HomeMy WebLinkAboutS-1714 Staff AnalysisITEM NO.: 7.
NAME: Coburn Land and Leasing, LLC Subdivision Site Plan Review
LOCATION: located at 11850 Arch Street
Planning Staff Comments:
1. Provide notification of the abutting property owners including the certified abstract
list, notice form with affidavit executed and proof of mailing. The notice must be
mailed no later than October 30, 2013. The Office of Planning and Development
must receive the proof of notice no later than November 8, 2013.
2. Provide the quantitative data including the building coverage, both principal and
accessory in square feet, the parcel size, the floor area, principal and accessory,
both existing and proposed and the proposed and existing parking spaces.
Variance/Waivers: None requested.
Public Works Conditions:
1. Arch Street Pike is classified on the Master Street Plan as a principal arterial.
Dedication of right-of-way to 55-feet from centerline will be required.
2. Vinson Road is classified on the Master Street Plan as a minor arterial. A dedication
of right-of-way 45-feet from centerline will be required.
Utilities and Fire Department/County Planning:
Wastewater: Outside the service boundary. Provide septic certification for the new
construction.
Entergy: Entergy has existing power lines on various lots on this site plan which will
need to remain. Developer/customer will need to work with Entergy for any facility
adjustments. Contact Entergy at 954-5158 for additional information.
Center -Point Energy: No comment received.
AT & T: No comment received.
Central Arkansas Water:
1. All Central Arkansas Water requirements in effect at the time of request for water
service must be met.
Item # 7.
2. The Little Rock Fire Department needs to evaluate this site to determine whether
additional public and/or private fire hydrant(s) will be required. If additional fire
hydrant(s) are required, they will be installed at the Developer's expense.
3. Please submit plans for water facilities and/or fire protection system to Central
Arkansas Water for review. Plan revisions may be required after additional review.
Contact Central Arkansas Water regarding procedures for installation of water
facilities and/or fire service. Approval of plans by the Arkansas Department of
Health Engineering Division and the Little Rock Fire Department is required.
4. Contact Central Arkansas Water regarding the size and location of the water meter.
5. A Capital Investment Charge based on the size of meter connection(s) will apply to
this project in addition to normal charges. This fee will apply to all connections
including metered connections off the private fire system.
6. If there are facilities that need to be adjusted and/or relocated, contact Central
Arkansas Water. That work would be done at the expense of the developer.
7. Due to the nature of this facility, installation of an approved reduced pressure zone
backflow preventer assembly (RPZA) is required on the domestic water service.
This assembly must be installed prior to the first point of use. Central Arkansas
Water requires that upon installation of the RPZA, successful tests of the assembly
must be completed by a Certified Assembly Tester licensed by the State of Arkansas
and approved by Central Arkansas Water. The test results must be sent to Central
Arkansas Water's Cross Connection Section within ten days of installation and
annually thereafter. Contact the Cross Connection Section at 377-1226 if you would
like to discuss backflow prevention requirements for this project.
8. The facilities on -site will be private. When meters are planned off private lines.
Private facilities shall be installed to Central Arkansas Water's material and
construction specifications and installation will be inspected by an engineer, licensed
to practice in the State of Arkansas. Execution of Customer Owned Line agreement
is required.
Fire Department: Provide a letter from the area Volunteer Fire Department indicating
their knowledge of the project. Place fire hydrant(s) per code. Maintain access.
Contact the Little Rock Fire Department for additional information.
County Planning:
1. Show source of title.
2. Provide septic approval for new and existing buildings.
3. Obtain fire department approval for new buildings.
4. Show FEMA flood panel information.
5. Show state plane coordinates.
6. Show existing contours.
7. Show vicinity map.
8. Pay $33.00 review fee.
Item # 7.
CATA: About two miles from nearest bus stop.
Parks and Recreation: No comment received.
Planning Division: No comment.
Landscape:
1. Compliance with the City's Landscape and Buffer Ordinances is required.
2. Landscaping is required for any new vehicular use areas and landscape upgrades
will be required for existing vehicular use areas.
3. If the site is over one (1) acre in size, an automatic irrigation system is required to
water landscape areas. If less than one (1) acre, a water source must be located
within seventy-five (75) feet of landscape areas.
4. A landscape plan prepared by a Design Professional as defined by the City's
Landscape Ordinance must be submitted and approved prior to any construction.
5. Buffers and opaque screening are required where the site abuts any residential use.
Revised plat/plan: Submit four (4) copies of a revised preliminary plat/plan (to include
the additional information as noted above) to staff on Wednesday, October 30, 2013.
Item # 7.
November 14, 2013
ITEM NO.: 7 FILE NO.: S-1714
NAME: Coburn Land and Leasing, LLC Subdivision Site Plan Review
LOCATION: Located at 11850 Arch Street
DEVELOPER:
Coburn Land and Leasing LLC
11850 Arch Street
Little Rock, AR 72206
SURVEYOR:
Brooks Surveying
20820 Arch Street Pike
Hensley, AR 72065
AREA: 30+ acres NUMBER OF LOTS: 1 FT. NEW STREET: 0 LF
CURRENT ZONING: Not Applicable —located within the City's Extraterritorial Planning
Jurisdiction in which the City exercises subdivision only
PLANNING DISTRICT:
CENSUS TRACT:
VARIANCEIWAIVERS
14 — Geyer Springs East
Sew
None requested.
A. PROPOSAL/REQUEST/APPLICANT'S STATEMENT:
The property is located within the City's planning jurisdiction in which the
subdivision ordinance only is enforced. Section 31-13 provides the criteria for
review of sites containing multiple buildings. The ordinance requires
developments involving the construction of two (2) or more buildings to be
reviewed and approved by the Planning Commission. The site contains
30+ acres. There were three (3) buildings located on site and the applicant has
recently constructed a fourth building. The new building is an 80-foot by 201-foot
building. The building will be used as a warehouse. The site does not have
public street frontage. The site is served by a 50-foot ingress/egress easement
extending from Arch Street Pike.
November 14, 2013
SUBDIVISION
ITEM NO.: 7 (Cont.) FILE NO.: S-1714
B. EXISTING CONDITIONS:
The property is located outside the City limits of Little Rock but within the City's
Extraterritorial Planning Jurisdiction. Within this area the City does not exercise
zoning jurisdiction but exercises only subdivision control. The property is located
in an industrial area. There are a number of businesses located along the
access easement, many of which have outdoor storage. Within the general area
there are residential and non-residential uses located along Arch Street Pike.
C. NEIGHBORHOOD COMMENTS;
As of this writing, staff not has received any comment from area residents
concerning the proposed request. All property owners located within 200-feet of
the site along with Southwest Little Rock United for Progress were notified of the
public hearing.
D. ENGINEERING COMMENTS:
PUBLIC WORKS CONDITIONS:
1. Arch Street Pike is classified on the Master Street Plan as a principal arterial.
Dedication of right-of-way to 55-feet from centerline will be required.
2. Vinson Road is classified on the Master Street Plan as a minor arterial.
A dedication of right-of-way 45-feet from centerline will be required.
E. UTILITIES AND FIRE DEPARTMENT/COUNTY PLANNING:
Wastewater: Outside the service boundary. Provide septic certification for the
new construction.
Entergy: Entergy has existing power lines on various lots on this site plan which
will need to remain. Developer/customer will need to work with Entergy for any
facility adjustments. Contact Entergy at 954-5158 for additional information.
Center -Point Energy: No comment received.
AT & T: No comment received.
Central Arkansas Water:
1. All Central Arkansas Water requirements in effect at the time of request for
water service must be met.
2
November 14, 2013
SUBDIVISION
FILE NO.: S-1714
2. The Little Rock Fire Department needs to evaluate this site to determine
whether additional public and/or private fire hydrant(s) will be required. If
additional fire hydrant(s) are required, they will be installed at the Developer's
expense.
3. Please submit plans for water facilities and/or fire protection system to Central
Arkansas Water for review. Plan revisions may be required after additional
review. Contact Central Arkansas Water regarding procedures for installation
of water facilities and/or fire service. Approval of plans by the Arkansas
Department of Health Engineering Division and the Little Rock Fire
Department is required.
4. Contact Central Arkansas Water regarding the size and location of the water
meter.
5. A Capital Investment Charge based on the size of meter connection(s) will
apply to this project in addition to normal charges. This fee will apply to all
connections including metered connections off the private fire system.
6. If there are facilities that need to be adjusted and/or relocated, contact Central
Arkansas Water. That work would be done at the expense of the developer.
7. Due to the nature of this facility, installation of an approved reduced pressure
zone backflow preventer assembly (RPZA) is required on the domestic water
service. This assembly must be installed prior to the first point of use.
Central Arkansas Water requires that upon installation of the RPZA,
successful tests of the assembly must be completed by a Certified Assembly
Tester licensed by the State of Arkansas and approved by Central Arkansas
Water. The test results must be sent to Central Arkansas Water's Cross
Connection Section within ten days of installation and annually thereafter.
Contact the Cross Connection Section at 377-1226 if you would like to
discuss backflow prevention requirements for this project.
8. The facilities on -site will be private. When meters are planned off private
lines. Private facilities shall be installed to Central Arkansas Water's material
and construction specifications and installation will be inspected by an
engineer, licensed to practice in the State of Arkansas. Execution of
Customer Owned Line agreement is required.
Fire Department: Provide
indicating their knowledge
Maintain access. Contact
information.
a letter from the area Volunteer Fire Department
of the project. Place fire hydrant(s) per code.
the Little Rock Fire Department for additional
3
November 14, 2013
SUBDIVISION
ITEM NO.: 7 (Cont.) FILE NO.: S-1714
County Planning:
1. Show source of title.
2. Provide septic approval for new and existing buildings.
3. Obtain fire department approval for new buildings.
4. Show FEMA flood panel information.
5. Show state plane coordinates.
6. Show existing contours.
7. Show vicinity map.
8. Pay $33.00 review fee.
CATA: About two miles from nearest bus stop.
Parks and Recreation: No comment received.
F. ISSUES/TECHNICAUDESIGN:
Planning Division: No comment.
Landscape:
1. Compliance with the City's Landscape and Buffer Ordinances is required.
2. Landscaping is required for any new vehicular use areas and landscape
upgrades will be required for existing vehicular use areas.
3. If the site is over one (1) acre in size, an automatic irrigation system is
required to water landscape areas. If less than one (1) acre, a water source
must be located within seventy-five (75) feet of landscape areas.
4. A landscape plan prepared by a Design Professional as defined by the City's
Landscape Ordinance must be submitted and approved prior to any
construction.
5. Buffers and opaque screening are required where the site abuts any
residential use.
G. SUBDIVISION COMMITTEE COMMENT: (October 23, 2013)
The applicant was not present. Staff presented an overview of the development
stating there were few outstanding technical issues associated with the request.
Staff stated the request was a Subdivision Site Plan Review request to allow the
4
November 14, 2013
SUBDIVISION
ITEM NO.: 7 (Cont.
FILE NO.: S-
placement of multiple buildings on a single parcel. Staff stated the site was
located outside the City limits but with the City's Extraterritorial Planning
Jurisdiction. Staff stated within this area the City did not exercise zoning only the
enforcement of the subdivision ordinance. Staff stated there were no outstanding
technical issues associated with the request in need of addressing via a revised
site plan. There was no further discussion of the item. The Committee then
forwarded the item to the full Commission for final action.
H. ANALYSIS:
There were no outstanding technical issues associated with the request in need
of addressing via a revised site plan. The applicant is seeking approval per
Section 31-13 of the Little Rock Code. The ordinance sets forth procedures for
processing multiple building site plans and to establish the standards for the
development of site. The Subdivision Site Plan review is a development review
process that provides for case by case consideration of project particulars
including the provision of parking and landscaping in accordance with the
appropriate ordinances, siting of buildings, and the relationship with adjoining
properties. The site contains 30± acres. There were three (3) buildings located
on site and the applicant has recently constructed a fourth building. The new
building is an 80-foot by 201-foot building to be used as a warehouse. The site
does not have public street frontage on Arch Street Pike. The site is served by a
50-foot ingress/egress easement extending from Arch Street Pike.
Staff is supportive of the request. Staff does not feel the placement of the
additional building on this site containing 30+ acres will significantly impact the
development or the area. The buildings have been placed with a substantial
setback from the property lines. The applicant has indicated with any additional
site improvements, landscaping will be brought in to compliance accordingly.
STAFF RECOMMENDATION:
Staff recommends approval of the request subject to compliance with the
comments and conditions as outlined in paragraphs D, E and F of the agenda
staff report.
PLANNING COMMISSION ACTION: (NOVEMBER 14, 2013)
The applicant was present. There were no registered objectors present. Staff
presented the item with a recommendation of approval of the request subject to
compliance with the comments and conditions as outlined in paragraphs D, E and F of
the agenda staff report.
November 14, 2013
SUBDIVISION
ITEM NO.: 7 (Cont.) FILE NO.: S-1714
There was no further discussion of the item. The chair entertained a motion for
approval of the item as recommended by staff. The motion carried by a vote of 8 ayes,
0 noes, 2 absent and 1 open position.
[: