NAME: Gateway Apartments Subdivision Site Plan Review
LOCATION: located in the 11500 Block of Bass Pro Parkway
Plannina Staff Comments:
S-1538-Q
1. Provide notification of the abutting property owners including the certified abstract list,
notice form with affidavit executed and proof of mailing. The notice must be mailed no
later than October 16, 2018. The Office of Planning and Development must receive the
proof of notice no later than October 26, 2018.
2. Provide details of the proposed signage plan. Will signage be as allowed in Commercial
Zones? Maximum 36-feet in height and 160 square feet in area
3. Verify the number of parking spaces. I calculate 413 parking spaces. The site plan note
indicates 404 parking spaces.
4. Note on the site plan the one-way gate entrances and exists.
5. Provide the building height proposed in the general notes section of the site plan.
6. Provide the proposed phasing plan. Will the units all be developed in a single phase? If
not note the proposed phasing plan in the general notes section of the site plan.
7. Note on the site plan the location of the USPS Mail Kiosk.
Variance/Waivers.
1. A variance from Section 36-302(d) to allow an increased building height.
2. A variance from Section 36-522 to allow a reduced land use buffer adjacent to the OS,
Open Space zoned property.
Engineering Comments:
Public Works Conditions:
1. Provide locations of streets and driveway intersections on the east side of Bass Pro
Parkway in the vicinity of the proposed driveway location.
2. Swimming pool discharge cannot be directly connected to the stormwater drainage
system. Discharge should be taken to an open, vegetated area for water treatment prior
to entering the City of Little Rock Municipal Separate Stormwater Sewer System.
3. Show the proposed location of fencing and gates along with control points. Turn around
must be provided for a SU-30 vehicle attempting to enter development. A stacking
distance of 30-feet from pavement must also be provided.
4. All driveways shall be concrete aprons per City Ordinance.
5. Repair or replace any curb, gutter, sidewalk and access ramps that are damaged and not
in compliance with ADA recommendations in the public right-of-way prior to occupancy.
6. A grading permit in accordance with Section 29-186 (c) and (d) will be required prior to
any land clearing or grading activities at the site. Other than residential subdivisions, site
grading and drainage plans must be submitted and approved prior to the start of
ITEM NO.: 5.
S-1538-Q
construction.
7. Stormwater detention ordinance applies to this property. Maintenance of the detention
pond and all private drainage improvements is the responsibility of the developer and/or
property owners association and detailed in the bill of assurance.
8. If disturbed area is one (1) or more acres, obtain a NPDES stormwater permit from the
Arkansas Department of Environmental Quality prior to the start of construction.
9. With the property being adjacent to the floodplain, the minimum Finish Floor elevation of
at least one (1) foot above the base flood elevation is required to be shown on plat and
grading plans.
10. Hauling of fill material on or off site over municipal streets and roads requires approval
prior to a grading permit being issued. Contact Public Works Traffic Engineering, Travis
Herbner, therbner ar7littlerock.gov or 501.379.1805 for more information.
11. Damage to public and private property due to hauling operations or operation of
construction related equipment from a nearby construction site shall be repaired by the
responsible party prior to issuance of a certificate of occupancy.
12. The owner and/or manager of each multi -family residence of 100 or more dwelling units
shall provide recycling and encourage participation by the tenants, renters, or owners of
each unit. Contact Melinda Glasgow, m las ow littlerock. ov or 501.371.4646 for more
information.
13. Submit a Traffic Impact Study for the proposed project. Study should address trip
generation and trip distribution for the development and also should take into account
existing and projected traffic.
Utilities/Fire DepartmentlParks/County Planning:
Little Rock Water Reclamation Authority: Sewer main extension required with easements if
sewer service is required for this project. Capacity Fee analysis required. Contact Little
Rock Water Reclamation Authority for additional information
Entergy: Entergy does not object to this proposal. There do not appear to be any conflicts
with existing electrical utilities at this location. There is an existing three phase, underground
power line along the west side of Bass Pro Parkway which should be located and avoided
during the construction of this project. Contact Entergy in advance to discuss electrical
service requirements, or adjustments to existing facilities (if needed).
Centerpoint Energy: No comment received.
AT & T: No comment received.
Central Arkansas Water: No comment received.
Fire Denartment:
1 Full Plan Review — Maintain Access
2. Fire Hydrants. Maintain fire apparatus access roads at fire hydrant locations as per
Appendix D of the 2012 Arkansas Fire Prevention Code Vol. 1 Section D103.1 Access
2
ITEM NO.: 5.
S-1538-Q
road width with a hydrant. Where a fire hydrant is located on a fire apparatus access road,
the minimum road width shall be 26 feet, exclusive of shoulders.
3. Grade. Maintain fire apparatus access roads as per Appendix D of the 2012 Arkansas
Fire Prevention Code Vol. 1 Section D103.2 Grade. Fire apparatus access roads shall not
exceed 10 percent in grade except as approved by the fire chief.
4. Loading. Maintain fire apparatus access road design as per Appendix D of the 2012
Arkansas Fire Prevention Code Vol. 1 Section D102.1 Access and loading. Facilities,
buildings or portions of buildings hereafter constructed shall be accessible to fire
department apparatus by way of an approved fire apparatus access road with an asphalt,
concrete or other approved driving surface capable of supporting the imposed load of fire
apparatus weighing at least 75,000 pounds.
5. Commercial and Industrial Developments — 2 means of access. - Maintain fire apparatus
access roads as per Appendix D of the 2012 Arkansas Fire Prevention Code Vol. 1
a. Section D104.1 Buildings exceeding three stories or 30 feet in height. Building
or facilities exceeding 30 feet or three stories in height shall have at least two
means of fire apparatus access for each structure.
b. Section D104.2 Building exceeding 62,000 square feet in area. Buildings or
facilities having a gross building area of more than 62,000 square feet shall be
provide with two separate and approved fire apparatus access roads.
c. Exception: Projects having a gross building area of up to 124,000 square feet
that have a single approved fire apparatus access road when all building are
equipped throughout with approved automatic sprinkler systems.
d. D104.3 Remoteness. Where two fire apparatus access roads are required, they
shall be placed a distance apart equal to not less than one half of the length of
the maximum overall diagonal dimension of the lot or area to be served,
measured in a straight line between accesses.
6. 30' Tall Buildings - Maintain aerial fire apparatus access roads as per Appendix D of the
2012 Arkansas Fire Prevention Code Vol. 1 Section D105.1 — D105.4
a. D105.1 Where Required. Where the vertical distance between the grade plane
and the highest roof surface exceed 30', approved aerial fire apparatus access
roads shall be provided. For the purposes of this section the highest roof
surfaces shall be determined by measurement to the eave of a pitched roof, the
intersection of a roof to the exterior wall, or the top of the parapet walls,
whichever is greater.
b. D105.2 Width. Aerial fire apparatus access roads shall have a minimum
unobstructed with of 26', exclusive of shoulders, in the immediate vicinity of the
building or portion thereof.
c. D105.3 Proximity to building. At least one of the required access routes meeting
this condition shall be located within a minimum of 15 feet and a maximum of
30 feet from the building, and shall be positioned parallel to one entire side of
ITEM NO.: 5,
S-1538-Q
7
0
the building. The side of the building on which the aerial fire apparatus access
road is positioned shall be approved by the fire code official.
d. D105.4 Obstructions. Overhead utility and power lines shall not be located over
the aerial fire apparatus access road or between the aerial fire apparatus road
and the building. Other obstructions shall be permitted to be places with the
approval of the fire code official.
Dead Ends. Maintain fire apparatus access roads at dead end locations as per Appendix
D of the 2012 Arkansas Fire Prevention Code Vol. 1 Section D103.4 Dead Ends. Dead-
end fire apparatus access roads in excess of 150 feet shall be provided with width and
turnaround provisions in accordance with Table D103.4. Requirements for Dead-end fire
apparatus access roads.
Gates. Maintain fire apparatus access road gates as per Appendix D of the 2012
Arkansas Fire Prevention Code Vol. 1 Section D103.5 Fire apparatus access road gates.
Gates securing the fire apparatus access roads shall comply with all of the following
criteria:
1. Minimum gate width shall be 20 feet.
2. Gates shall be of swinging or sliding type.
3. Construction of gates shall be of material that allow manual operation by one
person.
4. Gate components shall be maintained in an operable condition at all times and
replaces or repaired when defective.
5. Electric gates shall be equipped with a means of opening the gate by fire
department personnel for emergency access. Emergency opening devices shall
be approved by the fire code official.
6. Manual opening gates shall not be locked with a padlock or chain and padlock
unless they are capable of being opened by means of forcible entry tools or
when a key box containing the keys to the lock is installed at the gate location.
7. Locking device specifications shall be submitted for approval \by the fire code
official
8. Electric gate operators, where provided, shall be listed in accordance with UL
325.
9. Gates, intended for automatic operation shall be designed, constructed and
installed to comply with requirements of ASTM F 2200.
9. Fire Hydrants, Locate Fire Hydrants as per Appendix C of the 2012 Arkansas Fire
Prevention Code. Section C101 — C105, in conjunction with Central Arkansas Water
(Jason Lowder 501.377.1245) and the Little Rock Fire Marshal's Office (Capt. Tony
Rhodes 501.918.3757 or Capt. John Hogue 501.918.3754). Number and Distribution of
Fire Hydrants as per Table C105.1.
Parks and Recreation: No comment received.
County Planning: No comment.
4
ITEM NO.: 5.
S-1538-Q
Building Codes/Landscape:
Building Cade: Project is subject to full commercial plan review and approval prior to
issuance of a building permit. For information on submittal requirements and the review
process, contact a commercial plans examiner: Curtis Richey at 501.371.4724;
crichey(d), I ittle rock. gov
Landscape:
1. Site plan must comply with the City's landscape and buffer ordinance requirements.
2. A perimeter planting strip is required along any side of a vehicular use area that abuts
adjoining property or the right-of-way of any street. This strip shall be at least nine (9) feet
wide. One (1) tree and three (3) shrubs or vines shall be planted for every thirty (30) linear
feet of perimeter planting strip. The southwest perimeter planting strip is deficient.
3. Eight percent (8%) of the vehicular use area must be designated for green space; this
green space needs to be evenly distributed throughout the parking area(s). For
developments with more than one hundred fifty (150) parking spaces the minimum size of
an interior landscape area shall be three hundred (300) square feet. Interior islands must
be a minimum of seven and one half (7 1/2) feet in width. Trees shall be included in the
interior landscape areas at the rate of one (1) tree for every twelve (12) parking spaces.
4. Building landscape areas shall be provided between the vehicular use area used for
public parking and the general vicinity of the building. These shall be provided at the rate
equivalent to planter strip three (3) feet wide along the vehicular use area. One (1) tree
and four (4) shrubs shall be planted in the building landscape areas for each forty (40)
linear feet of vehicular use area abutting the building.
5. An irrigation system shall be required for developments of one (1) acre or larger.
6. The development of two (2) acres or more requires the landscape plan to be stamped with
the seal of a Registered Landscape Architect.
7. If any of the landscape code requirements cannot be met a variance from the City
Beautiful Commission may be required before a building permit is issued.
8. The City Beautiful Commission recommends preserving as many existing trees as
feasible on this site. Credit toward fulfilling Landscape Ordinance requirements can be
given when preserving trees of six (6) inch caliper or larger.
Tra nsportation/Plan ni ng
Rock Region Metro: This site is across the street from a stop of ours. There is some
connectivity between the sidewalk on Bass Pro Parkway and the proposed facilities. There
does not appear to be a direct sidewalk connection between the street and the southeastern-
most building in the plan (one of the buildings labelled "Building Type A Total Units 30"). We
request that the sidewalk be extended from this building out to the street.
Planning Division: No comment received.
ITEM NO.: 5. S-1538-Q
Revised plat/plan: Submit four (4) copies of a revised preliminary plat/plan (to include the
additional information as noted above) to staff on or before Wednesday, October 17, 2018. If
you have any questions please contact Dana Carney, dcarneyCa?littlerock.gav or
501.371.6817 or Jamie Collins, gcollins �_littlerock.gov or 501.371.6818.
November 1, 2018
ITEM NO.: 5 FILE NO.: S-1538-Q
NAME: Gateway Apartments Subdivision Site Plan Review
LOCATION: Located in the 11500 Block of Bass Pro Parkway
DEVELOPER:
Gateway Creek, LLC
c/o The Hodges Group
11601 Bass Pro Parkway
Little Rock, AR 72210
OWNER/AUTHORIZED AGENT:
Gateway Creek, LLC, Owner
McGetrick Engineering, Agent
SURVEYOR/ENGINEER:
McGetrick Engineering
11601 Bass Pro Parkway
Little Rock, AR 72210
AREA: 8.42-acres NUMBER OF LOTS: 1 FT. NEW STREET: 0 LF
WARD: 7 PLANNING DISTRICT: 16 — Otter Creek CENSUS TRACT: 41.03
CURRENT ZONING: C-4, Open Display District
VARIANCE/WAIVERS:
1. A variance from Section 36-302(d) to allow an increased building height.
2. A variance from Section 36-522 to allow a reduced land use buffer adjacent to the OS,
Open Space zoned property.
A. PROPOSAL/REQUEST/APPLICANT'S STATEMENT:
The request is for Subdivision/Multiple Building Site Plan Review as per Section
31-13 of the Little Rock Code of Ordinances. The applicant is requesting site plan
review to allow the development of an apartment complex on 8.42-acres in the
November 1, 2018
SUBDIVISION
ITEM NO.: 5 Cont.) FILE NO.: S-1538-Q
Gateway Town Center Subdivision. The property is currently zoned C-4, Open
Display District which allows multi -family development per the R-5, District or the
development of not more than 36 units per acre and a minimum land area per
dwelling unit of 1,200 square feet. The applicant is proposing to develop 251 units
of multi -family housing. The proposed density is 29 units per acre with a minimum
land area per dwelling of 1,462 square feet. The development is proposed with
gated entrances. The site plan includes the placement of 403 parking spaces
which exceeds the 376 parking spaces typically required for apartment
development.
The project is proposed in a single phase with construction beginning in early 2019.
The applicant is requesting a variance to allow an increase building height and a
reduced land use buffer along the northern perimeter of the site. The proposal is
to allow three (3) and four (4) story buildings with a maximum building height of
50-feet. The applicant is also requesting the rear land use buffer to be reduced to
nine (9) feet. According to the applicant the justification for the reduced land use
buffer is the owners of the development donated the adjacent 200 plus acres to
the Game and Fish Commission Foundation as an offset to the development in the
Gateway Town Center. The donated property is also in the floodway and will not
be developed.
B. EXISTING CONDITIONS:
The area is developing with a mixture of uses including retail, restaurants, a movie
theater and a hotel. The area to the west is zoned Open Space and is the floodway
of Otter Creek.
C. NEIGHBORHOOD COMMENTS:
All property owners located within 200-feet of the site along with the Otter Creek
Homeowners Association and Southwest Little Rock United for Progress were
notified of the public hearing.
D. ENGINEERING COMMENTS:
PUBLIC WORKS CONDITIONS:
Provide locations of streets and driveway intersections on the east side of
Bass Pro Parkway in the vicinity of the proposed driveway location.
2. Swimming pool discharge cannot be directly connected to the stormwater
drainage system. Discharge should be taken to an open, vegetated area for
water treatment prior to entering the City of Little Rock Municipal Separate
Stormwater Sewer System.
2
November 1, 2018
SUBDIVISION
ITEM NO.: 5 (Cont.) FILE NO.: S-1538-Q
3. Show the proposed location of fencing and gates along with control points.
Turn around must be provided for a SU-30 vehicle attempting to enter
development. A stacking distance of 30-feet from pavement must also be
provided.
4. All driveways shall be concrete aprons per City Ordinance.
5. Repair or replace any curb, gutter, sidewalk and access ramps that are
damaged and not in compliance with ADA recommendations in the public
right-of-way prior to occupancy.
6. A grading permit in accordance with Section 29-186 (c) and (d) will be
required prior to any land clearing or grading activities at the site. Other than
residential subdivisions, site grading and drainage plans must be submitted
and approved prior to the start of construction.
7. Stormwater detention ordinance applies to this property. Maintenance of the
detention pond and all private drainage improvements is the responsibility of
the developer and/or property owners association and detailed in the bill of
assurance.
8. If disturbed area is one (1) or more acres, obtain a NPDES stormwater permit
from the Arkansas Department of Environmental Quality prior to the start of
construction.
9. With the property being adjacent to the floodplain, the minimum Finish Floor
elevation of at least one (1) foot above the base flood elevation is required to
be shown on plat and grading plans.
10. Hauling of fill material on or off site over municipal streets and roads requires
approval prior to a grading permit being issued. Contact Public Works Traffic
Engineering, Travis Herbner, therbner Iittlerock.gov or 501.379.1805 for
more information. T
11. Damage to public and private property due to hauling operations or operation
of construction related equipment from a nearby construction site shall be
repaired by the responsible party prior to issuance of a certificate of
occupancy.
12. The owner and/or manager of each multi -family residence of 100 or more
dwelling units shall provide recycling and encourage participation by the
tenants, renters, or owners of each unit. Contact Melinda Glasgow,
mglasgow -_littlerock.goor 501.371.4646 for more information.
13. Submit a Traffic Impact Study for the proposed project. Study should address
trip generation and trip distribution for the development and also should take
into account existing and projected traffic.
3
November 1, 2018
SUBDIVISION
ITEM NO.: 5 (Cont.) _ FILE NO.: S-1538-Q
E. UTILITIES/FIRE DEPARTMENT/PARKS/COUNTY PLANNING:
Little Rock Water Reclamation Authority: Sewer main extension required with
easements if sewer service is required for this project. Capacity Fee analysis
required. Contact Little Rock Water Reclamation Authority for additional
information
Entergy: Entergy does not object to this proposal. There do not appear to be any
conflicts with existing electrical utilities at this location. There is an existing three
phase, underground power line along the west side of Bass Pro Parkway which
should be located and avoided during the construction of this project. Contact
Entergy in advance to discuss electrical service requirements, or adjustments to
existing facilities (if needed).
Centerpoint Energy: No comment received.
AT & T: No comment received.
Central Arkansas Water: No comment received.
Fire Department:
1. Full Plan Review — Maintain Access
2. Fire Hydrants. Maintain fire apparatus access roads at fire hydrant locations
as per Appendix D of the 2012 Arkansas Fire Prevention Code Vol. 1 Section
D103.1 Access road width with a hydrant. Where a fire hydrant is located on a
fire apparatus access road, the minimum road width shall be 26 feet, exclusive
of shoulders.
3. Grade. Maintain fire apparatus access roads as per Appendix D of the
2012 Arkansas Fire Prevention Code Vol. 1 Section D103.2 Grade. Fire
apparatus access roads shall not exceed 10 percent in grade except as
approved by the fire chief.
4. Loading. Maintain fire apparatus access road design as per Appendix D of the
2012 Arkansas Fire Prevention Code Vol. 1 Section D102.1 Access and
loading. Facilities, buildings or portions of buildings hereafter constructed shall
be accessible to fire department apparatus by way of an approved fire
apparatus access road with an asphalt, concrete or other approved driving
surface capable of supporting the imposed load of fire apparatus weighing at
least 75,000 pounds.
5. Commercial and Industrial Developments — 2 means of access. - Maintain fire
apparatus access roads as per Appendix D of the 2012 Arkansas Fire
Prevention Code Vol. 1.
4
November 1, 2018
SUBDIVISION
ITEM NO.: 5 (Cont.) FILE NO.: S-1
a. Section D104.1 Buildings exceeding three stories or 30 feet in height.
Building or facilities exceeding 30 feet or three stories in height shall
have at least two means of fire apparatus access for each structure.
b. Section D104.2 Building exceeding 62,000 square feet in area.
Buildings or facilities having a gross building area of more than
62,000 square feet shall be provide with two separate and approved
fire apparatus access roads.
c. Exception: Projects having a gross building area of up to 124,000
square feet that have a single approved fire apparatus access road
when all building are equipped throughout with approved automatic
sprinkler systems.
d. D104.3 Remoteness. Where two fire apparatus access roads are
required, they shall be placed a distance apart equal to not less than
one half of the length of the maximum overall diagonal dimension of
the lot or area to be served, measured in a straight line between
accesses.
6. 30' Tall Buildings -Maintain aerial fire apparatus access roads as per Appendix
D of the 2012 Arkansas Fire Prevention Code Vol. 1 Section D105.1 — D105.4.
a. D105.1 Where Required. Where the vertical distance between the
grade plane and the highest roof surface exceed 30', approved aerial
fire apparatus access roads shall be provided. For the purposes of
this section the highest roof surfaces shall be determined by
measurement to the eave of a pitched roof, the intersection of a roof
to the exterior wall, or the top of the parapet walls, whichever is
greater.
b. D105.2 Width. Aerial fire apparatus access roads shall have a
minimum unobstructed with of 26', exclusive of shoulders, in the
immediate vicinity of the building or portion thereof.
c. D105.3 Proximity to building. At least one of the required access
routes meeting this condition shall be located within a minimum of
15 feet and a maximum of 30 feet from the building, and shall be
positioned parallel to one entire side of the building. The side of the
building on which the aerial fire apparatus access road is positioned
shall be approved by the fire code official.
d. D105.4 Obstructions. Overhead utility and power lines shall not be
located over the aerial fire apparatus access road or between the
aerial fire apparatus road and the building. Other obstructions shall
be permitted to be places with the approval of the fire code official.
�1
November 1, 2018
SUBDIVISION
ITEM NO.: 5 (Cont.
FILE NO.: S-
7. Dead Ends. Maintain fire apparatus access roads at dead end locations as per
Appendix D of the 2012 Arkansas Fire Prevention Code Vol. 1 Section D103.4
Dead Ends. Dead-end fire apparatus access roads in excess of 150 feet shall
be provided with width and turnaround provisions in accordance with Table
D103.4. Requirements for Dead-end fire apparatus access roads.
8. Gates. Maintain fire apparatus access road gates as per Appendix D of the
2012 Arkansas Fire Prevention Code Vol. 1 Section D103.5 Fire apparatus
access road gates. Gates securing the fire apparatus access roads shall
comply with all of the following criteria:
1. Minimum gate width shall be 20 feet.
2. Gates shall be of swinging or sliding type.
3. Construction of gates shall be of material that allow manual operation
by one person.
4. Gate components shall be maintained in an operable condition at all
times and replaces or repaired when defective.
5. Electric gates shall be equipped with a means of opening the gate by
fire department personnel for emergency access. Emergency
opening devices shall be approved by the fire code official.
6. Manual opening gates shall not be locked with a padlock or chain
and padlock unless they are capable of being opened by means of
forcible entry tools or when a key box containing the keys to the lock
is installed at the gate location.
7. Locking device specifications shall be submitted for approval \by the
fire code official
8. Electric gate operators, where provided, shall be listed in accordance
with UL 325.
9. Gates, intended for automatic operation shall be designed,
constructed and installed to comply with requirements of ASTM F
2200.
9. Fire Hydrants. Locate Fire Hydrants as per Appendix C of the 2012 Arkansas
Fire Prevention Code. Section C101 — C105, in conjunction with Central
Arkansas Water (Jason Lowder 501.377.1245) and the Little Rock Fire
Marshal's Office (Capt. Tony Rhodes 501.918.3757 or Capt. John Hogue
501.918.3754). Number and Distribution of Fire Hydrants as per Table C105.1.
Parks and Recreation: No comment received.
County Planning: No comment.
L
November 1, 2018
SUBDIVISION
ITEM NO.: 5 Cont. FILE NO.: S-1538-Q
F. BUILDING CODES/LANDSCAPE:
Building Code: Project is subject to full commercial plan review and approval prior
to issuance of a building permit. For information on submittal requirements and the
review process, contact a commercial plans examiner: Curtis Richey at
501.371.4724; crichey@littlerock.gov
Landscape:
1. Site plan must comply with the City's landscape and buffer ordinance
requirements.
2. A perimeter planting strip is required along any side of a vehicular use area that
abuts adjoining property or the right-of-way of any street. This strip shall be at
least nine (9) feet wide. One (1) tree and three (3) shrubs or vines shall be
planted for every thirty (30) linear feet of perimeter planting strip.
3. Eight percent (8%) of the vehicular use area must be designated for green
space; this green space needs to be evenly distributed throughout the parking
area(s). For developments with more than one hundred fifty (150) parking
spaces the minimum size of an interior landscape area shall be three hundred
(300) square feet. Interior islands must be a minimum of seven and one half
(7 1/2) feet in width. Trees shall be included in the interior landscape areas at
the rate of one (1) tree for every twelve (12) parking spaces.
4. Building landscape areas shall be provided between the vehicular use area
used for public parking and the general vicinity of the building. These shall be
provided at the rate equivalent to planter strip three (3) feet wide along the
vehicular use area. One (1) tree and four (4) shrubs shall be planted in the
building landscape areas for each forty (40) linear feet of vehicular use area
abutting the building.
5. An irrigation system shall be required for developments of one (1) acre
or larger.
6. The development of two (2) acres or more requires the landscape plan to be
stamped with the seal of a Registered Landscape Architect.
7. If any of the landscape code requirements cannot be met a variance from the
City Beautiful Commission may be required before a building permit is issued.
8. The City Beautiful Commission recommends preserving as many existing trees
as feasible on this site. Credit toward fulfilling Landscape Ordinance
requirements can be given when preserving trees of six (6) inch caliper or
larger.
7
November 1, 2018
SUBDIVISION
ITEM NO.: 5 _(Cont.)
G. TRANSPORTATION/PLANNING:
FILE NO.: S-1538-Q
Rock Region Metro: This site is across the street from a stop of ours. There is
some connectivity between the sidewalk on Bass Pro Parkway and the proposed
facilities. There does not appear to be a direct sidewalk connection between the
street and the southeastern -most building in the plan (one of the buildings labelled
"Building Type A Total Units 30"). We request that the sidewalk be extended from
this building out to the street.
Planning Division: No comment.
H. SUBDIVISION COMMITTEE COMMENT:
(October 10, 2018)
Mr. Pat McGetrick was present representing the request. Staff presented an
overview of the item stating there were a few outstanding technical issues in need
of addressing related to the proposed site plan. Staff questioned the building
heights proposed for the new construction. Mr. McGetrick stated the building
height had changed. He stated one (1) of the buildings would be a four (4) story
building and the remaining buildings would be three (3) story buildings. Staff
requested the proposed phasing plan for the new construction. Staff requested
the applicant label the proposed gate locations and to indicate the locations of any
gates proposed as one-way exit only gates.
Public Works comments were addressed. Staff stated a Traffic Impact Study for
the proposed project was required. Mr. McGetrick stated there had been traffic
studies in the past and did not feel the use as multi -family would require an
additional study. He stated the use of the property was less intense than originally
designed as a full retail and distribution type development. Staff stated the study
was warranted and the study should address trip generation and trip distribution
for the development and also was to take into account the existing and the
projected traffic flows. Staff stated traffic patterns for a multi -family development
were not the same as traffic for a retail development. Staff stated a grading permit
was required prior to development. Staff stated the City's Stormwater Detention
Ordinance would apply to the future development of the site.
Landscaping comments were addressed. Staff stated the land use buffer adjacent
to the OS, Open Space zoned property was inadequate to meet the typical
minimum ordinance requirements. Mr. McGetrick stated the request included a
variance to allow the reduced buffer. Staff stated the original developer of the area
donated the OS, Open Space zoned property to the Game and Fish Commission.
He stated the property was located in the floodway and would not be developed.
Staff noted the comments from the various other departments and agencies. Staff
suggested the applicant contact the departments or agencies directly with any
November 1, 2018
SUBDIVISION
ITEM NO.: 5 (Cont.) FILE NO.: S-1538-Q
questions or concerns. There were no more issues for discussion. The Committee
then forwarded the item to the full Commission for final action.
ANALYSIS:
The applicant is requesting site plan review approval to allow the development of
a multi -building apartment complex on an 8.42 acre tract located in the Gateway
Town Center Subdivision. The property is zoned C-4 which allows multi -family
development as per the R-5 district or the development of not more than 36 units
per acre with a minimum land area per dwelling of 1,200 square feet. The applicant
is proposing five (5) buildings containing a total of 251 units with a density of 29
units per acre and a minimum land area per dwelling of 1,461 square feet.
The five (5) buildings will be three (3) and four (4) stories with maximum building
heights of 40 and 50 feet. The C-4 zoning district has a building height limit of 35
feet. A variance is requested to allow the increased building height. Staff is
supportive of a height variance. Height variances have been granted for the hotel
and the movie theater which are located near this tract.
Parking for 403 vehicles is proposed. A 251 unit multi -family development requires
375 parking spaces at 1 Y spaces per unit. Access to the development will be
from Bass Pro Parkway. The site will be enclosed by a 6-foot wrought iron fence.
Access to the site will be through two (2) gates located within the site, near the
leasing office. Additional one-way, exit -only gates will be located near the main
entrance and at a secondary point onto a driveway within the shopping center.
A variance is requested to allow the buffer on the rear of the site to be reduced to
the typical landscape ordinance requirement of nine (9) feet. That perimeter of the
site is adjacent to a large OS open space zoned tract which was donated by the
developers of Gateway Town Center to the Game and Fish Foundation. The code
allows for reduction of a buffer when a site is adjacent to a permanent public
open space.
Lighting is to be low-level and directional, shielded downward and into the site
Signage is to comply with that allowed in commercial zones. The property has
enough frontage to have two ground mounted signs on Bass Pro Parkway. The
signs may be placed no closer than one hundred fifty (150) linear feet from
each other.
Public Works Traffic Engineering has reviewed the traffic generation report and
site plan provided by the applicant. They are satisfied with the generation numbers
and are not requiring a full traffic study. Traffic does suggest that the main
driveway be revised to 36 feet in width to allow for three (3) lanes.
hr�
November 1, 2018
SUBDIVISION
ITEM NO.: 5 Cont. FILE NO.: S-1538-Q
To staff's knowledge, there are no outstanding issues.
Ordinance No. 20,839 adopted by the Little Rock Board of Directors on February
11, 2014, modified Section 31-13(f) of the Little Rock Code to limit the term of
approval of a site plan to a maximum of three (3) years from the date of approval.
If an approved multi -phase development, has not been completed within three (3)
years of the date of approval the site plan must be reviewed and reapproved by
the Commission in the same manner as the initial site plan review.
J. STAFF RECOMMENDATION:
Staff recommends approval of the request subject to compliance with the
comments and conditions outlined in paragraphs D, E and F and the staff analysis
as outlined in the staff agenda.
PLANNING COMMISSION ACTION: (NOVEMBER 1, 2018)
The applicant was present. There were no objectors present. Staff presented the item
and a recommendation of approval as outlined in the "staff recommendation" above.
There was no further discussion. The item was placed on the consent agenda and
approved as recommended by staff. The vote was 11 ayes, 0 noes and 0 absent.
10
ta
City of Little Rock
Department of Planning and Development
723 West Markham Street
Little Rock, Arkansas 72201-1334
Phone: (501) 371-4790 Fax: (501) 399-3435 or 371-6863
Date: November 2 2018
Pat McGetrick
P. O. Box 30441
Little Rock AR 72210
Re: 5-1538-Q. Gateway Apartments
Subdivision Site Plan Review
Dear Mr. McGetrick:
Planning
Zoning and
Subdivision
This is to advise you that in connection with your request concerning the above referenced
file number the following action was taken by the Planning Commission at its meeting on
November 1, 2018,
X Approved with conditions.
Recommended approval with conditions.
Recommended approval as submitted.
Denied your request as submitted.
Deferred to the
Other:
If you have any questions, please do not hesitate to contact me at 371-6817.
Respectfully,
Dana Carney
Zoning and Subdivisi
DC/aa
Meeting.