be placed with the
approval of the fire code official.
Dead Ends.
Maintain fire apparatus access roads at dead end locations as per Appendix
D of the 2021 Arkansas Fire Prevention Code Vol. 1 Section D103.4 Dead
Ends. Dead-end fire apparatus access roads in excess of 150 feet shall be
provided with width and turnaround provisions in accordance with Table D103.4.
Requirements for Dead-end fire apparatus access roads.
Gates
Maintain fire apparatus access road gates as per Appendix D of the 2021
Arkansas Fire Prevention Code Vol. 1 Section D103.5 Fire apparatus access
road gates. Gates securing the fire apparatus access roads shall comply with
all of the following criteria:
1. Minimum gate width shall be 20 feet.
2. Gates shall be of swinging or sliding type.
3. Construction of gates shall be of material that allow manual operation by
one person.
4. Gate components shall be maintained in an operable condition at all times
and replace or repaired when defective.
5. Electric gates shall be equipped with a means of opening the gate by fire
department personnel for emergency access. Emergency opening devices
shall be approved by the fire code official.
6. Manual opening gates shall not be locked with a padlock or chain and
padlock unless they are capable of being opened by means of forcible entry
tools or when a key box containing the keys to the lock is installed at the
gate location.
7. Locking device specifications shall be submitted for approval by the fire
code official
8. Electric gate operators, where provided, shall be listed in accordance with
November 13, 2025
ITEM NO.: 17 (cont.) FILE NO.: Z-10211
7
UL 325.
9. Gates, intended for automatic operation, shall be designed, constructed and
installed to comply with requirements of ASTM F 2200.
Parks and Recreation: No comments received.
F. BUILDING CODES/LANDSCAPE:
Building Code: No comments received.
Landscape:
1. Any new site development must comply with the City’s minimal landscape and
buffer ordinance requirements. Refer to the Code of Ordinances, Chapter 15
Landscaping and Tree Protection, and Chapter 36, Article IX – Buffers and
Screening.
2. Site development plans, with landscape and screening, must be submitted for
review, and approval, prior to site clearing and tree removal.
G. TRANSPORTATION/PLANNING:
Rock Region Metro: No comments received.
November 13, 2025
ITEM NO.: 17 (cont.) FILE NO.: Z-10211
8
Planning Division:
Land Use Plan:
The request is in District 15, the Geyer Springs West Planning District. The
development principles of this district seek to minimize potential negative impacts
between industrial and residential usage, and to improve traffic circulation. The
Land Use Plan shows Mixed Use (MX) use for the requested area. The Mixed Use
(MX) category provides for a mixture of residential, office and commercial uses to
occur. A Planned Zoning District is required if the use is entirely office or
November 13, 2025
ITEM NO.: 17 (cont.) FILE NO.: Z-10211
9
commercial or if the use is a mixture of the three. The application is for a Planned
Development-Commercial for Auto Sales.
Surrounding the application area, the southeast boundary of the application area
meets the Union Pacific Railroad right-of-way. To the west and southwest is area
designated for Mixed Use (MX) uses and is characterized by single-family homes,
small apartment complexes, duplexes, and commercial businesses.
This site is not located in an Overlay District.
Master Street Plan:
Helm Dr. is a Commercial Street on the Master Street Plan. Commercial Streets
are a Local public street which is abutted by non-residential or residential use
which is more intense than duplex or two-unit residential. These streets have the
same design standard as a Collector. The standard Right-of-way is 60 feet.
Sidewalks are required on both sides. This street may require dedication of right-
of-way and may require street improvements.
November 13, 2025
ITEM NO.: 17 (cont.) FILE NO.: Z-10211
10
Bicycle Plan:
Helm Dr. is not shown on the Master Bike Plan with existing or proposed facilities
in this area.
Historic Preservation Plan:
The application, as shown, should have no effect on identified historic resources.
November 13, 2025
ITEM NO.: 17 (cont.) FILE NO.: Z-10211
11
H. ANALYSIS:
The applicant proposes to rezone a 3.5 acre site from R-2 to PD-C to allow for the
development of an auto sales lot.
The site contains an existing building utilized as an auto sales and body shop and
several smaller existing buildings utilized for storage. Properties in the general
area contain a mixture of zoning and uses.
Access to the site will be provided by two (2) driveways extending from Mabelvale
Pike. There is an existing 18 foot driveway near the southwest corner of the
property. The applicant is proposing a second, 21.7 foot driveway, located near
the northwest corner of the property.
The developer will construct a new 3,200 square foot building in the northwest area
of the property near the north property line. The existing building currently operates
as an auto repair/body shop. The owner intends to continue existing operations to
repair vehicles brought in as inventory.
The site plan shows a front building setback over twenty-five (25) feet from the
west property line, ten (10) feet from the side (north) property line, over one-
hundred fifty (150) feet from the south property line, and well over three hundred
(300) feet from the rear property line.
The applicant notes that the business will not offer recreational (RVs) or all-terrain
(ATVs) vehicles for sale. Outside storage of auto parts, etc., will not be allowed at
any time.
All incidental work must be done inside an eclosed building.
Operating hours will be from Monday-Friday from 8:00am to 6:00pm with a
maximum number of three (3) employees at any given time.
Typically, eight (8) parking spaces are required for the proposed use. The applicant
is providing nineteen (19) parking spaces, including two (2) ADA parking spaces.
Employee, ADA and customer parking is located on the west side of the building.
The inventory parking area is located near the north entrance along Mabelvale
Pike. Staff feels the parking is sufficient to serve the proposed use.
The site plan shows a security fence along the north property line. Any fence or
wall erected must comply with Section 36-516 of the City’s Zoning Ordinance.
The applicant did not submit a signage plan with this application. All signs must
comply with Section 36-555 of the City’s Zoning Ordinance (signs permitted in
commercial zones).
November 13, 2025
ITEM NO.: 17 (cont.) FILE NO.: Z-10211
12
The applicant notes the owner will utilize the existing dumpster for his current
business on the property. Any dumpster on the site must be screened and comply
with Section 36-523 of the City’s Zoning Ordinance.
Any new lighting must be low-level and directed away from adjacent properties.
The abutting R-2 zoned property to the north is owned by the applicant. However,
a screen/buffer must be placed along the north property line.
All landscaping shall comply with Chapter 15 of the City of Little Rock Landscaping
Ordinance. Any variance from the landscape ordinance must be approved by the
Little Rock City Beautiful Commission.
Staff is supportive of the requested PD-C zoning. To staff’s knowledge there are
no outstanding technical issues with this application. Staff feels the proposed use
is compatible and similar to the development pattern in the area. The proposed
auto sales use is located along Mabelvale Pike (minor arterial). The area contains
a mixture of zoning and uses. Staff feels the proposed use will have no adverse
impact on the surrounding properties.
I. STAFF RECOMMENDATION:
Staff recommends approval of the requested PD-C zoning, subject to compliance
with the comments and conditions outlined in paragraphs D, E, and F, and the staff
analysis, of the agenda and staff report.
PLANNING COMMISSION UPDATE: (NOVEMBER 13, 2025)
The applicant was present. There were no persons registered in opposition. Staff
presented the item, and a recommendation of approval as outlined in the “staff
analysis” above. The item remained on the Consent Agenda for Approval. The vote
was (7) ayes, (0) nays, (3) absent, and (1) open position. The motion passed. The
application was approved.