ITEM NO.: 16
August 14, 2003
FILE NO.: S-1399
NAME: Wimbledon Greens Apartments Subdivision Site Plan Review
LOCATION: on the southeast corner of Baseline Road and Wimbledon Loop
Plannina Staff Comments:
IJ
1. Provide notification of property owners located within 200-feet of the site
complete with the certified abstract list, notice form with affidavit executed and
proof of mailing.
2. Dimension the distance between buildings.
3. Will the Certificates of Occupancies be issue as buildings or as sets of
buildings are completed or when the entire project is completed?
4. Provide details of the proposed signage. (Height/area)
5. Provide the fencing height of the brick and iron fence located on the street
sides. If the fence will be placed within the 25-foot building line setback the
maximum fence height allowed would be four feet unless a variance is
requested and granted.
6. Provide the fence height of the wood fence along the south and east property S�
lines. . op
6p �
Variance/Waivers:
1. None requested.
Public Works:
1. West Baseline is classified on the Master Street Plan as a principal arterial.
Dedication of right-of-way to 55 feet from centerline will be required as
indicated on the plans.
2. A 20 foot radial dedication of right-of-way is required at the intersection of
Baseline with Wimbledon Loop.
3. Sidewalks with appropriate handicap ramps are required in accordance with
Section 31-175 of the Little Rock Code and the Master Street Plan.
4. All driveways shall be concrete aprons per City Ordinance.
5. Plans of all work in right-of-way shall be submitted for approval prior to start of
work. Obtain barricade permit prior to doing any work in the right-of-way from
Traffic Engineering at (501) 379-1817 (Derrick Bergfield).
Y--
6. A grading permit in accordance with Section 29-186 (c) & (d) will be required
prior to any land clearing or grading activities at the site. Site grading, and
drainage plans will need to be submitted and approved prior to the start of
construction.
7. Provide the direction of flow and all storm water flows (Q) entering and
leaving the property.
8. Storm water detention ordinance applies to this property. Show the proposed
location for stormwater detention facilities on the plan. Facilities should
protect the down -stream pond.
9. In accordance with Section 32-8, no obstruction to visibility shall be located
within a triangular area 50' back from the intersecting right-of-way line (or
intersecting tangent lines for radial dedications) at the intersection of Baseline
with Wimbledon Loop.
10. Prepare a letter of pending development addressing streetlights as required
by Section 31-403 of the Little Rock code. Contact Traffic Engineering at
(501) 379-1813 (Steve Philpott) for more information regarding street light
requirements.
Utilities and Fire Department/County Planning:
Wastewater: Sewer main extension required, with easements, if service is
required for project. Capacity Contribution analysis required. Contact the Little
Rock Wastewater Utility at 688-1414 for additional details.
Entergy: Additional easements will be required for the interior of property for
underground electrical distribution. The exact location cannot be determined at
this time. Contact Entergy at 954-5158 for additional details.
Center -Point Energy:
SBC: Approved as submitted.
Central Arkansas Water: All Central Arkansas Water requirements in effect at
the time of request for water service must be met. Additional fire hydrant(s)
and/or on site fire protection will be required. This development will have minor
impact on existing water distribution system. Proposed water facilities will be
sized to provide adequate pressure and fire protection.
Fire Department: Place fire hydrants per code. Increase the driveway off
Wimbledon Loop to 20-feet. Contact the Little Rock Fire Department at 918-
3752 for additional details.
County Planning: No comment received.
CATA: No comment received.
Plannina Division: No comment.
Landscape: Areas set -aside for buffers and landscaping meet with
ordinance requirements.
An irrigation system to water landscaped areas will be required.
Prior to obtaining a building permit, it will be necessary to provide approved
landscape plans stamped with the seal of a Registered Landscape Architect.
The City Beautiful Commission recommends preserving as many existing trees
as feasible on this tree -covered site. Extra credit toward fulfilling Landscape
Ordinance requirements can be given when properly preserving trees of six (6)
inch caliper or larger.
Revised plat/plan: Submit four (4) copies of a revised preliminary plan (to
include the additional information as noted above) to staff on Wednesday, August
20, 2003.
September 4, 2003
ITEM NO.: 16
FILE NO.: S-1399
NAME: Wimbledon Greens Apartments Subdivision Site Plan Review
LOCATION: on the southeast corner of Baseline Road and Wimbledon Loop
DEVELOPER:
Otter Creek Land Company
#2 Otter Creek Court
Little Rock, AR 72209
ENGINEER:
McGetrick & McGetrick
319 President Clinton Avenue
Little Rock, AR 72201
AREA: 6.337 acres NUMBER OF LOTS: 1 FT. NEW STREET: 0
CURRENT ZONING: MF-24, Multi -family 24 units per acre
PLANNING DISTRICT: 16 — Otter Creek
CENSUS TRACT: 42.08
VARIANCESMAIVERS REQUESTED:
1. A variance to allow an increased fence height along the north and west property
lines.
2. A waiver of the land use buffer requirement.
A. PROPOSAL:
The applicant proposes the construction of 96 units of multi -family housing (15.16
units per acre) on this MF-24 zoned site. The applicant is proposing the
placement of thirteen buildings on the site, one of which is to serve as an
office/club house area. The unit mix proposed is one and two bedroom units with
September 4, 2003
SUBDIVISION
ITEM NO.: 16 (Cont.) _ FILE NO.: S-1399
32 one -bedroom units and 64 two bedroom units. Of the two bedroom units, five
will be fully accessible. The maximum building height proposed is 26-feet and all
the buildings proposed will be two story.
The applicant proposes the placement of a 2560 square foot clubhouse and a
pool on the site. The applicant is also proposing the placement of a playground
area near the pool site.
The applicant is proposing the placement of 182 parking spaces within the
development.
The applicant has indicated the development will be enclosed with a six-foot brick
and iron fence along the street sides, (the north and west) and a six-foot wood
fence on the remaining sides. The fence along the street sides will require a
variance to allow the desired location and height since the fence will be placed
within the building setback.
The applicant is requesting a waiver of the land use buffer requirement. The
ordinance requires at least seventy percent of the land use buffer to remain in its
natural state. The applicant has indicated the significant trees will be retained
but the undergrowth will be removed to ensure security for the development.
B. EXISTING CONDITIONS:
The site is a vacant tree covered site with road frontage on Baseline Road and
Wimbledon Loop. The road has been widened adjacent to the site along
Baseline Road. There is not a sidewalk in place. Wimbledon Loop has a median
and midway of the site there is a gate, the back entrance to Otter Creek.
There is a large apartment complex located to the north of this site, Eagle Hill
Apartments and the area to the west is vacant and tree covered. East of the site
is a single-family home located on a large tract of land. There is a newly
developing subdivision located further east. There are single-family homes
located south of the site in the Otter Creek Subdivision.
C. NEIGHBORHOOD COMMENTS:
As of this writing, staff has not received several informational phone calls from
area residents. All owners of property located within 200-feet of the proposed
site along with the Otter Creek Home Owners Association and Southwest Little
Rock United for Progress were notified of the Public Hearing.
D. ENGINEERING COMMENTS:
Public Works:
1. West Baseline is classified on the Master Street Plan as a principal arterial.
Dedication of right-of-way to 55 feet from centerline will be required as
indicated on the plans.
2
September 4, 2003
SUBDIVISION
ITEM NO.: _16 (Cont.) FILE NO.: S-1399
2. A 20 foot radial dedication of right-of-way is required at the intersection of
Baseline with Wimbledon Loop.
3. Sidewalks with appropriate handicap ramps are required in accordance with
Section 31-175 of the Little Rock Code and the Master Street Plan.
4. All driveways shall be concrete aprons per City Ordinance.
5. Plans of all work in right-of-way shall be submitted for approval prior to start
of work. Obtain barricade permit prior to doing any work in the right-of-way
from Traffic Engineering at (501) 379-1817 (Derrick Bergfield).
6. A grading permit in accordance with Section 29-186 (c) & (d) will be
required prior to any land clearing or grading activities at the site. Site
grading, and drainage plans will need to be submitted and approved prior to
the start of construction.
7. Provide the direction of flow and all storm water flows (Q) entering and
leaving the property.
8. Storm water detention ordinance applies to this property. Show the
proposed location for stormwater detention facilities on the plan. Facilities
should protect the down -stream pond.
9. In accordance with Section 32-8, no obstruction to visibility shall be located
within a triangular area 50' back from the intersecting right-of-way line (or
intersecting tangent lines for radial dedications) at the intersection of
Baseline with Wimbledon Loop.
10. Prepare a letter of pending development addressing streetlights as required
by Section 31-403 of the Little Rock code. Contact Traffic Engineering at
(501) 379-1813 (Steve Philpott) for more information regarding street light
requirements.
E. UTILITIES AND FIRE DEPARTMENT/COUNTY PLANNING:
Wastewater: Sewer main extension required, with easements, if service is
required for project. Capacity Contribution analysis required. Contact the Little
Rock Wastewater Utility at 688-1414 for additional details.
Entergy: Additional easements will be required for the interior of property for
underground electrical distribution. The exact location cannot be determined at
this time. Contact Entergy at 954-5158 for additional details.
Center -Point EneLg : No comment received.
SBC: Approved as submitted.
Central Arkansas Water: All Central Arkansas Water requirements in effect at
the time of request for water service must be met. Additional fire hydrant(s)
September 4, 2003
SUBDIVISION
ITEM NO.: 16 (Cont.) FILE NO.: S-1399
F
9
and/or on site fire protection will be required. This development will have minor
impact on existing water distribution system. Proposed water facilities will be
sized to provide adequate pressure and fire protection.
Fire Department: Place fire hydrants per code. Increase the driveway off
Wimbledon Loop to 20-feet. Contact the Little Rock Fire Department at
918-3752 for additional details.
County Planning: No comment received.
CATA: No comment received.
ISSUES/TECHNICAL/DESIGN:
Planning Division: No comment.
Landscape: Areas set -aside for buffers and landscaping meet with ordinance
requirements.
An irrigation system to water landscaped areas will be required.
Prior to obtaining a building permit, it will be necessary to provide approved
landscape plans stamped with the seal of a Registered Landscape Architect.
The City Beautiful Commission recommends
as feasible on this tree -covered site. Extr
Ordinance requirements can be given when
inch caliper or larger.
SUBDIVISION COMMITTEE COMMENT:
a
preserving as many existing trees
credit toward fulfilling Landscape
properly preserving trees of six (6)
(August 14, 2003)
Mr. Pat McGetrick was present representing the request. Staff briefly described
the proposed development indicating the request was for a multiple building site
plan review. Staff noted there were additional items needed on the proposed site
plan to complete the review. Staff requested all building dimensions be shown
on the site plan and the applicant provide the height of the proposed fencing.
Staff noted if the proposed fence located in the building setback was above four
feet, the applicant would need to request a variance. Staff also requested details
concerning the proposed signage.
Public Works comments were addressed. Staff stated all work in the right-of-way
would be required to be submitted for approval prior to construction. Staff
requested additional information concerning storm water flows enter and leaving
the property. Staff stated the stormwater detention ordinance applied to the
property and the applicant should locate the detention facilities on the site plan.
4
September 4, 2003
SUBDIVISION
ITEM NO.: 16 Cont. FILE NO.: S-1399
Landscaping comments were addressed. Staff noted at least seventy percent of
the buffer area should remain in its natural state. Mr. McGetrick stated this was
not acceptable. He noted the applicant had indicated a desire to leave all the
mature trees in the buffer area but to remove any and all underbrush. He stated
this made for a more secure facility. In apartment developments security was a
concern. Staff stated he would need to request a variance to be allowed to clear
the underbrush in the buffer area.
There was no further discussion of the item and the Committee then forwarded
the item to the full Commission for final action.
H. ANALYSIS:
The applicant submitted a revised plan to staff addressing most of the issues
raised at the August 14, 2003 Subdivision Committee meeting. The applicant
has indicated the proposed signage will be a maximum of six feet in height and
twenty-four square feet in area. The applicant has also dimensioned all building
setbacks from property lines. The applicant has requested a variance to allow
the six-foot brick and iron fence along West Baseline Road and Wimbledon Loop.
The fence will be placed within the twenty-five foot building setback and is
proposed as six feet in height. The zoning ordinance allows a maximum of four
feet in height within the building setback. The applicant has indicated the fence
will not be placed in the required fifty foot triangle area of the intersecting streets.
Staff is supportive of the fence placement and the requested fence height
variance.
The applicant has indicated the land use buffer will not be preserved. The zoning
ordinance requires at least seventy percent of the land use buffer remain in its
natural state. The applicant is requesting to be allowed to remove the
underbrush in this area. The applicant has stated all significant trees will remain
in the land use buffer area. The applicant has indicated security is a concern and
with the underbrush growth the development will not be able to police the site to
ensure the safety of their residents. Staff is supportive of the requested waiver.
The applicant has indicated a six foot wood fence will be placed along the
property line to screen the adjoining single-family zoned properties.
The applicant has indicated the maximum building height to be twenty-six feet.
The maximum building height allowed for MF-24 zoned property is thirty-five feet.
The applicant has also indicated the buildings will be placed at a minimum of
thirty feet from the property lines. The ordinance requires the building setback to
be equal to the building heights and not less than twenty-five feet.
The applicant has indicated the development will be constructed in phases with a
request for Certificate of Occupancies based on the completion of groups of
buildings. The applicant has indicated the requested Certificate of Occupancies
will be phased based on the completion of buildings which will not endanger the
safety of residents of the development.
5
September 4, 2003
SUBDIVISION
ITEM NO.: 16 Cont. FILE NO.: S-1399
The ordinance requires the development allow 2,400 square feet of lot area per
family. The applicant is proposing the placement of ninety-six units on the site
which would require 3.96 acres. The development contains 6.337 acres; more
than adequate to meet the minimum lot area requirement.
The applicant is proposing the placement of 182 parking spaces within the
development. The typical minimum parking requirement for a development of
this size would be 144 parking spaces or 1.5 spaces per unit. The proposed
parking is adequate the meet the typical minimum parking demand.
The applicant has indicated underground detention will be used to pipe water
along the east side of the development to centralized detention for Otter Creek if
detention is necessary.
To staffs knowledge there are no other outstanding issues associated with the
proposed request. Staff feels the proposed development should have minimal to
no adverse impact on the surrounding area.
I. STAFF RECOMMENDATION:
Staff recommends approval of the request as filed subject to compliance with the
conditions outlined in paragraphs D, E and F of this report.
Staff recommends approval of the requested waiver of the land use buffer
requirement to allow the clearing of the underbrush.
Staff recommends approval of the requested fence height variance along the
north and west property lines.
PLANNING COMMISSION ACTION: (SEPTEMBER 4, 2003)
Mr. Pat McGetrick was present representing the request. There was one objector
present. Staff presented the item with a positive recommendation subject to
compliance with the conditions outlined in paragraphs D, E and F of the above report.
Staff also presented a recommendation of approval of the requested waiver of the land
use buffer requirement to allow the clearing of the underbrush along the south and east
perimeters and the requested fence height variance along the north and west property
lines.
Mr. Kevin Wright addressed the Commission in opposition of the proposed request. He
stated his home backed up to the proposed development and he was not in favor of the
site developing with multi -family housing. He stated with the addition of the 96 units on
the site Wimbledon Loop would be taxed and traffic back-ups in the mornings would be
even more sever.
0
September 4, 2003
SUBDIVISION
ITEM NO.: 16 (Cont.) FILE NO.: S-1399
The Commission stated the proposed request was for a multiple building site plan
review. It was stated the site was zoned for multi -family and it was not a decision as to
if the site would be developed with multi -family units only if the proposed development
met the criteria under the Subdivision Ordinance for multiple buildings. Staff stated the
applicant was requesting a waiver of the land use buffer requirements. Staff questioned
Mr. Wright as to if he had issues with the request to clear the buffer area. Mr. Wright
stated he was not sure because he was not sure what this involved.
Mr. McGetrick addressed the Commission on behalf of the applicant. He stated he had
met with the Otter Creek Homeowners Association and they were in support of the
request. Commissioner Floyd questioned Mr. McGetrick if their support was not tied to
the proposed gate being closed on Wimbledon Loop. He stated he was not aware of
that requirement. Commissioner Floyd questioned if the main entrance and exit should
not be placed on Baseline Road. Mr. McGetrick stated the developer felt the location on
Wimbledon Loop a better location.
A motion was made to approve the proposed request as filed included the requested
waivers and variances. The motion carried by a vote of 6 ayes, 2 noes and 3 absent.