HomeMy WebLinkAboutS-1639 Map 6STRUCTURAL QUALITY CONTROL & GENERAL NOTES
REVISIONS:
NO. OATE REVISION
SPECIAL INSPECTION ITEMS
SPECIAL INSPECTION PROGRAM
PER 2006 INTERNATIONAL BUILDING CODE CHAPTER 17 AND 1997 FEMA 302 CHAPTER 3.
ITEM
CON(TIN)UOUS
PERIODIC DIC
COMMENTS
DIVISION 2 - SOILS & FOUNDATION
GRADING EXCAVATION &FILL
X
BY GEOTECHNICAL ENGINEER
DRILLED PIERS
DIVISION 3 - CONCRETE
REINFORCING PLACEMENT
REINFORCING WELDING
REFERENCE NOTE 6
ANCHOR BOLTS & INSERTS
PREPARATION OF TEST SPECIMENS
X
CONCRETE PLACEMENT
X
EPDXY ANCHOR PLACEMENT
EXPANSION ANCHOR PLACEMENT
INSULATED CONCRETE FORMS
DIVISION 4 - STRUCTURAL MASONRY
REINFORCING PLACEMENT
UNIT PLACEMENT
GROUT PLACEMENT
DIVISION 5 - STRUCTURAL STEEL
WELDING OF ANCHORS AND STUDS
METAL DECK WELDING
EMBEDDED PLATES
DIVISION 5 - SHOP WELDING
SINGLE PASS FILLET WELDS S 5/16"
FIELD WELDS > 5/16"
PARTIAL/ COMPLETE PENETRATION WELDS
DIVISION 5 - FIELD WELDING
SINGLE PASS FILLET WELDS S 5/16"
FIELD WELDS > 5/16"
PARTIAL/ COMPLETE PENETRATION WELDS
ARCHITECTURAL COMPONENTS
VENEER ANCHORAGE & TIES
ANCHORAGE OF NON LOAD BEARING WALLS
SUSPENDED CEILINGS
MECHANICAL & ELECTRICAL COMPONENTS
X
ELECTRICAL EQUIP. ANCHORAGE
PROGRAM FOOTNOTES:
1. THE ITEMS CHECKED WITH AN "X" SHALL BE INSPECTED IN ACCORDANCE WITH 2O001BC BY A
CERTIFIED INSPECTOR FROM AN ESTABLISHED TESTING AGENCY. FOR MATERIAL SAMPLING AND TESTING
REQUIREMENTS, REFER TO THE MATERIAL SAMPLING AND TESTING SECTION. THE PROJECT
SPECIFICATIONS AND SPECIFIC GENERAL NOTES SECTIONS. THE TESTING -'-`% Y SHALL SEND COPIES
OF ALL STRUCTURAL TESTING AND INSPECTION REPORTS DIRECTLY TO - HITECT, ENGINEER,
CONTRACTOR AND BUILDING OFFICIAL. ANY MATERIALS WHICH FAIL TO M_- RC,:EC
SPECIFICATIONS SHALL IMMEDIATELY BE BROUGHT TO THE ATTENTION OF THE ARCHITECT/ENGINEER.
SPECIAL INSPECTION TESTING REQUIREMENTS APPLY EQUALLY TO ALL BIDDER DESIGNED
COMPONENTS.
2. SPECIAL INSPECTION IS NOT REQUIRED FOR WORK PERFORMED BY AN AISC CERTIFIED COMPLEX
BUILDING FABRICATOR.
3. CONTINUOUS SPECIAL INSPECTION MEANS THAT THE SPECIAL INSPECTOR IS ON THE SITE AT ALL
TIMES OBSERVING THE WORK REQUIRING SPECIAL INSPECTION 1997 FEMA 302. PERIODIC SPECIAL
INSPECTION MEANS THAT THE SPECIAL INSPECTOR IS ON SITE AT TIME INTERVALS NECESSARY TO
CONFIRM THAT ALL WORK REQUIRING SPECIAL INSPECTION IS IN COMPLIANCE.
4. ALL WELDS SHALL BE VISUALLY INSPECTED AFTER COMPLETION.
5. ALL COMPLETE PENETRATION WELDS SHALL BE TESTED UL TRASONICALLY OF BY USE OF A
COMPARABLE APPROVED METHOD.
6. PERIODIC SPECIAL INSPECTION IS ALLOWED FOR WELDING OF ASTM A-706 REINFORCING STEEL NOT
GREATER THAN NO. 5 USED FOR EMBEDMENTS. PROVIDED THE MATERIALS AND THE QUALIFICATIONS
OF WELDING PROCEDURES AND WELDERS ARE VERIFIED PRIOR TO THE START OF WORK_ PERIODIC
INSPECTIONS ARE MADE OF WORK IN PROGRESS, AND THAT A VISUAL INSPECTION OF ALL WELDS IS
MADE PRIOR TO COMPLETION OR PRIOR TO SHIPMENT OF WELDING SHOP WELDING ITEMS.
7, CONTINUOUS INSPECTION IS ONLY REQUIRED AT WELDS THAT ARE PART OF THE LATERAL LOAD
RESISTING SYSTEM.
SPECIAL INSPECTION ITEMS
1. SPECIAL INSPECTION SHALL BE PROVIDED BY THE OWNER ACCORDING TO SECTION 1704 OF VOLUME 2 OF
ARKANSAS FIRE PREVENTION CODE (IBC-2000). THE SPECIAL INSPECTOR SHALL OBSERVE THE WORK FOR
CONFORMANCE WITH THE CONTRACT DOCUMENTS. THE SPECIAL INSPECTOR SHALL SEND REPORTS TO THE
ARCHITECT/ENGINEER SHALL BE BROUGHT TO THE ATTENTION OF THE CONTRACTOR FOR CORRECTION. THE
SPECIAL INSPECTOR SHALL SUBMIT A FINAL SIGNED REPORT STATING THAT THE ADDITIONAL TESTING AND
INSPECTION WORK WAS, TO THE BEST OF HIS KNOWLEDGE, IN CONFORMANCE WITH THE PLANS,
SPECIFICATIONS AND APPLICABLE WORKMANSHIP PROVISIONS OF THE IBC. SPECIAL INSPECTION IS REQUIRED
FOR THE FOLLOWING WORK:
A. SOIL BEARING PRESSURE OF BOTTOMS OF ALL FOOTINGS.
B. CONCRETE PLACEMENT
C. BOLTS INSTALLED IN CONCRETE
D. CONCRETE REINFORCING STEEL
E. ANY STRUCTURAL WELDING
F. SHEAR WALLS
DESIGN CRITERIA
BUILDING CODE: 2002 ARKANSAS FIRE PREVENTION CODE, 2006 INTERNATIONAL BUILDING CODE
GRAVITY LOADS:
LIVE LOADS:
FLOORS: SLAB ON GRADE 80 PSF
ROOF: (DO NOT REDUCE) 20 PSF
DEAD LOADS:
ACTUAL WEIGHT OF MATERIALS
COLLATERAL (ROOF) 8 PSF
METAL BUILDING 3 PSF
LATERAL LOADS
WIND: (REFERENCE: ASCE 7-07)
BASIC WIND SPEED: 90 MPH
EXPOSURE: C
SEISMIC CRITERIA
I HEREBY CERTIFY THAT THE STRUCTURAL PLANS SUBMITTED HEREWITH ARE DESIGNED WITH THE STRUCTURAL
LOAD CARRYING ELEMENTS TO RESIST THE ANTICIPATED FORCES OF THE DESIGNATED SEISMIC ZONE IN WHICH
THE STRUCTURE IS LOCATED IN ACCORDANCE
WITH ARKANSAS ACT 1100, 1991.
ZONE CLASSIFICATION OF PROJECT ..........................ZONE
1 (ACT 1100)
SEISMIC USE GROUP.................................................1
SPECIAL RESPONSE ACCELERATION COEFFICIENTS
.... Sds= 0.46g/ Sd1= 0.24g
SITE CALSS................................................................B
SEISMIC DESIGN CATEGORY.......................................D
BASIC STRUCTURAL SYSTEM....... .............................COMMON
RIGID FRAMES & PORTAL FRAMES
SEISMIC FORCE RESISTING SYSTEM..........................COMMON
RIGID FRAMES & PORTAL FRAMES
RESPONSE MODIFICATION FACTOR.............................R=3.5
DEFLECTION AMPLIFICATION FACTOR ..........................Cd=
4.0
CTOR ........ .......................
OVERSTRENGTHACT
SYSTEM FA
0=2.5
ANALYSIS PROCEDURE .... ......... .........
........EQUIVALENT LATERAL FORCE PROCEDURE
tf
IF
7
STEPHEN M. YELEN ' H Fl E.
ARKANSAS RMSTf ATION NO.
�409
fJ
�r
STRUCTURAL DESIGN APPROACH:
PORT: 1. THE FOUNDATION SYSTEM IS DESIGNED AS A COMBINATION OF SPREAD AND
CONTINUOUS FOOTINGS WITH A STIFFENED TURNDOWN SLAB.
2. VERTICAL LOADS SHALL BE SUPPORTED BY PURLINS SPANNING BETWEEN
THE RIGID FRAMES.
3. THE METAL BUILDING SHALL BE STABILIZED BY RIGID FRAMES IN THE
TRANSVERSE DIRECTION AND CROSS BRACING AND OR PORTAL FRAMES IN
LONGITUDINAL DIRECTION.
PAD: 1. THE FOUNDATION SYSTEM IS DESIGNED AS A POST TENSIONED STIFFENED
TURNDOWN SLAB WITH INTERIOR RIBS.
A. STABILITY DURING CONSTRUCTION, SHORING AND TEMPORARY STRUCTURES:
1, PERMANENT STABILITY OF THE BUILDING AND COMPONENTS IS NOT PROVIDED
UNTIL ALL THE STRUCTURAL ELEMENTS ARE INSTALLED AS SHOWN ON THE
CONTRACT DRAWINGS: THE CONTRACTOR IS RESPONSIBLE FOR PROVIDING
STABILITY TO ALL NON -SELF SUPPORTING ELEMENTS AND SAFETY TO ALL
WORKERS, ANIMALS, AND PROPERTY DURING CONSTRUCTION AND UNTIL ALL
PERMANENT BRACING ELEMENTS ARE INSTALLED.
2• WHERE SHORING AND/OR TEMPORARY STRUCTURES ARE REQUIRED IN ORDER TO
SATISFY THE CONTRACT REQUIREMENTS: THE CONTRACTOR IS TO DESIGN AND
BUILD THE TEMPORARY STRUCTURES WITHOUT EXTRA COST TO THE CONTRACT.
3. BRACING USED TO STABILIZE THE BUILDING DURING THE ERECTION PROCESS
SHALL BE DESIGNED BY THE CONTRACTOR SO TO NOT TWIST OR DISTORT
MEMBERS.
4. THE ANCHOR BOLTS ARE NOT DESIGNED TO STABILIZE THE STRUCTURE BY
PROVIDING FIXITY. CONTRACTOR SHALL PROVIDE TEMPORARY BRACING FOR
STABILITY DURING THE ERECTION PHASE.
B. MISCELLANEOUS
1. WORK NOT INDICATED ON A PART OF THE DRAWING BUT REASONABLY IMPLIED TO BE
SIMILAR TO THAT SHOWN AT CORRESPONDING PLACES SHALL BE REPEATED.
2. ALL DIMENSIONS SHALL TAKE PRECEDENCE OVER SCALE SHOWN ON PLANS, SECTIONS,
AND DETAILS.
3. THE DETAILS SHOWN AND DESIGNATED AS "TYPICAL DETAILS" APPLY GENERALLY TO THE
DRAWINGS IN ALL AREAS WHERE CONDITIONS ARE SIMILAR TO THOSE DESCRIBED IN THE
DETAILS UNLESS NOTED OTHERWISE
4. THE DETAILS ON THE CONTRACT DRAWINGS SHALL NOT BE REVISED BY THE CONTRACTOR
WITHOUT PRIOR APPROVAL BY THE ARCHITECT/ENGINEER. IF PERMITTED THE REVISED
DETAILS AND CALCULATIONS SHALL BE DONE ONLY BY A LICENSED PROFESSIONAL
ENGINEER AND SUBMITTED TO THE ARCHITECT/ENGINEER. FOR APPROVAL-
5. STRUCTURAL DRAWINGS SHALL BE USED IN CONJUNCTION WITH DRAWINGS
RELATING TO OTHER TRADES. GENERAL CONTRACTOR SHALL BE RESPONSIBLE
FOR CHECKING AND COORDINATING DIMENSIONS, CLEARANCES, OPENINGS, PIPE
SLEEVES, CURBS, ETC. WITH THE WORK OF OTHER TRADES.
6. THE GENERAL CONTRACTOR SHALL EXAMINE THE DRAWINGS FOR REQUESTED OPENINGS
AND SHALL PROVIDE FOR ALL OPENINGS WHETHER SHOWN ON THESE DRAWINGS OR NOT,
AND SHALL VERIFY SIZE AND LOCATION OF ALL OPENINGS WITH ALL SUB -CONTRACTORS.
C. EARTHWORK AND FOOTINGS
1. TOP OF FOOTING ELEVATIONS ARE GIVEN FOR BIDDING PURPOSES ONLY. THE
TURNDOWN SLAB BEARING ON CONTINUOUS FOOTINGS IN SHALE/CLAY ARE DESIGNED
FOR AN ALLOWABLE BEARING PRESSURE OF 1500 PSF. CONTRACTOR TO FIELD VERIFY
SOIL BEARING CAPACITY PRIOR TO PLACEMENT OF CONCRETE.
2. THE CONTRACTOR SHALL TAKE ADEQUATE MEASURES TO ALLOW FOR WORKING SURFACE
DURING CONSTRUCTION OF FOUNDATIONS AND SLAB -ON -GRADE, SUCH AS A
GRAVEL BED OF ADEQUATE DEPTH, ETC.
3. CONTRACTOR TO PROVIDE FOR DE -WATERING OF EXCAVATIONS FROM EITHER
SURFACE WATER, GROUND WATER OR SEEPAGE. SOME SURFACE WATER IS
ANTICIPATED IN EXCAVATIONS, AND THEY SHALL BE DE -WATERED BEFORE
PLACING CONCRETE.
4. CONTRACTOR SHALL PROVIDE AND INSTALL ALL CRIBBING, SHEATHING, AND
SHORING REQUIRED TO SAFELY RETAIN THE EARTH BANKS. SHORING AND
BRACING OF TRENCHES SHALL MEET THE REQUIREMENTS OF OSHA,
IF REQUIRED.
5. CONTRACTOR SHALL PROTECT ALL UTILITY LINES, ETC. ENCOUNTERED
DURING EXCAVATION AND BACKFILLING.
6. ALL FOUNDATION WORK SHALL MEET THE APPROVAL OF THE GEOTECHNICAL
CONSULTANT AND THE ARCHITECT/ENGINEER.
D. CONCRETE AND REINFORCING STEEL
1. THE DESIGN OF THE CONCRETE FOUNDATION AND SLAB ON GRADE IS BASED
ON ACI 318-07. SHALL GOVERN
ACI CODE PROVISIONS N ALL PHASES OF
CONCRETE CONSTRUCTION AND CURING.
SHALL B - 2. ALL REINFORCEMENTE A 615 GRADE 60 STEEL.
3. ALL REINFORCEMENT SHOULD BE SECURELY HELD IN PLACE WHILE PLACING
CONCRETE. IF REQUIRED, ADDITIONAL BARS OR STIRRUPS SHALL BE PROVIDED BY
THE CONTRACTOR TO FURNISH SUPPORT FOR ALL BARS.
4. ALL REINFORCING BARS SHALL BE LAPPED 48 BAR DIAMETERS - 24" MIN. U.N.O.
TERMINATE CONTINUOUS BARS AT NON CONTINUOUS END WITH STAN
DARD HOOKS.
TENSION REINFORCEMENT IN GRADE BEAMS SHALL BE LAPPED TO 60 BAR DIAMETERS.
5. CONCRETE COVER FOR REINFORCING STEEL SHALL BE 1" FOR SLABS
ALL CONCRETE EXPOSED TO WEATHER OR EARTH SHALL HAVE
CONCRETE COVER OF 2" FOR BARS LARGER THAN 5 "
# 1-1 /2FOR #5 BARS OR
SMALLER, AND 3" FOR ALL CONCRETE PLACED AGAINST EARTH, U.N.O. TOLERANCES
SHALL BE AS PER ACI-318.
6. PIPES OR CONDUITS PLACED IN FOUNDATION AND SLABS SHALL NOT BE SPACED
CLOSER THAN 3 DIAMETERS ON CENTER. PIPES AND CONDUITS PLACED IN SLAB
SHALL NOT HAVE AN OUTSIDE DIAMETER LARGER THAN 1/3" OF SLAB THICKNESS.
ALUMINUM CONDUITS SHALL NOT BE PLACED IN CONCRETE.
7. PROVIDE CORNER BARS IN ALL STIFFENED TURNDOWN SLAB INTERSECTIONS, BARS
SHALL MATCH SIZE AND SPACING OF HORIZONTAL BARS IN THOSE MEMBERS.
8. LOCATION OF SLOTTED INSERTS, WELD PLATES, ANCHOR RODS AND ALL OTHER ITEMS
TO BE EMBEDDED IN CONCRETE SHALL BE COORDINATED WITH ARCHITECTURAL AND
MECHANICAL DRAWINGS.
9. REINFORCING BARS SHALL NOT BE WELDED, UNLESS SPECIFICALLY NOTED ON THE
DRAWING AS BEING WELDED. WELDED REINFORCING SHALL CONFORM TO ASTM A706.
10.ALL CONCRETE WORK SHALL CONFORM TO THE LATEST ACI CODE AND DETAILING
MANUAL.
11. CONTRACTOR SHALL VERIFY DIMENSIONS AND LOCATIONS OF ALL OPENINGS,
PIPE SLEEVE CURBS, ETC., AS REQUIRED BY OTHER TRADES BEFORE CONCRETE
IS PLACED.
12. ALL LAPS IN WELDED WIRE FABRIC SHALL BE ONE MESH PLUS TWO INCHES
AT SPLICES.
13. COARSE AGGREGATE FOR CONCRETE SHALL NOT CONTAIN LIGNITE, STEEL, OR
OTHER MATERIALS THAT MAY BE DETRIMENTAL TO THE CONCRETE.
14.MAXIMUM TOLERANCE FOR SLAB EDGES IS 1/2"f EXCEPT WHERE TIGHTER
TOLERANCE IS REQUIRED FOR ARCHITECTURAL REASONS.
15. CONCRETE PLACED WHEN AIR TEMPERATURES EXCEEDING 90 DEGREES F. ARE
EXPECTED SHALL BE CURED BY MOIST CURING METHODS INCLUDING COVERING
WITH PLASTIC OR BURLAP AND KEPT MOIST FOR 7 DAYS MINIMUM.
16.FLY ASH MAY BE SUBSTITUTED FOR CEMENT CONTENT AT NOT MORE THAN 15%
17. THE TOTAL ALLOWABLE MIX WATER (INCLUDES WATER AT BATCH PLANT PLUS
ANY FIELD ADDED WATER) CONTENT SHALL NOT EXCEED THE VALUE AT WHICH
THE MIX DESIGN WAS CERTIFIED BY LAB TESTS. GENERALLY THE SLUMP SHALL
BE 5" WITH A TOLERANCE OF -1" AND 42". THE CONCRETE DELIVERY TICKET
SHALL SHOW THE AMOUNT OF WATER ADDED IN FIELD, IF APPLICABLE.
18. CONCRETE STRENGTH AT 28 DAYS:
ITEM
MIN. STRENGTH
AIR ENTRAINING
WATER REDUCING
ADMIX REQUIRED
REINFORCED FOOTINGS
3.0 KSI
WRA
EXTERIOR SLABS
3.0 KSI
5% AIR
WRA
INTERIOR SLAB ON GRADE
3.0 KSI
3% AIR
WRA
*WRA - INDICATES WATER REDUCING ADMIXTURE
E. POST TENSIONED CONCRETE
1. ALL POST -TENSIONING TENDONS AND REINFORCING SHALL BE SIZED BY
POST -TENSIONING ENGINEER. PROVIDE COMPLETE DRAWINGS SEALED BY AN ENGINEER
REGISTERED IN THE STATE OF ARKANSAS.
2. FOUNDATION SECTIONS SHOWN ARE FOR GENERAL INFORMATION ONLY. THE POST
TENSIONING ENGINEER MAY CHANGE SIZES AND/OR CONFIGURATION OF FOOTINGS,
REINFORCING, AND TENDONS.
3. ALL POST TENSIONING TENDONS SHALL BE 7 WIRE LOW RELAXATION STRAND
CONFORMING TO ASTM A416.
4. TENDONS SHALL NOT BE FULLY STRESSED UNTIL CONCRETE HAS REACHED A MINIMUM
COMPRESSIVE STRENGTH OF 2000 PSI. A PARTIAL STRESS OF 25% OF FULL STRESS
MAY BE APPLIED TO CABLES 24 HOURS MINIMUM AFTER THE POUR IS COMPLETED.
5. CALCIUM CHLORIDE NOR ANY OTHER ADD MIXTURES THAT IS CORROSIVE TO METALS
SHALL BE ADDED TO THE CONCRETE MIX.
& THE P/T CONTRACTOR SHALL COMPUTE THE TENDON INITIAL FORCE, THE TENSION FORCE
AFTER SHORT TERM REDUCTION, AND THE TENSION FORCE AFTER LONG TERM
REDUCTION.
7. THE EXPECTED ELONGATION OF EACH CABLE WHEN STRESSED SHALL BE INDICATED ON
THE P/T SHOP DRAWINGS.
b
F. PRE-ENGINEERED METAL BUILDINGS
1. THE PRE-ENGINEERED METAL BUILDING SUPPLIER SHALL DESIGN THE PRE-
ENGINEERED METAL BUILDING FOR THE LOADS AND CRITERIA SHOWN ON THE
PLANS AND SPECIFICATIONS.
2. SHOP DRAWINGS AND CALCULATIONS SHALL BE SEALED BY A REGISTERED
PROFESSIONAL ENGINEERING IN THE STATE OF ARKANSAS AND SUBMITTED TO
THE ENGINEER FOR REVIEW.
3. THE PRE-ENGINEERED METAL BUILDING SUPPLIER SHALL SUPPLY COLUMN
REACTIONS FOR DESIGN OF THE FOUNDATION BY THE ENGINEER.
4. ALL WELDING SHALL BE PERFORMED BY WELDERS CERTIFIED BY AWS TO
PERFORM THE WELDING IN ACCORDANCE WITH AWS.
5. FINAL BOLTING OR WELDING SHALL NOT BE PERFORMED UNTIL THE STRUCTURE
HAS BEEN PROPERLY ALIGNED.
6. PRE-ENGINEERED METAL BUILDING MANUFACTURER SHALL DESIGN THE BUILDING
FOR A MAXIMUM DRIFT OF h/200 UNDER WORST LATERAL LOAD COMBINATION.
COLUMN BASES SHALL BE ASSUMED TO BE PINNED.
7. LOCATION OF THE PRE-ENGINEERED METAL BUILDING COLUMNS SHOWN AS A
GENERAL ARRANGEMENT. MANUFACTURER SHALL DESIGN METAL BUILDING SYSTEM
AND SUBMIT FINAL COLUMN REACTIONS, SHOP DRAWINGS AND ERECTION
DRAWINGS WITH DIMENSIONS FOR APPROVAL PRIOR TO BEGINNING CONSTRUCTION
OPERATIONS. CONTRACTOR SHALL VERIFY ALL SPAN ARRANGEMENTS AND COLUMN
LOCATIONS.
B. PRE-ENGINEERED METAL BUILDING MANUFACTURER SHALL PROVIDE WRITTEN
CERTIFICATION THAT THE BUILDING COMPONENTS ARE IN COMPLIANCE WITH
A.I.S.C., A.I.S.I. & DESIGN LOADS IN ACCORDANCE WITH CHAPTER 16, 2006 I.B.C.
ABBREVIATIONS
ADJ.
ADJACENT
ADD'L
ADDITIONAL
A.F.F.
ABOVE FINISHED FLOOR
APPROX.
APPROXIMATE
ARCH.
ARCHITECTURAL
BD
BOARD
B.F.F.
BELOW FINISHED FLOOR
BM.
BEAM
BOT,
BOTTOM
C
CHANNEL
CJ
CONTROL JOINT
CLR
CLEAR.
CMU
CONCRETE
MASONRY UNIT
COL. t
C@
U'AN
CONC.
COICPETE
CONN.f
CONNLaSTION
CONT.
CONTINUOUS
CTR'D
CENTERED
DB
DECK BEARING
D.B.A.
DEFOr MED BAR ANCHOR
DIMENS16N
DIM.
DTL.
DETAIL
EA,
EACH
E. F.
EACH FA E
ELEV.
ELEVATION
E.W.
EACH WAY
EXP.
EXPANSION
EXT.
EXTERIOR
F. D.
FOUNDATION DRAIN
FDN
FOUNDATION
FTG
FOOTING
GA
GAGE
GALV.
GALVAN17ED
G.C.
GENERAL CONTRACTOR
HOP
H'GH CHAIRS WITH PLATES
HORIZ.
HORIZONTAL
HISS
FOLLOW STRUCTURAL STEEL
IN.
NGH
JT.
JOINT
K
KIPS
KCJ
KEYED CONSTRUCTION
JOINT
K5F KPS P SQUARE FOOT
L TENSION DEVELOPMENT
LEENGTH OF BAR
LLH
_ONO LEG HORIZONTAL
LLV
_ONG LEG VERTICAL
LT.
UGHT
MATL.
MATERIAL
MAX.
MAXIMuM
MIN.
MINIMUM
N.T.S.
:NOT TO SCALE
O.C.
ON CENTER
PSI
POUNDS PER SQUARE INCH
REINF.
REINFORCEMENT
REQ'D.
REQUIRED
SECT.
SECTION
SHT.
SHEET
SIM.
SIMILAR
SPA.
SPACING
STD.
STANDARD
TB
TIE BEAM
T.O.F.
TOP OF FOOTING
T.O.S.
TOP OF STEEL
TS
THICKENED SLAB
TYR
TYPICAL
U.N.O.
UNLESS NOTED OTHERWISE
VERT.
VERTICAL
V.I.F.
VERIFY IN FIELD
W/
WITH
W.S.
WATER STOP
WT,
WEIGHT
ZRC
ZINC BASE PAINT
SYMBOLS
L
ANGLE
*
AT
0
DIAMETER
#
NUMBER
<
LESS THAN
>
GREATER THAN
h
PLATE
CENTERLINE
PROJECT NAME:
F_
OQ
z
W
cc
Q
Z
W
U
Uw
Ir
O
-'
SHEET TITLE:
STRUCTURAL
QUALITY CONTROL &
GENERAL NOTES
PROJECT NUMBER
HW9-360
PROJECT DATE:
JUNE 2009
SHEET NUMBER:
S-1.0