HomeMy WebLinkAboutS-1756 ApplicationNAME PLANNING COMMISSION REVIEW CENTRAL ARKANSAS WATER 27 August 2015 TYPE ISSUE COMMENTS JLM CHILD HEALTH Z-1854-E All Central Arkansas Water requirements in MANAGEMENT REVISED SHORT effect at the time of request for water service FORM PID must be met. The Little Rock Fire Department needs to evaluate this site to determine whether additional public and/or private fire hydrant(s) will be required. If additional fire hydrant(s) are required, they will be installed at the Developer's expense. Please submit plans for water facilities and/or fire protection system to Central Arkansas Water for review. Plan revisions may be required after additional review. Contact Central Arkansas Water regarding procedures for installation of water facilities and/or fire service. Approval of plans by the Arkansas Department of Health Engineering Division and Little Rock Fire Department is required. A Capital Investment Charge based on the size of meter connection(s) will apply to this project in addition to normal charges. This fee will apply to all connections including metered connections off the private fire system. If there are facilities that need to be adjusted and/or relocated, contact Central Arkansas Water. That work would be done at the expense of the developer. Contact Central Arkansas Water regarding the size and location of the water meter. Due to the nature of this facility, installation of an approved reduced pressure zone backflow preventer assembly (RPZ) is required on the domestic water service. This assembly must be installed prior to the first point of use. Central Arkansas Water (CAW) requires that upon installation of the RPZA, successful tests of the assembly must be completed by a Certified Assembly Tester licensed by the State of Arkansas and approved by CAW. The test results must be sent to CAW's Cross Connection Section within ten days of installation and annually thereafter. Contact the Cross Connection Section at 377-1226 if you would like to NAME TYPE ISSUE COMMENTS discuss backflow prevention requirements for this project. The facilities on -site will be private. When meters are planned off private lines, private facilities shall be installed to Central Arkansas Water's material and construction specifications and installation will be inspected by an engineer, licensed to practice in the State of Arkansas. Execution of Customer Owned Line Agreement is required. Fire sprinkler systems which do not contain additives such as antifreeze shall be isolated with a double detector check valve assembly. If additives are used, a reduced pressure zone backflow preventer shall be required. This development will have minor impact on the existing water distribution system. Proposed water facilities will be sized to provide adequate pressure and fire protection. 2 NAME TYPE ISSUE COMMENTS ISOM SHORT FORM PD-O Z-9064 All Central Arkansas Water requirements in effect at the time of request for water service must be met. The Little Rock Fire Department needs to evaluate this site to determine whether additional public and/or private fire hydrant(s) will be required. If additional fire hydrant(s) are required, they will be installed at the Developer's expense. Please submit plans for water facilities and/or fire protection system to Central Arkansas Water for review. Plan revisions may be required after additional review. Contact Central Arkansas Water regarding procedures for installation of water facilities and/or fire service. Approval of plans by the Arkansas Department of Health Engineering Division and Little Rock Fire Department is required. A Capital Investment Charge based on the size of meter connection(s) will apply to this project in addition to normal charges. This fee will apply to all connections including metered connections off the private fire system. If there are facilities that need to be adjusted and/or relocated, contact Central Arkansas Water. That work would be done at the expense of the developer. Contact Central Arkansas Water regarding the size and location of the water meter. Due to the nature of this facility, installation of an approved reduced pressure zone backflow preventer assembly (RPZ) is required on the domestic water service. This assembly must be installed prior to the first point of use. Central Arkansas Water (CAW) requires that upon installation of the RPZA, successful tests of the assembly must be completed by a Certified Assembly Tester licensed by the State of Arkansas and approved by CAW. The test results must be sent to CAW's Cross Connection Section within ten days of installation and annually thereafter. Contact the Cross Connection Section at 377-1226 if you would like to discuss backflow prevention requirements for this project. The facilities on -site will be private. When meters are planned off private lines, private KI NAME TYPE ISSUE COMMENTS facilities shall be installed to Central Arkansas Water's material and construction specifications and installation will be inspected by an engineer, licensed to practice in the State of Arkansas. Execution of Customer Owned Line Agreement is required. Fire sprinkler systems which do not contain additives such as antifreeze shall be isolated with a double detector check valve assembly. If additives are used, a reduced pressure zone backflow preventer shall be required. This development will have minor impact on the existing water distribution system. Proposed water facilities will be sized to provide adequate pressure and fire protection. 4 NAME BUTLER SHORT FORM PD-C TYPE ISSUE Z-5234-C COMMENTS All Central Arkansas Water requirements in effect at the time of request for water service must be met. The Little Rock Fire Department needs to evaluate this site to determine whether additional public and/or private fire hydrant(s) will be required. If additional fire hydrant(s) are required, they will be installed at the Developer's expense. Please submit plans for water facilities and/or fire protection system to Central Arkansas Water for review. Plan revisions may be required after additional review. Contact Central Arkansas Water regarding procedures for installation of water facilities and/or fire service. Approval of plans by the Arkansas Department of Health Engineering Division and Little Rock Fire Department is required. If there are facilities that need to be adjusted and/or relocated, contact Central Arkansas Water. That work would be done at the expense of the developer. Contact Central Arkansas Water regarding the size and location of the water meter. Due to the nature of this facility, installation of an approved reduced pressure zone backflow preventer assembly (RPZ) is required on the domestic water service. This assembly must be installed prior to the first point of use. Central Arkansas Water (CAW) requires that upon installation of the RPZA, successful tests of the assembly must be completed by a Certified Assembly Tester licensed by the State of Arkansas and approved by CAW. The test results must be sent to CAW's Cross Connection Section within ten days of installation and annually thereafter. Contact the Cross Connection Section at 377-1226 if you would like to discuss backflow prevention requirements for this project. The facilities on -site will be private. When meters are planned off private lines, private facilities shall be installed to Central Arkansas Water's material and construction specifications and installation will be inspected by an engineer, licensed to practice in the State of Arkansas. Execution of Customer Owned Line Agreement is required. I.7 NAME TYPE ISSUE COMMENTS Fire sprinkler systems which do not contain additives such as antifreeze shall be isolated with a double detector check valve assembly. If additives are used, a reduced pressure zone backflow preventer shall be required. This development will have minor impact on the existing water distribution system. Proposed water facilities will be sized to provide adequate pressure and fire protection. lj NAME TYPE ISSUE COMMENTS THE GREEN HOUSE COTTAGES Z-9063 All Central Arkansas Water requirements in OF POPLAR GROVE LONG effect at the time of request for water service FORM PD-R must be met. The Little Rock Fire Department needs to evaluate this site to determine whether additional public and/or private fire hydrant(s) will be required. If additional fire hydrant(s) are required, they will be installed at the Developer's expense. Please submit plans for water facilities and/or fire protection system to Central Arkansas Water for review. Plan revisions may be required after additional review. Contact Central Arkansas Water regarding procedures for installation of water facilities and/or fire service. Approval of plans by the Arkansas Department of Health Engineering Division and Little Rock Fire Department is required. If there are facilities that need to be adjusted and/or relocated, contact Central Arkansas Water. That work would be done at the expense of the developer. Contact Central Arkansas Water regarding the size and location of the water meter. Due to the nature of this facility, installation of an approved reduced pressure zone backflow preventer assembly (RPZ) is required on the domestic water service. This assembly must be installed prior to the first point of use. Central Arkansas Water (CAW) requires that upon installation of the RPZA, successful tests of the assembly must be completed by a Certified Assembly Tester licensed by the State of Arkansas and approved by CAW. The test results must be sent to CAW's Cross Connection Section within ten days of installation and annually thereafter. Contact the Cross Connection Section at 377-1226 if you would like to discuss backflow prevention requirements for this project. The facilities on -site will be private. When meters are planned off private lines, private facilities shall be installed to Central Arkansas Water's material and construction specifications and installation will be inspected by an engineer, licensed to practice in the State of Arkansas. Execution of Customer Owned Line Agreement is required. NAME TYPE ISSUE COMMENTS Fire sprinkler systems which do not contain additives such as antifreeze shall be isolated with a double detector check valve assembly. If additives are used, a reduced pressure zone backflow preventer shall be required. This development will have minor impact on the existing water distribution system. Proposed water facilities will be sized to provide adequate pressure and fire protection. 8 NAME TYPE ISSUE COMMENTS THE VILLAGE AT RAHLING Z-6323-U ROAD LOT 13 SHORT FORM PCD All Central Arkansas Water requirements in effect at the time of request for water service must be met. The Little Rock Fire Department needs to evaluate this site to determine whether additional public and/or private fire hydrant(s) will be required. If additional fire hydrant(s) are required, they will be installed at the Developer's expense. Please submit plans for water facilities and/or fire protection system to Central Arkansas Water for review. Plan revisions may be required after additional review. Contact Central Arkansas Water regarding procedures for installation of water facilities and/or fire service. Approval of plans by the Arkansas Department of Health Engineering Division and Little Rock Fire Department is required. A Capital Investment Charge based on the size of meter connection(s) will apply to this project in addition to normal charges. This fee will apply to all connections including metered connections off the private fire system. If there are facilities that need to be adjusted and/or relocated, contact Central Arkansas Water. That work would be done at the expense of the developer. Contact Central Arkansas Water regarding the size and location of the water meter. Due to the nature of this facility, installation of an approved reduced pressure zone backflow preventer assembly (RPZ) is required on the domestic water service. This assembly must be installed prior to the first point of use. Central Arkansas Water (CAW) requires that upon installation of the RPZA, successful tests of the assembly must be completed by a Certified Assembly Tester licensed by the State of Arkansas and approved by CAW. The test results must be sent to CAW's Cross Connection Section within ten days of installation and annually thereafter. Contact the Cross Connection Section at 377-1226 if you would like to discuss backflow prevention requirements for this project. The facilities on -site will be private. When meters are planned off private lines, private NAME TYPE ISSUE COMMENTS facilities shall be installed to Central Arkansas Water's material and construction specifications and installation will be inspected by an engineer, licensed to practice in the State of Arkansas. Execution of Customer Owned Line Agreement is required. Fire sprinkler systems which do not contain additives such as antifreeze shall be isolated with a double detector check valve assembly. If additives are used, a reduced pressure 10 NAME TYPE ISSUE PLAZA MEXICANA LONG FORM Z-9061 PID COMMENTS All Central Arkansas Water requirements in effect at the time of request for water service must be met. The Little Rock Fire Department needs to evaluate this site to determine whether additional public and/or private fire hydrant(s) will be required. If additional fire hydrant(s) are required, they will be installed at the Developer's expense. Please submit plans for water facilities and/or fire protection system to Central Arkansas Water for review. Plan revisions may be required after additional review. Contact Central Arkansas Water regarding procedures for installation of water facilities and/or fire service. Approval of plans by the Arkansas Department of Health Engineering Division and Little Rock Fire Department is required. If there are facilities that need to be adjusted and/or relocated, contact Central Arkansas Water. That work would be done at the expense of the developer. Contact Central Arkansas Water regarding the size and location of the water meter. Due to the nature of this facility, installation of an approved reduced pressure zone backflow, preventer assembly (RPZ) is required on the domestic water service. This assembly must be installed prior to the first point of use. Central Arkansas Water (CAW) requires that upon installation of the RPZA, successful tests of the assembly must be completed by a Certified Assembly Tester licensed by the State of Arkansas and approved by CAW. The test results must be sent to CAW's Cross Connection Section within ten days of installation and annually thereafter. Contact the Cross Connection Section at 377-1226 if you would like to discuss backflow prevention requirements for this project. The facilities on -site will be private. When meters are planned off private lines, private facilities shall be installed to Central Arkansas Water's material and construction specifications and installation will be inspected by an engineer, licensed to practice in the State of Arkansas. Execution of Customer Owned Line Agreement is required. 11 NAME TYPE ISSUE COMMENTS Fire sprinkler systems which do not contain additives such as antifreeze shall be isolated with a double detector check valve assembly. If additives are used, a reduced pressure zone backflow preventer shall be required. This development will have minor impact on the existing water distribution system. Proposed water facilities will be sized to provide adequate pressure and fire protection. 12 NAME TYPE ISSUE COMMENTS LAMARCHE GARDEN S-1280-P The Little Rock Fire Department needs to PRELIMINARY PLAT evaluate this site to determine whether additional public and/or private fire hydrant(s) will be required. If additional fire hydrant(s) are required, they will be installed at the Developer's expense. Please submit plans for water facilities and/or fire protection system to Central Arkansas Water for review. Plan revisions may be required after additional review. Contact Central Arkansas Water regarding procedures for installation of water facilities and/or fire service. Approval of plans by the Arkansas Department of Health Engineering Division and Little Rock Fire Department is required. A Capital Investment Charge based on the size of meter connection(s) will apply to this project in addition to normal charges. This fee will apply to all connections including metered connections off the private fire system. If there are facilities that need to be adjusted and/or relocated, contact Central Arkansas Water. That work would be done at the expense of the developer. Contact Central Arkansas Water regarding the size and location of the water meter. Due to the nature of this facility, installation of an approved reduced pressure zone backflow preventer assembly (RPZ) is required on the domestic water service. This assembly must be installed prior to the first point of use. Central Arkansas Water (CAW) requires that upon installation of the RPZA, successful tests of the assembly must be completed by a Certified Assembly Tester licensed by the State of Arkansas and approved by CAW. The test results must be sent to CAW's Cross Connection Section within ten days of installation and annually thereafter. Contact the Cross Connection Section at 377-1226 if you would like to discuss backflow prevention requirements for this project. The facilities on -site will be private. When meters are planned off private lines, private facilities shall be installed to Central Arkansas Water's material and construction specifications and installation will be inspected by an engineer, licensed to 13 NAME TYPE ISSUE COMMENTS practice in the State of Arkansas. Execution of Customer Owned Line Agreement is required. Fire sprinkler systems which do not contain additives such as antifreeze shall be isolated with a double detector check valve assembly. If additives are used, a reduced pressure zone backflow preventer shall be required. This development will have minor impact on the existing water distribution system. Proposed water facilities will be sized to provide adequate pressure and fire protection. 14 NAME TYPE ISSUE COMMENTS NORTHWEST TERRITORY LOT Z-8043-C The Little Rock Fire Department needs to 10 SHORT FORM PCD evaluate this site to determine whether additional public and/or private fire hydrant(s) will be required. If additional fire hydrant(s) are required, they will be installed at the Developer's expense. Please submit plans for water facilities and/or fire protection system to Central Arkansas Water for review. Plan revisions may be required after additional review. Contact Central Arkansas Water regarding procedures for installation of water facilities and/or fire service. Approval of plans by the Arkansas Department of Health Engineering Division and Little Rock Fire Department is required. A Capital Investment Charge based on the size of meter connection(s) will apply to this project in addition to normal charges. This fee will apply to all connections including metered connections off the private fire system. If there are facilities that need to be adjusted and/or relocated, contact Central Arkansas Water. That work would be done at the expense of the developer. Contact Central Arkansas Water regarding the size and location of the water meter. Due to the nature of this facility, installation of an approved reduced pressure zone backflow preventer assembly (RPZ) is required on the domestic water service. This assembly must be installed prior to the first point of use. Central Arkansas Water (CAW) requires that upon installation of the RPZA, successful tests of the assembly must be completed by a Certified Assembly Tester licensed by the State of Arkansas and approved by CAW. The test results must be sent to CAW's Cross Connection Section within ten days of installation and annually thereafter. Contact the Cross Connection Section at 377-1226 if you would like to discuss backflow prevention requirements for this project. The facilities on -site will be private. When meters are planned off private lines, private facilities shall be installed to Central Arkansas Water's material and construction specifications and installation will be inspected by an engineer, licensed to 15 NAME TYPE ISSUE COMMENTS practice in the State of Arkansas. Execution of Customer Owned Line Agreement is required. Fire sprinkler systems which do not contain additives such as antifreeze shall be isolated with a double detector check valve assembly. If additives are used, a reduced pressure zone backflow preventer shall be required. This development will have minor impact on the existing water distribution system. Proposed water facilities will be sized to provide adequate pressure and fire protection. 16 NAME TYPE ISSUE COMMENTS THE VILLAGE AT RAHLING Z-6323-V The Little Rock Fire Department needs to ROAD LOT 1C REVISED PCD evaluate this site to determine whether additional public and/or private fire hydrant(s) will be required. If additional fire hydrant(s) are required, they will be installed at the Developer's expense. Please submit plans for water facilities and/or fire protection system to Central Arkansas Water for review. Plan revisions may be required after additional review. Contact Central Arkansas Water regarding procedures for installation of water facilities and/or fire service. Approval of plans by the Arkansas Department of Health Engineering Division and Little Rock Fire Department is required. A Capital Investment Charge based on the size of meter connection(s) will apply to this project in addition to normal charges. This fee will apply to all connections including metered connections off the private fire system. If there are facilities that need to be adjusted and/or relocated, contact Central Arkansas Water. That work would be done at the expense of the developer. Contact Central Arkansas Water regarding the size and location of the water meter. Due to the nature of this facility, installation of an approved reduced pressure zone backflow, preventer assembly (RPZ) is required on the domestic water service. This assembly must be installed prior to the first point of use. Central Arkansas Water (CAW) requires that upon installation of the RPZA, successful tests of the assembly must be completed by a Certified Assembly Tester licensed by the State of Arkansas and approved by CAW. The test results must be sent to CAW's Cross Connection Section within ten days of installation and annually thereafter. Contact the Cross Connection Section at 377-1226 if you would like to discuss backflow prevention requirements for this project. The facilities on -site will be private. When meters are planned off private lines, private facilities shall be installed to Central Arkansas Water's material and construction specifications and installation will be inspected by an engineer, licensed to 17 NAME TYPEISSUE COMMENTS practice in the State of Arkansas_ Execution of Customer Owned Line Agreement is required. Fire sprinkler systems which do not contain additives such as antifreeze shall be isolated with a double detector check valve assembly. If additives are used, a reduced pressure zone backflow preventer shall be required. This development will have minor impact on the existing water distribution system. Proposed water facilities will be sized to provide adequate pressure and fire protection. 18 NAME TYPE ISSUE COMMENTS 65TH STREET SELF STORAGE S-1755 The Little Rock Fire Department needs to SUBDIVISION SITE PLAN evaluate this site to determine whether REVIEW additional public and/or private fire hydrant(s) will be required. If additional fire hydrant(s) are required, they will be installed at the Developer's expense. Please submit plans for water facilities and/or fire protection system to Central Arkansas Water for review. Plan revisions may be required after additional review. Contact Central Arkansas Water regarding procedures for installation of water facilities and/or fire service. Approval of plans by the Arkansas Department of Health Engineering Division and Little Rock Fire Department is required. A Capital Investment Charge based on the size of meter connection(s) will apply to this project in addition to normal charges. This fee will apply to all connections including metered connections off the private fire system. If there are facilities that need to be adjusted and/or relocated, contact Central Arkansas Water. That work would be done at the expense of the developer. Contact Central Arkansas Water regarding the size and location of the water meter. Due to the nature of this facility, installation of an approved reduced pressure zone backflow preventer assembly (RPZ) is required on the domestic water service. This assembly must be installed prior to the first point of use. Central Arkansas Water (CAW) requires that upon installation of the RPZA, successful tests of the assembly must be completed by a Certified Assembly Tester licensed by the State of Arkansas and approved by CAW. The test results must be sent to CAW's Cross Connection Section within ten days of installation and annually thereafter. Contact the Cross Connection Section at 377-1226 if you would like to discuss backflow prevention requirements for this project. The facilities on -site will be private. When meters are planned off private lines, private facilities shall be installed to Central Arkansas Water's material and construction specifications and installation will be inspected by an engineer, licensed to 19 NAME TYPE ISSUE COMMENTS practice in the State of Arkansas. Execution of Customer Owned Line Agreement is required. Fire sprinkler systems which do not contain additives such as antifreeze shall be isolated with a double detector check valve assembly. If additives are used, a reduced pressure zone backflow preventer shall be required. This development will have minor impact on the existing water distribution system. Proposed water facilities will be sized to provide adequate pressure and fire protection. 481 NAME TYPE ISSUE COMMENTS LAKE NIXON SUBDIVISION SITE S-1756 The Little Rock Fire Department needs to PLAN REVIEW evaluate this site to determine whether additional public and/or private fire hydrant(s) will be required. If additional fire hydrant(s) are required, they will be installed at the Developer's expense. Please submit plans for water facilities and/or fire protection system to Central Arkansas Water for review. Plan revisions may be required after additional review. Contact Central Arkansas Water regarding procedures for installation of water facilities and/or fire service. Approval of plans by the Arkansas Department of Health Engineering Division and Little Rock Fire Department is required. A Capital Investment Charge based on the size of meter connection(s) will apply to this project in addition to normal charges. This fee will apply to all connections including metered connections off the private fire system. If there are facilities that need to be adjusted and/or relocated, contact Central Arkansas Water. That work would be done at the expense of the developer. Contact Central Arkansas Water regarding the size and location of the water meter. Due to the nature of this facility, installation of an approved reduced pressure zone backflow preventer assembly (RPZ) is required on the domestic water service. This assembly must be installed prior to the first point of use. Central Arkansas Water (CAW) requires that upon installation of the RPZA, successful tests of the assembly must be completed by a Certified Assembly Tester licensed by the State of Arkansas and approved by CAW. The test results must be sent to CAW's Cross Connection Section within ten days of installation and annually thereafter. Contact the Cross Connection Section at 377-1226 if you would like to discuss backflow prevention requirements for this project. The facilities on -site will be private. When meters are planned off private lines, private facilities shall be installed to Central Arkansas Water's material and construction specifications and installation will be inspected by an engineer, licensed to 21 NAME TYPEISSUE COMMENTS practice in the State of Arkansas. Execution of Customer Owned Line Agreement is required. Fire sprinkler systems which do not contain additives such as antifreeze shall be isolated with a double detector check valve assembly. If additives are used, a reduced pressure zone backflow preventer shall be required. This development will have minor impact on the existing water distribution system. Proposed water facilities will be sized to provide adequate pressure and fire protection. 22 NAME TYPE ISSUE COMMENTS NORMANDY PARK SHORT FORM PD-R Z-9062 All Central Arkansas Water requirements in effect at the time of request for water service must be met. The Little Rock Fire Department needs to evaluate this site to determine whether additional public and/or private fire hydrant(s) will be required. If additional fire hydrant(s) are required, they will be installed at the Developer's expense. Please submit plans for water facilities and/or fire protection system to Central Arkansas Water for review. Plan revisions may be required after additional review. Contact Central Arkansas Water regarding procedures for installation of water facilities and/or fire service. Approval of plans by the Arkansas Department of Health Engineering Division and Little Rock Fire Department is required. If there are facilities that need to be adjusted and/or relocated, contact Central Arkansas Water. That work would be done at the expense of the developer. Contact Central Arkansas Water regarding the size and location of the water meter. Due to the nature of this facility, installation of an approved reduced pressure zone backflow preventer assembly (RPZ) is required on the domestic water service. This assembly must be installed prior to the first point of use. Central Arkansas Water (CAW) requires that upon installation of the RPZA, successful tests of the assembly must be completed by a Certified Assembly Tester licensed by the State of Arkansas and approved by CAW. The test results must be sent to CAW's Cross Connection Section within ten days of installation and annually thereafter. Contact the Cross Connection Section at 377-1226 if you would like to discuss backflow prevention requirements for this project. The facilities on -site will be private. When meters are planned off private lines, private facilities shall be installed to Central Arkansas Water's material and construction specifications and installation will be inspected by an engineer, licensed to practice in the State of Arkansas. Execution of Customer Owned Line Agreement is required. 23 NAME TYPE ISSUE COMMENTS Fire sprinkler systems which do not contain additives such as antifreeze shall be isolated with a double detector check valve assembly. If additives are used, a reduced pressure zone backflow preventer shall be required. This development will have minor impact on the existing water distribution system. Proposed water facilities will be sized to provide adequate pressure and fire protection. 24 NAME TYPE ISSUE COMMENTS CHENAL VELLEY TRACT 4A, 413, S-867-CCCCCCCC All Central Arkansas Water requirements in AND 8 REVISED PRELINIMARY effect at the time of request for water service PLAT must be met. The Little Rock Fire Department needs to evaluate this site to determine whether additional public and/or private fire hydrant(s) will be required. If additional fire hydrant(s) are required, they will be installed at the Developer's expense. Please submit plans for water facilities and/or fire protection system to Central Arkansas Water for review. Plan revisions may be required after additional review. Contact Central Arkansas Water regarding procedures for installation of water facilities and/or fire service. Approval of plans by the Arkansas Department of Health Engineering Division and Little Rock Fire Department is required. A Capital Investment Charge based on the size of meter connection(s) will apply to this project in addition to normal charges. This fee will apply to all connections including metered connections off the private fire system. If there are facilities that need to be adjusted and/or relocated, contact Central Arkansas Water. That work would be done at the expense of the developer. Contact Central Arkansas Water regarding the size and location of the water meter. Due to the nature of this facility, installation of an approved reduced pressure zone backflow preventer assembly (RPZ) is required on the domestic water service. This assembly must be installed prior to the first point of use. Central Arkansas Water (CAW) requires that upon installation of the RPZA, successful tests of the assembly must be completed by a Certified Assembly Tester licensed by the State of Arkansas and approved by CAW. The test results must be sent to CAW's Cross Connection Section within ten days of installation and annually thereafter. Contact the Cross Connection Section at 377-1226 if you would like to discuss backflow prevention requirements for this project. The facilities on -site will be private. When meters are planned off private lines, private 25 NAME TYPE ISSUE COMMENTS facilities shall be installed to Central Arkansas Water's material and construction specifications and installation will be inspected by an engineer, licensed to practice in the State of Arkansas. Execution of Customer Owned Line Agreement is required. Fire sprinkler systems which do not contain additives such as antifreeze shall be isolated with a double detector check valve assembly. If additives are used, a reduced pressure zone backflow preventer shall be required. This development will have minor impact on the existing water distribution system. Proposed water facilities will be sized to provide adequate pressure and fire protection. 26 NAME TYPE ISSUE COMMENTS ARKANSAS SYSTEMS -TRACT 4 Z-6051-J LONG FORM PCD All Central Arkansas Water requirements in effect at the time of request for water service must be met. The Little Rock Fire Department needs to evaluate this site to determine whether additional public and/or private fire hydrant(s) will be required. If additional fire hydrant(s) are required, they will be installed at the Developer's expense. Please submit plans for water facilities and/or fire protection system to Central Arkansas Water for review. Plan revisions may be required after additional review. Contact Central Arkansas Water regarding procedures for installation of water facilities and/or fire service. Approval of plans by the Arkansas Department of Health Engineering Division and Little Rock Fire Department is required. A Capital Investment Charge based on the size of meter connection(s) will apply to this project in addition to normal charges. This fee will apply to all connections including metered connections off the private fire system. If there are facilities that need to be adjusted and/or relocated, contact Central Arkansas Water. That work would be done at the expense of the developer. Contact Central Arkansas Water regarding the size and location of the water meter. Due to the nature of this facility, installation of an approved reduced pressure zone backflow preventer assembly (RPZ) is required on the domestic water service. This assembly must be installed prior to the first point of use. Central Arkansas Water (CAW) requires that upon installation of the RPZA, successful tests of the assembly must be completed by a Certified Assembly Tester licensed by the State of Arkansas and approved by CAW. The test results must be sent to CAW's Cross Connection Section within ten days of installation and annually thereafter. Contact the Cross Connection Section at 377-1226 if you would like to discuss backflow prevention requirements for this project. The facilities on -site will be private. When meters are planned off private lines, private 27 NAME TYPE ISSUE COMMENTS facilities shall be installed to Central Arkansas Water's material and construction specifications and installation will be inspected by an engineer, licensed to practice in the State of Arkansas. Execution of Customer awned Line Agreement is required. Fire sprinkler systems which do not contain additives such as antifreeze shall be isolated with a double detector check valve assembly. If additives are used, a reduced pressure zone backflow preventer shall be required. This development will have minor impact on the existing water distribution system. Proposed water facilities will be sized to provide adequate pressure and fire protection. 28 Little Rock Wastewater Comments ' Project Number S-1280-P Project Name Project Type LaMarche Gardens Preliminary Plat Project Number S-1385-C Project Name Project Type Little North Fork Lots 13 Single Family Replat and 14 Project Number S-1755 Project Name Project Type 65th Street Self Storage Subdiv Site Plan Review Project Number S-1756 Project Name Project Type Lake Nixon Subdivision Subdiv Site Plan Review Project Number S-867-C Project Name Project Type Chenal Valley, Tract 4A, Preliminary Plat 4B, and 8 Project Number Z-5234-C Project Name Project Type Butler PD-C Planned Development Commercial Project Number Z-6051-J Project Name Project Type Arkansas Systems Tract 4 Planned Development Commercial Comment Made Sewer main extension required with easements if new sewer service is required for this project. Comment Made Sewer Available to this Project. Comment Made Sewer main extension required with easements if new sewer service is required for this project. Comment Made Outside Service Boundary, no comment. Comment Made Sewer Available to this project. Sewer Easement(s) must be retained at front of 4B Comment Made Sewer Available to this Project. Comment Made Sewer Available to this project. EAD Plan Review Required. Project Number Z-6323-U Project Name Project Type Comment Made The Village at Rahling Road Planned Development Commercial Sewer Available to this Project. Dumpster Enclosure Lot 13 shall not encroach on sewer easement. Tuesday, August 04, 2015 Page 1 of 2 Project Number Z-6323-V Project Name Project Type The Village at Rahling Road Planned Development Commercial Lot 1C Project Number Z-7854-E Project Name Project Type JLM Child Health Planned Development Industrial Management Project Number Z-8043-C Project Name Project Type Northwest Territory Lot 10 Planned Development Commercial Project Number Z-9061 Project Name Project Type Plaza Mexicana Planned Development Commercial Project Number Z-9062 Project Name Project Type Normandy Park Planned Development Residential Project Number Z-9063 Project Name Project Type The Green House Cottages Planned Development Residential of Poplar Grove Project Number Z-9064 Project Name Project Type ISOM Planned Development Office Comment Made Sewer Available to this Project. Comment Made Sewer Available to this Project. Comment Made Sewer Available to this project. Sewer Easement(s) must be retained; EAD Review Required if grease trap is needed. Comment Made Sewer Available to this project. EAD Plan Review Required. Comment Made Sewer Available to this Project. Comment Made Sewer main extension required with easements if new sewer service is required for this project. Comment Made Sewer main extension required with easements if new sewer service is required for this project. Address Not currently connected to sewer. Tuesday, August 04, 2015 Page 2 of 2 To: Dana Carney, Zoning & Subdivision Manager Date: 8-03-15 Donna James, Zoning Monte Moore, Subdivision From: Curtis Richey / Mark Alderfer: Building Codes Building Code Comment: Z-7854-E 5 Remington Cove No Comment Z-9064 3224 Shackleford Due to change in occupancy the facility must comply with all 2012 Arkansas Fire Prevention Codes. Contact Building Codes for an on -site inspection to review conditions and requirements. Curtis Richey at 501.371.4724; crichev@ little rock.or or Mark Alderfer at 501.371.4875; maiderfer littlerock.or . Z-5234-C 2708 / 2718 South Arch No Comment Z-9063 7713 (Canis Road Project is subject to full commercial plan review and approval prior to issuance of a building permit. For information on submittal requirements and the review process, contact a commercial plans examiner: Curtis Richey at 501.371.4724; crichev littierock.org or Mark Alderfer at 501,371.4875; malderfer littlerock.or . Z6323-U 40 Rahling Circle Project is subject to full commercial plan review and approval prior to issuance of a building permit. For information on submittal requirements and the review process, contact a commercial plans examiner: Curtis Richey at 501.371.4724; crichev@littlero_ck.org or Mark Alderfer at 501.371.4875; ma€derfer@littlerock.or . Z-9061 SW Corner of 65" & Scott Hamilton Project is subject to full commercial plan review and approval prior to issuance of a building permit. For information on submittal requirements and the review process, contact a commercial plans examiner: Curtis Richey at 501.371.4724; criche littlerock.or or Mark Alderfer at 501.371.4875; malderfer@iittlerock.org. S-1280-P LaMarche Drive East of Valley Falls Estates South of Gardens at Valley Falls No Comment Z-80463-C NW Corner of Cantrell & Chenal Project is subject to full commercial plan review and approval prior to issuance of a building permit. For information on submittal requirements and the review process, contact a commercial plans examiner: Curtis Richey at 501.371.4724; cricheV@Iittlerock.org or Mark Alderfer at 501.371.4875; malderfer@11ttlerock.orR. Z-6323-V Rahling Circle just south of Noah's Project is subject to full commercial plan review and approval prior to issuance of a building permit. For information on submittal requirements and the review process, contact a commercial plans examiner: Curtis Richey at 501.371.4724; crichev@littleLgLk.org or Mark Alderfer at 501.371.4875; malderfer@tittlerock.org. littlerock.org. 5-1755 4400 Block of 65"' Street Project is subject to full commercial plan review and approval prior to issuance of a building permit. For information on submittal requirements and the review process, contact a commercial plans examiner: Curtis Richey at 501.371.4724; cri chev@ little rock.or or Mark Alderfer at 501.371.4875; malderfer littlerock.or . Z-9062 NE Corner of R Street and Normandy Drive No Comment 5-867-CCCCCCCC NW Corner of Chenal and Rahling Road Project is subject to full commercial plan review and approval prior to issuance of a building permit. For information on submittal requirements and the review process, contact a commercial plans examiner: Curtis Richey at 501.371.4724; crichev Iittlerock.orR or Mark Alderfer at 501.371.4875; malderfer littlerack.or . Z-6051-! East side of Chenal Parkway and South of Systems Drive Project is subject to full commercial plan review and approval prior to issuance of a building permit. For information on submittal requirements and the review process, contact a commercial plans examiner: Curtis Richey at 501.371.4724; crichev@littlerock.oror Mark Alderfer at 501.371.4875; malderfer@littlerock.org. 5-1756 18500 Cooper Orbit No Comment 5-1385-C 14 and 16 Penny Lane No Comment Regards, Curtis Richey Commercial Plans Examiner Public Works Review Comments Planning Commission Board of Adjustment Agenda Date: 8-27-15 Z File Number LA-0065 Stagecoach and Baseline Timber Harvest Variance SE corner of Stagecoach Rd and Baseline Rd 1 Harvest activities must comply with state and federal forestry harvest techniques and code. Damage to offsite property must be repaired by the applicant in a timely manner. 2 Tree tops and debris generated from the harvest activity must be removed at the conclusion of harvest to reduce the potential fire hazard. Contact the Little Rock Fire Department for conditions and additional requirements. How will the tops and debris be removed? 3 Vegetation must be established on disturbed area within 21 days of completion of harvest activities. 4 A grading permit in accordance with section 29-186 (c) & (d) will be required prior to any land clearing or grading activities at the site. 5 The harvest activities shall be expeditously completed in a time frame not to exceed one (1) year in duration from the time work commences to installation of all final erosion control measures and vegetation. 6 All erosion and stabilization controls, including permanent vegetation are to be maintained by the responsible party for a period of 2 years following completion of site work. 7 Maintenance for the 2 year period shall be guaranteed through posting of cash, surety bond or letter of credit as referenced in Sec. 31-431(2) at the time of final inspection of the harvest and grading activities. 8 All required federal, state, and local permits and approvals shall be obtained prior to commencement of land alteration activities. 9 Public works staff must be contacted for inspection for final approval of site stabilization prior to acceptance and relinquishment of maintenance bond. 10 Provide location of vehicle tracking pad constructed per Little Rock Code Sec. 29-190(12). 11 Obtain permits for improvements within State Highway right-of-way from AHTD, District VI. Contact AHTD to determine if a permit is needed for a temporary access driveway to Stagecoach Rd and/or Baseline Rd. 12 Erosion controls must be installed to reduce discharge of polluted stormwater. The proposed erosion control devices must be shown on the harvest plan must be provided with a grading permit application at the time harvest is desired. 13 Is the interior of the property proposed to be clear cut? 14 Due to the existing sewer line and easement, contact Vince Hotho of the Little Rock Wastewater Utility at 501-688-1452 or 501-442-6042 prior to beginning harvest activities to obtain the special protection provisions. Z File Number S-1280-P LaMarche Garden Preliminary Plat LaMarche Dr E of Valley Falls Estates Friday, July 31, 2015 Page 1 of 8 I To comply with the Master Street Plan, LaMarche Garden Drive should be constructed to a residential street standard with 50 ft right-of-way and sidewalk on 1 side from LaMarche Drive to the west intersection of LaMarche Garden Loop. 2 Are the streets proposed to be public or private? 3 Repair or replace any curb and gutter or sidewalk that is damaged in the public right-of-way prior to occupancy. 4 A grading permit in accordance with section 29-186 (c) & (d) will be required prior to any land clearing or grading activities at the site. Other than residential subdivisions, site grading and drainage plans must be submitted and approved prior to the start of construction. Is the subdivision proposed to be phased? If phasing is desired, is a variance requested to advance grade future phases of construction with construction of phase 1? 5 Storm water detention ordinance applies to this property. 6 If disturbed area is 1 or more acres, obtain a NPDES storm water permit from the Arkansas Department of Environmental Quality prior to the start of construction. 7 Street lights are required by Section 31-403 of the LR code. Provide plans for approval to Traffic Engineering. Street lights must be installed prior to platting/certificate of occupancy. Contact Traffic Engr 379-1813 (Greg Simmons) for more info. 8 An emergency access easement should be provided to the public right-of-way. Using turn movement templates show the proposed emergecy access easement can be maneuvered by a firetruck (B-40). 9 The street name LaMarche Garden Drive should be changed to "court" or "cove" do to possible confusion with LaMarche Drive. 10 Provide a letter prepared by a registered engineer certifying the sight distance at the intersection(s) comply with 2004 AASHTO Green Book standards. Z File Number 5-1385-C Little North Fork Lots 13 & 14 14 & 16 Penny Lane 1 Repair or replace any curb and gutter or sidewalk that is damaged in the public right-of-way prior to occupancy. Z File Number 5-1755 65th Street Self Storage Subd Site Plan Review 4400 block of 65th Street 1 Repair or replace any curb and gutter or sidewalk that is damaged in the public right-of-way prior to occupancy. 2 All driveways shall be concrete aprons per City Ordinance. 3 A grading permit in accordance with section 29-186 (c) & (d) will be required prior to any land clearing or grading activities at the site. Other than residential subdivisions, site grading and drainage plans must be submitted and approved prior to the strt of construction. If the development is proposed to be phased, is a variance requested to grade future phases with construction of Phase 1? 4 All existing curb cuts not proposed to be used should be closed with new curb and gutter. 5 Storm water detention ordinance applies to this property. Show the proposed location for stormwater detention facilities on the plan. 6 If disturbed area is 1 or more acres, obtain a NPDES storm water permit from the Arkansas Department of Environmental Quality prior to the start of construction. Friday, July 31, 2015 Page 2 of 8 7 Driveway locations and widths do not meet the traffic access and circulation requirements of Sections 30-43 and 31-210. The driveway spacing from the side property line on an arterial street is 150 ft. A variance must be requested for the proposed driveway location. 8 Damage to public and private property due to hauling operations or operation of construction related equipment from a nearby construction site shall be repaired by the responsible party prior to issuance of a certificate of occupancy. 9 An additional curb cut will not be permitted for the proposed future development on the north adjacent to W. 65th St. Z File Number S-1756 Lake Nixon Subdivision Site Plan Review 18500 Cooper Orbit Road 0 No comments 2 No construction or building addition can occur within the public right-of-way. Z File Number S-867-CCCCCCCC Chenal Valley Tract 4A, 413, and 8 Rev Pre Plat Z File Number 5-867-CCCCCCCC Chenal Valley Tract 4A, 413, and 8 Rev Pre Plat NW corner of Chenal Parkway and Rahling Rd NW corner of Chenal Parkway and Rahling Rd 1 The proposed public street does not meet the Master Street Plan design standards for a commercial street. The street should be within 60 ft right-of-way and sidewalks on both sides. 2 Due to the limited properties served, the proposed street should be private and not public. If the street is proposed to be public, a turnaround or cul-de-sac must be provided where the street changes from public to private. 3 Repair or replace any curb and gutter or sidewalk that is damaged in the public right-of-way prior to occupancy. 4 Storm water detention ordinance applies to this property. 5 Street Improvement plans shall include signage and striping. Public Works must approve completed plans prior to construction. 6 Street lights are required by Section 31-403 of the LR code. Provide plans for approval to Traffic Engineering. Street lights must be installed prior to platting/certificate of occupancy. Contact Traffic Engr 379-1813 (Greg Simmons) for more info. 7 Damage to public and private property due to hauling operations or operation of construction related equipment from a nearby construction site shall be repaired by the responsible party prior to issuance of a certificate of occupancy. 8 The driveway accessing Chenal Parkway should continue to function as a right in/right out only and not provide a median cut for left turns movements. 9 Intersection of Chenal and Rahling carries significant amount of traffic and currently warrants dual left -turn lanes for the eastbound movement. Proposed full -access median opening will introduce additional conflict points in traffic flow thereby increasing the potential for crashes. 10 Proposed driveway on the eastside of Chenal Parkway will introduce an unsignalized intersection and may cause illegal turn movements from one drive to the other. 11 Wide medians with inadequate sight distance also make it very difficult to see oncoming traffic. The proposed triangular island in the median requires drivers to turn their heads more than 90 degrees to see gaps in traffic before merging. 12 Provide a letter prepared by a registered engineer certifying the sight distance at the intersection(s) comply with 2004 AASHTO Green Book standards. The driveway at the proposed median cut does not have adequate sight distance to the right due to the raised median. Z File Number Z-5234-C Butler PD-C 2708 & 2718 S. Arch St Friday, July 31, 2015 Page 3 of 8 I Repair or replace any curb and gutter or sidewalk that is damaged in the public right-of-way prior to occupancy. 2 All driveways shall be concrete aprons and constructed to ADA standards per City Ordinance. 3 Public Works, Civil Engineering staff should be contacted for inspection of all improvements within the right-of-way. 4 With residential properties located on 2 sides of the parking lot development, provide a Sketch Grading and Drainage Plan per Sec. 29-186. 5 If access is desired to the alley from the parking lot, the alley adjacent to the subject property should be overlayed with asphalt. Z File Number Z-6051-J Arkansas Systems -Tract 4 PCD Chenal Parkway & Systems Drive submitted site? 1 Chenal Parkway is classified on the Master Street Plan as a principal arterial. Dedication of right-of- way to 55 feet from centerline will be required. 2 Sidewalks with appropriate handicap ramps are required in accordance with Sec. 31-175 of the Little Rock Code and the Master Street Plan. Sidewalks should be installed along Chenal Parkway. 3 Repair or replace any curb and gutter or sidewalk that is damaged in the public right-of-way prior to occupancy. 4 A grading permit in accordance with section 29-186 (c) & (d) will be required prior to any land clearing or grading activities at the site. Site grading, and drainage plans will need to be and approved prior to the start of construction. Is advanced grading requested to occur on the 5 Storm water detention ordinance applies to this property. Show the proposed location for stormwater detention facilities on the plan. 6 If disturbed area is 1 or more acres, obtain a NPDES storm water permit from the Arkansas Department of Environmental Quality prior to the start of construction. 7 Alteration of the water course will require approval from the Little Rock District of the US Army Corps of Engineers prior to start of work. 8 The existing curb along Arkansas Systems Drive and the median at Chenal Parkway has been painted red and signed as a "Fire Lane". No records show the public street functions as a fire lane. The paint should be removed. 9 A special Grading Permit for Flood Hazard Areas will be required per Sec. 8-283 prior to construction. 10 The minimum Finish Floor elevation of at least 1 ft above the proposed base flood elevation is required to be shown on plat and grading plans for Lot 4A and4B. At time of construction and prior to issuance of the final certificate of occupancy, an elevation certificate will be required to be provided. 1 I In accordance with Section 31-176, floodway areas must be shown as floodway easements or be dedicated to the public. In addition, a 25 foot wide access easement is required adjacent to the floodway boundary. 12 The base flood elevations show to be below the bottom of the ditch. The majority of the channel adjacent to the subject property shows to be in the floodplain with the channel upstream shown to be in the floodway. Prior to issuance of a grading permit, a "No Rise Certification" based on the proposed conditions must be provided to staff for review and approval. Friday, July 31, 2015 Page 4 of 8 13 Per City code, Section 36-341, vehicle parking is restricted from being provided in the floodway. A variance must be requested? 14 Damage to public and private property due to hauling operations or operation of construction related equipment from a nearby construction site shall be repaired by the responsible party prior to issuance of a certificate of occupancy. 15 Design plans for piping system must be submitted to staff for approval prior to issuance of a grading permit. The proposed piping must be placed within a drainage easement. What is the proposed ditch section design? 16 Street lights are required by Section 31-403 of the LR code. Provide plans for approval to Traffic Engineering. Street lights must be installed prior to platting/certificate of occupancy. Contact Traffic Engr 379-1813 (Greg Simmons) for more info. Streetlights do not appear to be installed along Arkansas Systems Drive. Z File Number Z-6323-U The Village at Rahling Road, Lot 13 PCD 40 Rahling Circle 1 Repair or replace any curb and gutter or sidewalk that is damaged in the private right-of-way prior to occupancy. 2 A grading permit in accordance with section 29-186 (c) & (d) will be required prior to any land clearing or grading activities at the site. Other than residential subdivisions, site grading and drainage plans must be submitted and approved prior to the start of construction. 3 If disturbed area is 1 or more acres, obtain a NPDES storm water permit from the Arkansas Department of Environmental Quality prior to the start of construction. 4 Prior to construction of retaining walls, a engineer's certification of design and plans must be submitted to Public Works for approval. After construction, an as -built certification is required for construction of the retaining wall. 5 Driveway locations and widths do not meet the traffic access and circulation requirements of Sections 30-43 and 31-210. With the proposed shared access driveway and also a second driveway, the second driveway should be located at least 125 ft from the side property line. A variance must be requested for the location of the second driveway. Z File Number Z-6323-V The Village at Rahling Road, Lot I PCD Rahling Circle S ofNoah's Facility 1 Repair or replace any curb and gutter or sidewalk that is damaged in the public right-of-way prior to occupancy. 2 If disturbed area is 1 or more acres, obtain a NPDES storm water permit from the Arkansas Department of Environmental Quality prior to the start of construction. Z File Number Z-7854-E JLM Child Health Management Rev PID 5 Remington Cove 1 Repair or replace any curb and gutter or sidewalk that is damaged in the public right-of-way prior to occupancy. 2 Storm water detention ordinance applies to this property. Show the proposed location for stormwater detention facilities on the plan. Friday, July 31, 2015 Page 5 of 8 Z File Number Z-8043-C Northwest Territory Lot 10 PCD NE Corner Cantrell Rd and Chenal Parkway 1 Sidewalks with appropriate handicap ramps are required in accordance with Sec. 31-175 of the Little Rock Code and the Master Street Plan. 2 Repair or replace any curb and gutter or sidewalk that is damaged in the public right-of-way prior to occupancy. 3 A grading permit in accordance with section 29-186 (c) & (d) will be required prior to any land clearing or grading activities at the site. Other than residential subdivisions, site grading and drainage plans must be submitted and approved prior to the start of construction. 4 Storm water detention ordinance applies to this property. 5 If disturbed area is 1 or more acres, obtain a NPDES storm water permit from the Arkansas Department of Environmental Quality prior to the start of construction. 6 Obtain permits for improvements within State Highway right-of-way from AHTD, District VI. 7 Street Improvement plans shall include signage and striping. The pedestrian striping should be reapplied on Hwy 10 due to the deterioration of the existing striping. Public Works must approve completed plans prior to construction. 8 Damage to public and private property due to hauling operations or operation of construction related equipment from a nearby construction site shall be repaired by the responsible party prior to issuance of a certificate of occupancy. Z File Number Z-9061 Plaza Mexicana PID SW Corner 65th St and Scott Hamilton Dr 1 WB left turns will not be allowed into the site from W. 65th St at the east driveway without construction of a center turn lane beginning at the W. 65th St/Scott Hamilton Dr. intersection. 1 A 20 feet radial dedication of right-of-way is required at the intersection of W. 65th St & Scott Hamilton Dr. 2 Repair or replace any curb and gutter or sidewalk that is damaged in the public right-of-way prior to occupancy. 3 A grading permit in accordance with section 29-186 (c) & (d) will be required prior to any land clearing or grading activities at the site. Other than residential subdivisions, site grading and drainage plans must be submitted and approved prior to the start of construction. Is a variance requested to advance grade phased construction. If desired, provide proposed phasing plan. 4 Storm water detention ordinance applies to this property. Show the proposed location for stormwater detention facilities on the plan. 5 If disturbed area is 1 or more acres, obtain a NPDES storm water permit from the Arkansas Department of Environmental Quality prior to the start of construction. 6 The striped median in Scott Hamilton Drive will be required to be modified for left turn movements to meet AASHTO and MUTCD standards at the time of building permit. 7 Damage to public and private property due to hauling operations or operation of construction related equipment from a nearby construction site shall be repaired by the responsible party prior to issuance of a certificate of occupancy. Friday, July 31, 2015 Page 6 of 8 Z File Number Z-9062 Normandy Park PD-R NW corner of R St & Normandy St. I A 20 feet radial dedication of right-of-way is required at the intersection of Normandy St. and R St. 2 With site development, provide design of street conforming to the Master Street Plan. Construct one-half street improvement to R St. with 5 ft sidewalk with planned development. The new back of curb should connect with the existing curb to the east and maintain the same width for the entire property frontage. 3 Provide grading and drainage plan to show the amount of remaining front yard when retaining walls, steps and sidewalk is provided for the parallel parking spacing. 4 A grading permit in accordance with section 29-186 (c) & (d) will be required prior to any land clearing or grading activities at the site. Other than residential subdivisions, site grading and drainage plans must be submitted and approved prior to the start of construction. 5 Damage to public and private property due to hauling operations or operation of construction related equipment from a nearby construction site shall be repaired by the responsible party prior to issuance of a certificate of occupancy. 6 Prior to construction of retaining wails, a engineer's certification of design and plans must be submitted to Public Works for approval. After construction, an as -built certification is required for construction of the retaining wall. 7 Provide grading and drainage plan to show the amount of remaining front yard when retaining walls, steps and sidewalk is proivded for the parallel parking spacing. 8 The existing street has a width of 15 ft. Fire code requires the minium street width to be 20 ft. 9 Staff does not recommend the construction of parallel parking spaces on a 15 ft one way street. Z File Number Z-9063 The Green House Cottages of Poplar Grove PD-R 7713 Kanis Rd Z File Number Z-9063 The Green House Cottages of Poplar Grove PD-R 7713 Kanis Rd 1 Kanis Rd is classified on the Master Street Plan as a minor arterial. A dedication of right-of-way 45 feet from centerline will be required. 2 With site development, provide design of street conforming to the Master Street Plan. Construct one-half street improvement to Kanis Road including 5-foot sidewalks with planned development. The proposed plan for widening Kanis Road shows Kanis Road to shift to the south adjacent to this property and neighboring properties with the construction of a possible retaining wall to the east. With that being the case prior to issuance of a building permit, in -lieu of construction a payment should be made to the City of Little Rock for the cost of widening Kanis Road to the Master Street Plan standard. The estimated costs will be reviewed and approved by staff. 3 A grading permit in accordance with section 29-186 (c) & (d) will be required prior to any land clearing or grading activities at the site. Other than residential subdivisions, site grading and drainage plans must be submitted and approved prior to the start of construction, If a variance is requested to advance grade future phases with Phase 1, provide a phasing plan. 4 Storm water detention ordinance applies to this property. 5 If disturbed area is t or more acres, obtain a NPDES storm water permit from the Arkansas Department of Environmental Quality prior to the start of construction. 6 Street Improvement plans shall include signage and striping. Public Works must approve completed plans prior to construction. 7 Street lights are required by Section 31-403 of the LR code. Provide plans for approval to Traffic Engineering. Street lights must be installed prior to platting/certificate of occupancy. Contact Traffic Engr 379-1813 (Greg Simmons) for more info. 8 Provide a letter prepared by a registered engineer certifying the sight distance at the intersection(s) comply with 2004 AASHTO Green Book standards can be achieved by proposed grading and clearing on the subject property and within the public right-of-way. A line of sight graphic should be provided. 9 Damage to public and private property due to hauling operations or operation of construction related equipment from a nearby construction site shall be repaired by the responsible party prior to issuance of a certificate of occupancy. 10 Provide proof of approval of construction of a detention pond and other driveway and parking improvements within the gas line easement. 11 Prior to construction of retaining walls, a engineer's certification of design and plans must be submitted to Public Works for approval. After construction, an as -built certification is required for construction of the retaining wall. Z File Number Z-9064 Isom PD-O 3224 Shackleford Pass 1 Due to the proposed use of the property, the Master Street Plan specifies that Shackleford Pass for the frontage of this property must meet commercial street standards. Dedicate right-of-way to 30 feet from centerline. 2 With site development, provide design of street conforming to the Master Street Plan. Construct one-half street improvement to Shackleford Pass including 5-foot sidewalks with planned development. The new curb should connect with the existing curb to the north and maintain the same width of 15.5 ft from centerline. 3 Remove portions of the existing fence along the north property line out of the right-of-way. 4 Damage to public and private property due to hauling operations or operation of construction related equipment from a nearby construction site shall be repaired by the responsible party prior to issuance of a certificate of occupancy. Friday, July 31, 2015 Page 8 of 8 MEMORANDUM TO: DONNA JAMES, SUBDIVISION ADMINISTRATOR FROM: TRACY SPILLMAN, PLANS DEVELOPMENT ADMINISTRATOR SUBJECT: REVIEW OF THE BUFFER AND LANDSCAPE REQUIREMENTS OF THE AUGUST 05, 2015, SUBDIVISION COMMITTEE MEETING CC: DANA CARNEY, ZONING & SUBDIVISION MANAGER DATE: JULY 31, 2015 NEW BUSINESS: 1. 5 Remin on Cove Z-7854-E Site plan must comply with the City's minimal landscape and buffer ordinance requirements. Screening requirements will need to be met for the vehicular use areas adjacent to street right-of-ways. Provide screening shrubs with an average linear spacing of not less at three (3) feet within the required landscape area. Provide trees with an average linear spacing of not less than thirty (30) feet. A perimeter planting strip is required along any side of a vehicular use area that abuts adjoining property or the right-of-way of any street. This strip shall be at least nine (9) feet wide. One (1) tree and three (3) shrubs or vines shall be planted for every thirty (30) linear feet of perimeter planting strip. Trees shall be included in the interior landscape areas at the rate of one (1) tree for every twelve (12) parking spaces. Any exiting landscape or irrigation disturbed by construction shall be repaired or replaced before completion and final acceptance of the project." The City Beautiful Commission recommends preserving as many existing trees as feasible on this site. Credit toward fulfilling Landscape Ordinance requirements can be given when preserving trees of six (6) inch caliper or larger. 2. 3224 Shackleford Pass Z-9064 Site plan must comply with the City's minimal landscape and buffer ordinance requirements. Street buffers will be required at six (6) percent of the average depth of the lot. The minimum dimension shall be one-half (1/2) the full width requirement but in no case less than nine (9) feet. The maximum dimension required shall be fifty (50) feet. Trees and shrubs are required planed adjacent to street right-of-way. Plant material is to be provided at 1 tree and 3 shrubs for every 30 linear feet. Existing trees and vegetation can be used to satisfy landscape requirements. Screening requirements will need to be met for the vehicular use areas adjacent to street right-of-ways. Provide screening shrubs with an average linear spacing of not less at three (3) feet within the required landscape area. Provide trees with an average linear spacing of not less than thirty (30) feet. A perimeter planting strip is required along any side of a vehicular use area that abuts adjoining property or the right-of-way of any street. This strip shall be at least nine (9) feet wide. One (1) tree and three (3) shrubs or vines shall be planted for every thirty (30) linear feet of perimeter planting strip. A land use buffer six (6) percent of the average width / depth of the lot will be required when an adjacent property has a dissimilar use of a more restrictive nature. The minimum dimension shall be nine (9) feet. As a component of all land use buffer requirements, opaque screening, whether a fence or other device, a minimum of six (6) feet in height shall be required upon the property line side of the buffer. The plantings, existing and purposed, shall be provided within the landscape ordinance of the city, section 15-81. The properties to the south and west are zoned R-2, screening will be required. An irrigation system shall be required for developments of one (1) acre or larger. For developments of less than one (1) acre a there shall be a water source within seventy- five (75) feet of the plants to be irrigated. The City Beautiful Commission recommends preserving as many existing trees as feasible on this site. Credit toward fulfilling Landscape Ordinance requirements can be given when preserving trees of six (6) inch caliper or larger. 3. 2708 and 2718 South Arch fZ-5.23 Site plan must comply with the City's minimal landscape and buffer ordinance requirements. Street buffers will be required at six (6) percent of the average depth of the lot. The minimum dimension shall be one-half (1/2) the full width requirement but in no case less than nine (9) feet. The property is located in the City's designated mature area. A twenty- five (25%) percent reduction of the buffer requirements is acceptable. Trees and shrubs are required planed adjacent to street right-of-way. Plant material is to be provided at 1 tree and 3 shrubs for every 30 linear feet. Existing trees and vegetation can be used to satisfy landscape requirements. A land use buffer six (6) percent of the average width / depth of the lot will be required when an adjacent property has a dissimilar use of a more restrictive nature. The properties to the north and south are zoned R-4. The minimum dimension of the buffer shall be six (6) feet nine (9) inches in areas designated as mature. As a component of all land use buffer requirements, opaque screening, whether a fence or other device, a minimum of six (6) feet in height shall be required upon the property line side of the buffer. The plantings, existing and purposed, shall be provided within the landscape ordinance of the city, section 15-81. An irrigation system shall be required for developments of one (1) acre or larger. For developments of less than one (1) acre a there shall be a water source within seventy- five (75) feet of the plants to be irrigated. The City Beautiful Commission recommends preserving as many existing trees as feasible on this site. Credit toward fulfilling Landscape Ordinance requirements can be given when preserving trees of six (6) inch caliper or larger. 4. 7713 Kanis Road (Z-9063) Site plan must comply with the City's minimal landscape and buffer ordinance requirements. Interior landscape areas shall comprise at least eight (8) percent of any vehicular use area containing twelve (12) or more parking spaces. Trees shall be included in the interior landscape areas at the rate of one (1) tree for every twelve (12) parking spaces. Landscape areas shall be provided between the vehicular use area used for public parking and the general vicinity of the admin / rehab building, excluding truck loading or service areas not open to public parking. These areas shall be equal to an equivalent planter strip three (3) feet wide along the vehicular use area. A land use buffer six (6) percent of the average width / depth of the lot will be required when an adjacent property has a dissimilar use of a more restrictive nature. The surrounding properties are zoned R-2 or MF 18. The minimum dimension shall be nine (9) feet. The maximum dimension required shall be fifty (50) feet. As a component of all land use buffer requirements, opaque screening, whether a fence or other device, a minimum of six (6) feet in height shall be required upon the property line side of the buffer. A minimum of seventy (70) percent of the land use buffer shall be undisturbed. Easements cannot count toward fulfilling this requirement. The plantings, existing and purposed, shall be provided within the landscape ordinance of the city, section 15-81. Screening of the adjacent properties will be required. An irrigation system shall be required for developments of one (1) acre or larger. The City Beautiful Commission recommends preserving as many existing trees as feasible on this site. Credit toward fulfilling Landscape Ordinance requirements can be given when preserving trees of six (6) inch caliper or larger. 5. 40 Rahling Circle (Z-6323-U) Site plan must comply with the City's minimal landscape and buffer ordinance requirements. Screening requirements will need to be met for the vehicular use areas adjacent to street right-of-ways. Provide screening shrubs with an average linear spacing of not less at three (3) feet within the required landscape area. Provide trees with an average linear spacing of not less than thirty (30) feet. A perimeter planting strip is required along any side of a vehicular use area that abuts adjoining property or the right-of-way of any street. This strip shall be at least nine (9) feet wide. One (1) tree and three (3) shrubs or vines shall be planted for every thirty (30) linear feet of perimeter planting strip. Building landscape areas shall be provided at the rate equivalent to planter strip three (3) feet wide along the vehicular use area. One (1) tree and four (4) shrubs shall be planted in the building landscape areas for each forty (40) linear feet of vehicular use area abutting the building. An irrigation system shall be required for developments of one (1) acre or larger The City Beautiful Commission recommends preserving as many existing trees as feasible on this site. Credit toward fulfilling Landscape Ordinance requirements can be given when preserving trees of six (6) inch caliper or larger. 6. Southwest corner of 65th and Scott Hamilton Z-6323-U Site plan must comply with the City's minimal landscape and buffer ordinance requirements. Screening requirements will need to be met for the vehicular use areas adjacent to street right-of-ways. Provide screening shrubs with an average linear spacing of not less at three (3) feet within the required landscape area. Provide trees with an average linear spacing of not less than thirty (30) feet. A perimeter planting strip is required along any side of a vehicular use area that abuts adjoining property or the right-of-way of any street. This strip shall be at least nine (9) feet wide. One (1) tree and three (3) shrubs or vines shall be planted for every thirty (30) linear feet of perimeter planting strip. Building landscape areas shall be provided at the rate equivalent to planter strip three (3) feet wide along the vehicular use area. One (1) tree and four (4) shrubs shall be planted in the building landscape areas for each forty (40) linear feet of vehicular use area abutting the building. An irrigation system shall be required for developments of one (1) acre or larger The City Beautiful Commission recommends preserving as many existing trees as feasible on this site. Credit toward fulfilling Landscape Ordinance requirements can be given when preserving trees of six (6) inch caliper or larger. 7. LaMarche Drive east of Valley Falls and South of the Gardens at Vallev Falls 5-1280-P) No Comment. 8. Northeast corner of Cantrell Road Chenal Parkwa Z-8043-C Site plan must comply with the City's minimal landscape and buffer ordinance requirements and the Highway 10 Scenic Corridor Overlay District. The Highway 10 frontage (front yard) shall consist of a minimum of forty (40) feet of landscaped area exclusive of right -of --way. The landscaped area shall contain organic and/or combined man-made/organic features such as berms, brick walls and dense plantings such that vehicular use areas are screened when viewed from an elevation of forty-two (42) inches above the elevation of the adjacent street. Trees shall be planted or be existing at least every twenty (20) feet and have a minimum of two (2) inches in diameter when measured twelve (12) inches from the ground at time of planting. Provide screening shrubs no less than thirty (30) inches in height at installation with an average linear spacing of not less at three (3) feet within the required landscape area A land use buffer six (6) percent of the average width / depth of the lot will be required when an adjacent property has a dissimilar use of a more restrictive nature. The property to the east is zoned R-2.The minimum dimension shall be thirteen (13) feet. As a component of all land use buffer requirements, opaque screening, whether a fence or other device, a minimum of six (6) feet in height shall be required upon the property line side of the buffer. A minimum of seventy (70) percent of the land use buffer shall be undisturbed. Easements cannot count toward fulfilling this requirement. The plantings, existing and purposed, shall be provided within the landscape ordinance of the city, section 15-81. Screening requirements will need to be met for the vehicular use areas adjacent to street right-of-ways. Provide screening shrubs with an average linear spacing of not less at three (3) feet within the required landscape area. Provide trees with an average linear spacing of not less than thirty (30) feet. A perimeter planting strip is required along any side of a vehicular use area that abuts adjoining property or the right-of-way of any street. This strip shall be at least nine (9) feet wide. One (1) tree and three (3) shrubs or vines shall be planted for every thirty (30) linear feet of perimeter planting strip. Building landscape areas shall be provided at the rate equivalent to planter strip three (3) feet wide along the vehicular use area. One (1) tree and four (4) shrubs shall be planted in the building landscape areas for each forty (40) linear feet of vehicular use area abutting the building. Eight percent (8%) of the vehicular use area must be designated for green space; this green space needs to be evenly distributed throughout the parking area(s). The minimum size of an interior landscape area shall be one hundred fifty (150) square feet for developments with one hundred fifty (150) or fewer parking spaces. Interior islands must be a minimum of seven and one half (7 1/2) feet in width. Trees shall be included in the interior landscape areas at the rate of one (1) tree for every twelve (12) parking spaces. A landscape irrigation system shall be required as per Highway 10 site design and development standards. The City Beautiful Commission recommends preserving as many existing trees as feasible on this site. Credit toward fulfilling Landscape Ordinance requirements can be given when preserving trees of six (6) inch caliper or larger. 9. Rahlina Circle. just South of Noah's Facili Site plan must comply with the City's minimal landscape and buffer ordinance requirements. Screening requirements will need to be met for the vehicular use areas adjacent to street right-of-ways. Provide screening shrubs with an average linear spacing of not less at three (3) feet within the required landscape area. Provide trees with an average linear spacing of not less than thirty (30) feet. A perimeter planting strip is required along any side of a vehicular use area that abuts adjoining property or the right-of-way of any street. This strip shall be at least nine (9) feet wide. One (1) tree and three (3) shrubs or vines shall be planted for every thirty (30) linear feet of perimeter planting strip. Building landscape areas shall be provided at the rate equivalent to planter strip three (3) feet wide along the vehicular use area. One (1) tree and four (4) shrubs shall be planted in the building landscape areas for each forty (40) linear feet of vehicular use area abutting the building. An irrigation system shall be required for developments of one (1) acre or larger The City Beautiful Commission recommends preserving as many existing trees as feasible on this site. Credit toward fulfilling Landscape Ordinance requirements can be given when preserving trees of six (6) inch caliper or larger. 10. 4400 Block of 65th (5-1755 Site plan must comply with the City's minimal landscape and buffer ordinance requirements. A land use buffer six (6) percent of the average width / depth of the lot will be required when an adjacent property has a dissimilar use of a more restrictive nature. The property to the west is zoned R-2. As a component of all land use buffer requirements, opaque screening, whether a fence or other device, a minimum of six (6) feet in height shall be required upon the property line side of the buffer. A minimum of seventy (70) percent of the land use buffer shall be undisturbed. Easements cannot count toward fulfilling this requirement. The plantings, existing and purposed, shall be provided within the landscape ordinance of the city, section 15-81. A perimeter planting strip is required along any side of a vehicular use area that abuts adjoining property or the right-of-way of any street. This strip shall be at least nine (9) feet wide. One (1) tree and three (3) shrubs or vines shall be planted for every thirty (30) linear feet of perimeter planting strip. Landscape areas shall be provided between the vehicular use area used for public parking and the general vicinity of the building, excluding truck loading or service areas not open to public parking. These areas shall be equal to an equivalent planter strip three (3) feet wide along the vehicular use area. An irrigation system shall be required for developments of one (1) acre or larger. For developments of less than one (1) acre a there shall be a water source within seventy- five (75) feet of the plants to be irrigated. The City Beautiful Commission recommends preserving as many existing trees as feasible on this site. Credit toward fulfilling Landscape Ordinance requirements can be given when preserving trees of six (6) inch caliper or larger. 11. 18500 Cooper Orbit Road S-1756 Site plan must comply with the City's minimal landscape and buffer ordinance requirements. The City Beautiful Commission recommends preserving as many existing trees as feasible on this site. Credit toward fulfilling Landscape Ordinance requirements can be given when preserving trees of six (6) inch caliper or larger. 12. Northeast Corner of "R" Street and Normand Z-9062 No Comments 13. Northeast Corner of Chenal Parkway and Rahlin Road Z-867-CCCCCCCC No Comments 14. East Side of Chenal Parkwa and South of Systems Drive Z-6051- Site plan must comply with the City's minimal landscape and buffer ordinance requirements. Screening requirements will need to be met for the vehicular use areas adjacent to street right-of-ways. Provide screening shrubs with an average linear spacing of not less at three (3) feet within the required landscape area. Provide trees with an average linear spacing of not less than thirty (30) feet. A perimeter planting strip is required along any side of a vehicular use area that abuts adjoining property or the right-of-way of any street. This strip shall be at least nine (9) feet wide. One (1) tree and three (3) shrubs or vines shall be planted for every thirty (30) linear feet of perimeter planting strip. Building landscape areas shall be provided at the rate equivalent to planter strip three (3) feet wide along the vehicular use area. One (1) tree and four (4) shrubs shall be planted in the building landscape areas for each forty (40) linear feet of vehicular use area abutting the building. An irrigation system shall be required for developments of one (1) acre or larger The City Beautiful Commission recommends preserving as many existing trees as feasible on this site. Credit toward fulfilling Landscape Ordinance requirements can be given when preserving trees of six (6) inch caliper or larger. 6. 14 and 16 Penny Lane (S-138 No Comments City Limits I-PqD .4 ...................................... City Limits THIS SITE R2 C 0 M A E)OPER-OR&TCV- Area Zoning Case: S-1756 N Location: 18500 Cooper Orbit RD Ward: N/A PD: 18 0 220440 880 Feet CT 42.07 TRS: TlN R13W18 1� 1 1" NRT ST WMTER SWTHVEST WMTER SECTION 16 T-1-N R-13-V 39M Am.. ro n�^i eT•.vl t• E nlem" s o.•+x.e• c 4. "OF � NeTR lu wv. m/4.ocT .R.r. us yr 4nA. �,. Ix �.. wr. rccl .m..s •up ,a ••s PACTS NjkAAENi 2066 ARKANSAS Try1T4 NAD 83 W 14155IL31000 E. U8011L68000 ELEV 451.54 NGVD 29 PART W THE NV2 SID/TI T WMTER SECTM IB T-1-N R-13-W 70.13 A - .... yarn x n�cvrl \ 1.44 r PART 6 SV2 S➢VTHEAST WMTM \ SECT10l75A2 18 �l-ry: -13-V w ROM°io� 9 T.voNn ImTr rnvE ��r meo lea w P++1 �TRN e r nwl.Nc r r faw[ IW .RTR6 uu .NTs N an — 26307' y N �7•iY[I' v t%41P TrT A4 e.64' 9F.E0 .l1,4f r TRSTAVx C4LL TRIM SEL}Dll CD.FR PMT W Nl1RTNTAST WARIER ` SECTTON 19 T-3-N R-13-V 30.14 Acr.i " 39L%' RAon I �� E936r MORR 10.D 7� PROPOSED 1SX00' PORTABLE BULL DNG r •NO PLUMBING FOR BUILDING •REQUE571NO A RRDUCIION OF THE SOW " BL=IN'0 SETBACK FROM 26' TO 10' grylvfid0x \ — IL[ cA18 WDO. ,� ��ayaiP�vnld H.•r�.nw S-1756 0 18500 COOPER ORBIT RD 0 SITE PLAN REVIEW C City of Little Rock Department of Planning and Development Planning 723 West Markham Street Zoning and Little Rock, Arkansas 72201-1334 Subdivision Phone: (501) 371-4790 Fax: (501) 399-3435 or 371-6863 October 16, 2015 Minton Engineering 300 North Port Drive Cabot, AR 72023 Re- S-1756 - Lake Nixon Subdivision Site Plan Review, located at 18500 Cooper Orbit Road Dear Sirs: This is to advise you that in connection with your request concerning the above referenced file number the following action was taken by the Planning Commission at its meeting on October 8, 2015: Approved with conditions. Recommended approval with conditions. Recommended approval as submitted. Denied your request as submitted. Deferred to the _Meeting. X Other: Withdrew vour request. If you have any questions please do not hesitate to contact me at 371-6821. Respectfully, Donna James, AICP Subdivision Administrator t • sitpin.doc 03/01/10 INFORMATION SHEET FOR SUBDIVISION PUD's PD's, ZONING OR SUBDIVISION SITE PLAN REVIEWS ITEM NO. DATE FILE NO. NAME: C/►G-L�e_ ►' �kl-J44 LOCATION: DEVELOPER: z ~� ghplk►5lr STREET ADDRESS -ZZZ E . sIV- CITY/STATE/ZIP L 4ktl , c,kc- A -77Z7,oZ TELEPHONE NO. ( S(---) t1 ?o EA - _ 9 Z a 4 ENGINEER: �nri»�J Grti r� ', ►� GT c� r5r--r Zn] c.. STREET ADDRESS SCO IJor �oc� Qc. CITY/STATE/ZIP C4AOO-�r L -7-Zc7-Z TELEPHONE NO. ( So l) al Lt 1 - S 55-7 AREA Z IS .-77 - Ac— FT. NEW STREET ZONING NUMBER OF LOTS PROPOSED USES PLANNING DISTRICT CENSUS TRACT VARIANCES REQUESTED 1.) �G.JvGty la.cv��q Sc�bks. ory C.00p¢r D� �.�- roM, 2S� �0 1�� -ac PvoQoi6d� S}« c.�ruva . 2.) 3.) 4.) ��� � 300 North Port Drive (D Cabot, AR 72023 (501) 941-5559 July 20, 2015 Mrs. Donna James City of Little Rock - Planning 723 W. Markham St. Little Rock, AR 72201 Re: Site Plan Review & Variance Request, Lake Nixon Day Camp, Little Rock, AR Mrs. James: Attached please find the information sheet and 18 copies of the survey and proposed site plan. This project consists of adding a 18x60' portable building along Cooper Orbit Road. This structure will only be accessed from inside the camp facility and will not require access from Cooper Orbit. The building will be used for general operations and storage for the Camp and will not require water or sewer service to the building. The owner is requesting that the building setback be reduced from 25' to 10' for the new structure. By placing the building at the existing setback, the owner is concerned that the line of site from the main camp facility will be cut off from the western portion of the lake, making it difficult to monitor camp activities. Also, by reducing the setback the new building will line up with the existing pavilion just to the east. Please place this item on the agenda for the next planning commission meeting, contact me if you have any questions or need any additional information Minton, PE :ct Engineer City of Little Rock Department of Planning and Development Planning 723 West Markham Street Zoning and Little Rock, Arkansas 72201-1334 Subdivision Phone: (501) 371-4790 Fax: (501) 399-3435 or 371-6863 NOTICE OF PUBLIC HEARING BEFORE THE LITTLE ROCK PLANNING COMMISSION ON A REQUEST FOR A USE CHANGE OR DEVELOPMENT OF LAND DATE: July 22, 2015 TO: Spring ValleV Manor Neighborhood Association ATTENTION: Ms. Jena McDonnell ADDRESS: 114 Secluded Circle Little Rock AR 72210 REQUEST: Lake Nixon Subdivision Site Plan Review S-1756 . a request for a multiple building subdivision siteplan) review to allow the placement to two 2 buildings on the site to be used for general operations and storage and future educational programs provided by the Camp. GENERAL LOCATION OR ADDRESS: 18500 Cooper Orbit Road OWNED BY/APPLICANT: 2nd Baptist Church — Josh Minton Minton En ineerin 501.941.5559) agent NOTICE IS HEREBY GIVEN THAT an application for a Subdivision Site Plan Review of the above property has been filed with the Department of Planning and Development. A public hearing will be held by the Little Rock Planning Commission in the Little Rock Board of Directors Chambers, second floor, City Hall, 500 West Markham Street, on August 27, 2015 at 4:00 P.M. This notice is provided in order to assure that neighborhood associations are aware of issues that may affect their neighborhood. Information requests should be directed to the Planning staff at 371-4790. Tony Bozynski Director of Planning and Development City of Little Rock Department of Planning and Development Planning 723 West Markham Street Zoning and Little Rock, Arkansas 72201-1334 Subdivision Phone: (501) 371-4790 Fax: (501) 399-3435 or 371-6863 NOTICE OF PUBLIC HEARING BEFORE THE LITTLE ROCK PLANNING COMMISSION ON A REQUEST FOR A USE CHANGE OR DEVELOPMENT OF LAND September 8, 2015 Spring Valley Manor Property Owners Association Ms. Jena McDonnell 114 Secluded Circle Little Rock, AR 72210 REQUEST: Lake Nixon Subdivision Site Plan Review S-1756 a reguest for a multiple building subdivision siteplan),review to allow the placement to two 2 buildings on the site to be used for general operations and storage and future educational programs provided by the Camp. GENERAL LOCATION OR ADDRESS: 18500 Cooper Orbit Road OWNED BY/APPLICANT: 2nd Baptist Church — Josh Minton Minton Engineering (501.941.5559) aqent NOTICE IS HEREBY GIVEN THAT an application for a Subdivision Site Plan Review of the above property has been filed with the Department of Planning and Development. A public hearing will be held by the L.R. Planning Commission in the Little Rock Board of Directors Chambers, second floor, City Hall, 500 West Markham Street, on October 8, 2015 at 4:00 P.M. You were previously notified of this application request. This item was deferred from the August 27, 2015, public hearing to this new hearing date. This notice is provided in order to assure that neighborhood associations are aware of issues that may affect their neighborhood. Information requests should be directed to the Planning staff at 371-4790. Tony Bozynski Director of Planning and Development James, Donna From: Josh Minton <mintoneng@gmail.com> on behalf of Josh Minton <josh@mintoneng.com> Sent: Monday, September 14, 2015 12:02 PM To: James, Donna Subject: Camp Nixon Mrs. James, the Camp has decided to not purchase the building that we had requested the permit for. Please remove this item from the agenda for the October PC meeting. Thanks -Josh Josh mintton, pE m i nto n 300 North Port Driva Croat, AR 72023 1501F941.55S9 James, Donna From: Jim Cranor <jcranor@pulaskicounty.net> Sent: Thursday, July 23, 2015 9:09 AM To: James, Donna Cc: Van McClendon Subject: Re: Issue at 711 Howlett Lane and 5-1756 Thanks Donna. Regarding S-1756, Pulaski County has no comment other than to make sure the portable building is placed outside the right of way dedicated along Cooper Orbit Road to comply with the master street plan. Jim Jim Cranor Plans Review Coordinator Pulaski County Planning and Development 3200 Brown Street Little Rock, AR 72204 501-340-8265 From: James, Donna <DJames@littlerock.org> Sent: Thursday, July 23, 2015 7:59 AM To: McKinley Adams Cc: Jim Cranor Subject: RE: Issue at 711 Howlett Lane Tony Bozynski, Director of Planning, has signed off on the request. Please let me know if you need anything additional from the City. From: McKinley Adams [mailto:mckinley@tagconstructionco.com] Sent: Wednesday, July 22, 2015 5:17 PM To: James, Donna Subject: Issue at 711 Howlett Lane Ms. Donna, Here is a letter addressed from the homeowner and also our company. I was not sure which would be best. Please let me know if there is anything else you all need to resolve this matter. Thanks, McKinley Adams 501-350-2868 mckinievCa7tapconstruct onco.com www.tagconstructioncompany.com TAG Construction Co. Inc. 4329 McDaniel Circle Little Rock, AR 72206 City of Little Rock ,_ Department of Planning and Development Planning 723 West Markham Street Zoning and Little Rock, Arkansas 72201-1334 Subdivision Phone: (501) 371-4790 Fax: (501) 399-3435 or 371-6863 DATE: July 20, 2015 Entergy Center Point - ARKLA AT&T Central Arkansas Water Little Rock Wastewater Pulaski County Planning Little Rock Fire Department NAME: Lake Nixon Subdivision Site Plan Review TYPE OF ISSUE: Subdivision Site Plan Review — add additional classroom space FILE NUMBER: S-1756 LOCATION: 18500 Cooper Orbit Road Public Works: Engineering, Traffic (2) Parks and Recreation Department Planning and Development — Site Plan Review Planning and Development Graphics Planning and Development — Building Codes CATA TO WHO IT MAY CONCERN: On August 27, 2015 the Little Rock Planning Commission will consider the above referenced issue. NOTE: The Interdepartmental Meeting at which this issue will be discussed will be held on July 31, 2015. NOTE: The Subdivision Committee Meeting at which this issue will be discussed will be held on August 5, 2015. A copy of the plan for the referenced issue is enclosed for your consideration, and your comments and/or recommendations will be appreciated. Sincerely, a( Donna James, AICP Subdivision Administrator (Please respond below and return this letter with your comments for our records.) Approved as Submitted. PLEASE RETURN COMMENTS BY August 3, 20I5. Easement (s) required (See attached plat or description.) *To all utilities: If an easement is requested which is in excess of 10 feet in width, provide justification for the easement or the request will not be included in the Planning Commission agenda. Comments: A Enclosure F19 $ $ 26 City of Little Rock Planning and Development Filing Fees Date , 201.j— Annexation $ Board of Adjustment Cond Use Permit/T U P. �$ Final Plat J U L $ Planned Unit Dev CII-Y OF 1- [ LE ROCK Preliminaiy Plat $ Special Use Permit Rezoning Site Plans Street Name Change Street Name Signs Number at ea Public Hearing Signs Number Eea Total File No Location