HomeMy WebLinkAboutResponse to CommentsHope Consulting Engineers
129 North Main Street
Benton, Arkansas, 72015
(501) 315-2626
October, 17th 2024
City of Little Rock Planning and Development Planning Commission
dstafford@littlerock.gov and tthrower@littlerock.gov
RE: Z-10061
Flores Office-Warehouse – PD-O
7524 Fairfield Drive
Development Staff Comments & Responses:
1. Provide building elevations. Conceptual elevation has been added to the plan sheet.
2. Provide cross-sections. Cross-sections have been requested from the architect.
3. Provide uses that are to take place within each building. This information from the architect has
been requested.
4. Show locations of the two garage doors as referred to in the cover letter. The floor plan that will
provide this information has been requested from the architect.
5. Will there be a dumpster on site? If so, it will be required to be screened according to section
36-523 (d) of the zoning code. A roll-out dumpster application will be used or this project.
6. Provide, at a minimum, a six (6) foot tall opaque fence along the East property line as per code
requirements. Fence has been added and called out on plan.
7. Any sight lighting must be low-level and directed away from adjacent properties. All lighting
will comply and be placed on the building.
8. Any new signage placed on-site must comply with Section 36-553 of the Zoning Code. Signage
will comply with all zoning regulations that apply.
9. Provide hours and days of operation. Monday thru Friday, 8am-5pm.
Maintain Access Comments & Responses:
Fire Hydrants:
Maintain fire apparatus access roads at fire hydrant locations as per Appendix D of the 2021 Arkansas
Fire Prevention Code Vol. 1 Section D103.1 Access road width with a hydrant. Where a fire hydrant
is located on a fire apparatus access road, the minimum road width shall be 26 feet, exclusive of
shoulders. Entrance access drive has been widened to be 26' wide.
Grade:
Maintain fire apparatus access roads as per Appendix D of the 2021 Arkansas Fire Prevention Code
Vol. 1 Section D103.2 Grade: Fire apparatus access roads shall not exceed 10 percent in grade
except as approved by the fire chief. If the grade exceeds 10 percent, approval will be denied and
the applicant must submit request to be reviewed by Fire Chief for Approval. The access road will
not exceed 10 percent grade.
Loading:
Maintain fire apparatus access road design as per Appendix D of the 2021 Arkansas Fire Prevention
Code Vol. 1 Section D102.1 Access and loading. Facilities, buildings or portions of buildings hereafter
constructed shall be accessible to fire department apparatus by way of an approved fire apparatus
access road with an asphalt, concrete or other approved driving surface capable of supporting the
imposed load of fire apparatus weighing at least 75,000 pounds. Plans comply with this code section
requirement.
Commercial and Industrial Developments – 2 means of access. - Maintain fire apparatus access
roads as per Appendix D of the 2021 Arkansas Fire Prevention Code Vol. 1
Section D104.1 Buildings exceeding three stories or 30 feet in height. Building or facilities
exceeding 30 feet in height shall have at least two means of fire apparatus access for each structure.
Not applicable.
Section D104.2 Building exceeding 62,000 square feet in area. Buildings or facilities having a gross
building area of more than 62,000 square feet shall be provided with two separate and approved fire
apparatus access roads. Exception: Projects having a gross building area of up to 124,000 square feet
that have a single approved fire apparatus access road when all building are equipped throughout with
approved automatic sprinkler systems. Not applicable. This building's footprint is only 1500 square
feet.
Section D104.3 Remoteness. Where two fire apparatus access roads are required, they shall be placed
a distance apart equal to not less than one half of the length of the maximum overall diagonal
dimension of the lot or area to be served, measured in a straight line between accesses. Not applicable,
this building doesnt require two access roads.
30' Tall Buildings – Maintain aerial fire apparatus access roads as per Appendix D of the 2021
Arkansas Fire Prevention Code Vol. 1 Section D105.1 – D105.4
D105.1 Where Required. Where the vertical distance between the grade plane and the highest roof
surface exceed 30', approved aerial fire apparatus access roads shall be provided. For the purposes of
this section the highest roof surfaces shall be determined by measurement to the eave of a pitched roof,
the intersection of a roof to the exterior wall, or the top of parapet walls, whichever is greater. Not
applicable, building is not 30' tall.
D105.2 Width. Aerial fire apparatus access roads shall have a minimum unobstructed width of 26',
exclusive of shoulders, in the immediate vicinity of the building or portion thereof. Entrance access
drive has been widened to be 26' wide.
D105.3 Proximity to building. At least one of the required access routes meeting this condition shall
be located within a minimum of 15 feet and a maximum of 30 feet from the building, and shall be
positioned parallel to one entire side of the building. The side of the building on which the aerial fire
apparatus access road is positioned shall be approval of the fire code official. Not applicable.
D105.4 Obstructions. Overhead utility and power lines shall not be located over the aerial fire
apparatus access road or between the aerial fire apparatus road and the building. Other obstructions
shall be permitted to be places with the approval of the fire code official. Existing overhead power lines
are in place already.
Dead Ends:
Maintain fire apparatus access roads at dead end locations as per Appendix D of the 2021
Arkansas Fire Prevention Code Vol. 1 Section D103.4 Dead Ends. Dead-end fire apparatus access
roads in excess of 150 feet shall be provided with width and turnaround provisions in accordance with
Table D103.4. Requirements for Dead-End fire apparatus access roads. Adequate turn around space has
been provided.
Gates:
Maintain fire apparatus access road gates as per Appendix D of the 2021 Arkansas Fire
Prevention Code Vol. 1 Section D103.5 Fire apparatus access roads gates. Gates securing the fire
apparatus access roads shall comply with all of the following criteria: Gate requirement is not
applicable.
1. Minimum gate width shall be 20 feet.
2. Gates shall be of swinging or sliding type.
3. Construction of gates shall be of material that allow manual operation by one person.
4. Gate components shall be maintained in an operable condition at all times and replaces or
repaired when defective.
5. Electric gates shall be equipped with a means of opening the gate by fire department
personnel for emergency access. Emergency opening devices shall be approved by the fire
code official.
6. Manual opening gates shall not be locked with a padlock or chain and padlock unless they
are capable of being opened by means of forcible entry tools or when a key box containing
the keys to the lock is installed at the gate location.
7. Locking device specifications shall be submitted for approval by the fire code official.
8. Electric gate operators, where provided, shall be listed in accordance with UL 325.
9. Gates, intended for automatic operation shall be designed, constructed and installed to
comply with requirements of ASTM F 2200.