HomeMy WebLinkAboutS-1639 Map 12SEE SITE PLAN
AND CIVIL PLANS FOR ROUTING
1O NEW 24OV/1P, 200A, WEATHERPROOF, FUSED, LOCKABLE SERVICE ENTRANCE
DISCONNECT SWITCH. FUSE AT 100A,
2O GROUND PER NEC ARTICLE 250.
J NEW 18 CKT, 100A, 24OV,1P MLO PANELBOARD. SEE SCHEDULE THIS
SHEET, PROVIDE WITH LOCKABLE, NEMA 3R ENCLOSURE.
(3) #3, #8G, 1-1/4" C.
O (3) #1, #6G, 1-1/4" C.
:311
'C. W/ 3#12 TO HEUPAD UGHTING
® EXISTING 240V, HIGH LEG DELTA PANELBOARD WITH SPARE CAPACITY
AND SPACE AVAILABLE FOR NEW 100A FEED TO PANEL "LA". FIELD
VERIFY ALL REQUIREMENTS. SECURE PEAK DEMAND LOAD FROM UTILITY
COMPANY TO ENSURE THAT NEW LOAD DOES NOT EXCEED PANEL RATING
AFTER NEC MANDATED DIVERSIFICATION.
OPROVIDE NEW 100A/2P CIRCUIT BREAKER TO MATCH EXISTING. NEW
BREAKER SHALL BE SAME MAKE, MANUFACTURER AND AIC RATING.
OPROVIDE NEW 20A/1P CIRCUIT BREAKER TO MATCH EXISTING. NEW
BREAKER SHALL BE SAME MAKE, MANUFACTURER AND AIC RATING.
1 ELECTLE RICAL RISER DIAGRAM
BURNDY #GAR OR EQUAL
(LOCATE WITHIN 5' - 0"
OF WATER SERVICE) —
1" OR LARGER METAL COLD
WATER PIPING 10' - 0"
LINEAR FOOT MINUMUM
UNDERGROUND IN DIRECT
CONTACT WITH EARTH AND
ELECTRICALLY CONTINUOUS
TO BONDING CONNECTION
IN ACCESSIBLE LOCATION
UNSPLICED - NEUTRAL TI
REBAR PER NEC 250-81,
250-81b, & 250-SIC -
EXOTHERMIC WELD
CONNECTION - TYPICAL -
STRUCTURE —
BUILDING EXTEER
CONDUCTOR TO BE
INSULATED WHERE
IN CONTACT WITH
CONCRETE
REINFORCED
CONCRETE
FOOTING
o = EXOTH1ER%4C WELD CONKCTION
(CADWELD OR EQUAL)
2 SERVICE
SCALE NONE
GROUNDING BUSHING WITH
BONDING CONDUCTOR
SAME SIZE AS GROUNDING
ELECTRODE CONDUCTOR
LOW RESISTANCE ENCASEMENT
CADWELD "GEM" OR EQUAL
(BELOW VAPOR BARRIER)
14 REBAR, 20' - 0" MINIMUM
TOTAL LENGTH - LOCATE AS
NEAR BOTTOM OF FOOTING AS
POSSIBLE BUT NO LESS THAN
2" FROM BOTTOM AND SIDE
OF FOOTING
NCE GROUNDING DETAIL
Q `
PANELBOARD; L
VOLTAGE: 120/24OV, 10, 3W
BUS RATING: 1ODA
100A M.L.O.
TOTAL _
CONNECTED VA:
TOTAL A 0 : -
HANGER
LOCATION:
MFG. GE OR
AND CUTLER HAMMER
TYPE;
EQUIP,
GRD• YES
BUS;
ISOL
GRID. NO
BUS:
TOTAL B -
SURFACE
MOUNTING:
NEMA 3R
ENCLOSURE:
MINIMUM
AI.C. 10,000
RATING:
NG
FED PANEL EXISTING
FROM;
LOAD
(VA)
SERVES
P
CAR.
NO.
n
^
^
n
n
^
^
AB
¢¢
^
^
n
^
n
(1
CAR.
NO.
P
VT
SERVES
LOAD
(VA)
A
s
A
s
1300
LIGHTING
1
1
2
1
SECURITY SYSTEM
-
1300
UGHTING
3
4
1
EXHAUST FAN
1700
1200
OVERHEAD DOOR MOTOR
1
5
6
1
SPARE
-
1200
GATE OPERATOR
1
7
8
1
SPARE
-
500
EXTERIOR RECEPTACLE
1
9
10
1
SPARE
-
850
EXTERIOR UGHTING
11
12
1
SPARE
-
1080
RECEPTACLES
1
�3
14
1
SPARE
-
1080
SPARE
15
16
1
SPARE
-
1080
SPARE
17
18
1
SPARE
-
-
SPARE
19
2O
1
SPARE
-
II PANELBOARD LEGEND 11
* U,L LISTED HACR TYPE CIRCUIT BREAKER
• U.L LISTED ARC -FAULT CIRCUIT BREAKER
COORDINATE LOCATION WITH PLUMBING PLANS
■ ROUTE THROUGH RELAY/TIMECLOCK
r---------------------- 1
TIME CLOCK, TORK
#DGLC, OR EQUAL,
MOUNTED IN ELEC. RM.
141
SEE NOTE I BELOW
20A, 120V
"LA"-4
PHOTOELECTRIC CELL
TORK #EPC1, OR
EQUAL, CONDUIT
MOUNTED ON ROOF
y9IE:
1. TIME CLOCK CIRCUIT #1 PROVIDES (PHOTO ON / TIME OFF) OPERATION.
CIRCUIT #2 PROVIDES (PHOTO ON / PHOTO OFF) OPERATION. VERIFY DESIRED
OPERATION WITH OWNER.
3 LIGHTING CONTROL DIAGRAM
SCALE NONE
110
LTG
It
l000//S<�oP
ee ARKANSAS�=
e REG`itED�`
P1t0 E IONAL\l,;
I ER �
_E
* ee
�T 10213��i'ee
V R/
loci
z
O
H
n
E
U
N
Ld
c�
LJ
H
Q
0
LiJ
F---IlI
M--�1
IW
F--1
H+W
Heiple Wiedower
Architects Planners
319 President Clinton Ave.
Little Rock, AR 72201
(t)501-707-0115
(f) 501-707-0118
Project No:
HW9-360
Date:
06-16-09
Sheet Title:
ELECTRICAL
DETAILS
4 Of 4
Sheet No:
E4m1
e
Drawing Property of H+W Architects PLLC 2009