Loading...
HomeMy WebLinkAboutZ-9165-A Map 4/ I.D. NAMEPLATE WITH THE \ FOLLOWING INFORMATION: / 1. EQUIPMENT I.D. ABBREVIATION 2. VOLTAGE, PHASE, WIRES 3. EMERGENCY OR NORMAL SYSTEM \ 4. POWER SOURCE ORIGINATION AND I II OVERCURRENT DEVICE SIZE. ` EXAMPLE \ PANEL E/ 480/277V3, 3 PHASE, 4 WIRE / EMERGENCY SYSTEM FED BY HEDA-3, (100A/3P) COVER PANEL IDENTIFICATION NOTES: 1. SIMILAR FOR DISCONNECTS, MOTOR CONTROLLERS, TRANSFORMERS, LIGHTING CONTROL PANEL, AUTOMATIC TRANSFER SWITCHES, ETC. 2. PROVIDE PANEL IDENTIFICATION FOR ALL NEW PANELS AND FOR ALL EXISTING REWORKED PANELS THAT DO NOT CURRENTLY HAVE IDENTIFICATION TAGS IN PLACE. 1 PANEL IDENTIFICATION DETAIL O 24" MIN. 3' SOD WHERE GRASSY AREA CONCRETE/ASPHALT IN PAVED AREA ��. I �� I�O��I�s•4�i'xOM ��pj��I�I��. I i�aVii�i�Ir% WA �O �O�•�I �Olpj�iV Q��.��p �s_I�.i�a_���i�O�i►i�i;I�. �a'I�jQ'Ipj �i•IOI�OIOI �OI�j�0I0I I�s•I�.��OIa•I i�`Iei�QI�. r��.�.. �'�OI•�` � COMPACTED BACKFILL 6 P 6' 3 " FiTa 6' 6' TRENCH MARKER TAPE (TYPICAL) —SCH. 80 PVC CONDUITS AS REQUIRED TRENCH DETAIL BOXES USED TO ROUTE FIRE ALARM & BUILDING MANAGEMENT SYSTEM CONTROLS SHALL BE PROVIDED WITH COVERS THAT INDICATE SERVICE. I I 3,5-16 UNIC HEX HEAD BOLT ® W/ TWO WASHERS COVER �� O e •' 112" X 4" PULL SLOT BOXES INSTALLED INSTALLED IN AREAS .5 SKID RESISTANT SURFACE THAT MAY RECEIVE VEHICULAR TRAFFIC SHALL BE PROVIDED WITH TRAFFIC RATED COVERS. \EXTENSION BOXES SHALL HAVE GASKETED HEAVY DUTY BOLT DOWN MID COVER, OPEN BOTTOM. PROVIDE A MINIMUM 12' AGGREGATE BASE BELOW ALL BOXES. LENGTH PULL BOXES SHALL BE PROVIDED ALONG THE LENGTH OF ALL BELOW GRADE CIRCUITS. SPACING SHALL BE SUCH THAT PULLING TENSION REQUIRED IS WITHIN MANUFACTURER'S SPEGFIED LIMITS. MAXIMUM SPACING BETWEEN PULL PULL POINTS SHALL BE 150'. MINIMUM BOX BOX SIZE SHALL BE 24"X24'. — 2X 4" MO HOLES 4 1 IN - GRADE PULL BOX DETAIL kl� ELECTRICAL GENERAL NOTES A. CIRCUITS OF DIFFERENT PHASES MAY SHARE THE SAME EQUIPMENT GROUND. THE EQUIPMENT GROUNDING CONDUCTOR SIZE SHALL NOT BE LESS THAN #12 AWG OR AS INDICATED ON THE DRAWINGS. B. ALL CONDUCTORS SHALL BE COPPER THHNITHWN. ALL CONDUCTORS #10 AWG AND SMALLER SHALL BE SOLID COPPER. ALL CONDUCTORS #8 AWG AND LARGER SHALL BE STRANDED COPPER USING BOLTED LUGS AT TERMINALS, C. ALL POWER CONDUCTORS SHALL BE ROUTED IN CONDUIT. D. UNLESS NOTED OTHERWISE, THE MINIMUM CONDUIT SIZE SHALL BE 3/4". MINIMUM UNDERGROUND CONDUIT SHALL BE 1". ALL CONDUITS SHALL BE CONCEALED WHERE POSSIBLE. EMT CONDUIT WITH COMPRESSION FITTINGS SHALL BE USED INDOORS. GRS CONDUIT SHALL BE USED ABOVE GRADE IN OUTDOOR LOCATIONS. SCH. 80 PVC CONDUIT SHALL BE USED BELOW GRADE. E. MINIMUM WIRE SIZE SHALL BE #12 AWG UNLESS OTHERWISE NOTED. MINIMUM UNDERGROUND WIRING SHALL BE #10 AWG. F. ALL WORK SHALL COMPLY WITH THE LATEST EDITION OF THE NATIONAL ELECTRIC CODE. G. ALL ELECTRICAL EQUIPMENT (CONDUIT, BOXES, SUPPORTS, ETC.) INSTALLED IN EXPOSED CEILING AREAS SHALL BE PAINTED AS DIRECTED BY THE ARCHITECT. H. COMPRESSION FITTINGS SHALL BE USED ON ALL EMT CONDUIT. SET SCREW FITTINGS ARE NOT ALLOWED. I. ALL CIRCUITS SHALL BE LABELED IN PANEL SCHEDULES. PANEL SCHEDULES SHALL BE TYPED. HAND WRITTEN PANEL SCHEDULES ARE NOT ACCEPTABLE. J. FLEXIBLE CONNECTIONS AT EQUIPMENT AND TRANSFORMERS SHALL BE 6'-0" MAX. K. ALL DEVICES SHALL BERATED 20A MINIMUM. 15A DEVICES ARE NOT ACCEPTABLE, L. CONNECT DEVICES BY WRAPPING WIRE AROUND SCREW TERMINAL IN A CLOCKWISE DIRECTION AND TIGHTEN SCREW, BACK -CONNECTED SPRING DEVICES ARE NOT ALLOWED. M. PULL ALL THE CONDUCTORS THROUGH RACEWAY AT THE SAME TIME. N. PROVIDE PULL STRING AND PROTECTIVE BUSHING IN ALL SPARE CONDUITS. 0. PROVIDE ALL LABOR AND MATERIALS REQUIRED TO PERFORM AND DOCUMENT AN ARC FAULT AND SHORT CIRCUIT ANALYSIS FOR ALL EQUIPMENT AND ELECTRICAL PANELS. ANALYSIS SHALL BE PERFORMED BY THE ELECTRICAL GEAR MANUFACTURER AND SHALL INCLUDE THE UTILITY SERVICE TRANSFORMER, ALL ELECTRICAL PANELBOARDS, AND MOTORS. SHORT CIRCUIT STUDY SHALL BE PERFORMED WITH THE AID OF AN APPROPRIATE COMPUTER PROGRAM AND SHALL BE IN ACCORDANCE WITH THE LATEST APPLICABLE IEEE AND ANSI STANDARDS. HAND DRAWN COORDINATION CURVES WILL NOT BE ACCEPTED. FAULTS FOR BOTH UTILITY SOURCE AND EMERGENCY POWER SHALL BE ANALYZED. ARC FLASH HAZARD ANALYSIS SHALL BE PERFORMED PER NFPA 70E. AT A MINIMUM, THE DELIVERABLES SHALL BE AS FOLLOWS: - EXECUTIVE SUMMARY EXPLAINING THE RESULTS AND ANY CONCLUSIONS OR RECOMMENDATIONS. ARC FLASH INCIDENT ENERGY AND RESULTING PPE LEVELS SINGLE -LINE SYSTEM DIAGRAM INCLUDING AMP RATINGS, AIC, FRAME SIZE, TRIP SETTINGS GROUND FAULT SETTINGS, AND CABLE INFORMATION (TYPE, SIZE, LENGTH) SHORT CIRCUIT ANALYSIS TIME -CURRENT COORDINATION ANALYSIS INCLUDING RECOMMENDED SETTINGS. ANSI COMPLIANT EQUIPMENT WARNING LABELS INDICATING PPE LEVELS, INCIDENT ENERGY, FLASH BOUNDARY, AND AVAILABLE FAULT CURRENT. 1.518" SLOTTED UNISTRUT PAINTED 4"X4" STEEL POST — PAINTED LINE POWER CIRCUITS 1 LIGHTING CONTACTORS WEATHERPROOF — RECEPTACLE PANELFEEDEF PANEL 'SITE' WIDTH AS REQUIRED w A A A A A SPORTS LIGHITN CONTROLAND MONITORING PANEL 18" ROUND X 36" DEEP 3000 PSI CONCRETE SUPPORTS W/ #3 REBAR A 12" O.C. EACH WAY - DIGITAL CELULAR ANTENNA CONTROL POWER CIRCUIT (20AI1P) OFF -ON -AUTO KEYED SWITCHES LOAD POWER CIRCUITS TO SITE LIGHTING POLES SITE LIGHTING PANEL DETAIL ELECTRICAL ABBREVIATIONS ABBREVIATION DESCRIPTION AC ABOVE COUNTER or ALTERNATING CURRENT AFF ABOVE FINISH FLOOR AFCI ARC FAULT CIRCUIT INTERRUPTING AFG ABOVE FINISH GRADE AHU AIR HANDLING UNIT AL ALUMINUM ATS AUTOMATIC TRANSFER SWITCH AN REFERS TOAUDIONIDEO AWG AMERICAN WIRE GAUGE C CONDUIT CCTV CLOSED CIRCUIT TELEVISION CKTorCIR CIRCUIT CU COPPER db DECIBEL DC DIRECTCURRENT DIA DIAMETER EF EXHAUST FAN EMT ELECTRICAL METALLIC TUBING EP EXPLOSION PROOF EPO EMERGENCY POWER OFF ERV ENERGY RECOVERY VENTILATOR FA FIRE ALARM FLA FULL LOAD AMPS GFCI GROUND FAULT CIRCUIT INTERRUPTING GRID GROUND GRS GALVANIZED RIGID STEEL IMC INTERMEDIATE METAL CONDUIT KCMIL THOUSAND CIRCULAR MILS KVA KILOVOLTAMPS LTG LIGHTING LRA LOCKED ROTOR AMPS MC METAL CLAD CABLE MCA MINIMUM CIRCUIT AMPACITY MCB MAIN CIRCUIT BREAKER MTD MOUNTED MTS MANUAL TRANSFER SWITCH NC NORMALLY CLOSED NEC NATIONAL ELECTRICAL CODE NEMA NATIONAL ELECTRICAL MANUFACTURER'S ASSOCIATION NF NON -FUSED NFPA NATIONAL FIRE PROTECTION ASSOCIATION NO NORMALLY OPEN NS NON -SWITCHED P POLE PE PHOTOELECTRIC CELL PNL PANELBOARD PWR POWER QTY QUANTITY RAP REMOTE ANNUNCIATOR PANEL REQ REQUIRED RMS ROOM MEAN SQUARED RTU ROOFTOP UNIT SP SURGE PROTECTION ST SHUNT TRIP SPD SURGE PROTECTIVE DEVICE SW SWITCH TC TIME CLOCK TEL TELEPHONE TYR TYPICAL UC DENOTES UNDER COUNTER - VERIFY LOCATION UL UNDERWRITERS LABORATORY LON UNLESS OTHERWISE NOTED V VOLTAGE VA VOLT AMPS VFD VARIABLE FREQUENCY DRIVE W WATT OR WIRE WH WATER HEATER WP WEATHERPROOF XFMR TRANSFORMER SYMBOLS SCHEDULE SYMBOL DESCRIPTION FLUORESCENT LIGHT FIXTURE - CEILING MOUNTED FLUORESCENT LIGHT FIXTURE CONNECTED TO EMERGENCY BALLAST (OR CONNECTED TO EMERGENCY POWER CIRCUIT) �-�-� FLUORESCENT STRIP LIGHT - CEILING MOUNTED OR CHAIN HUNG FLUORESCENT STRIP LIGHT - EQUIPPED WITH SELF-CONTAINED EMERGENCY BATTERY PACK (OR W/ EMERGENCY POWER CIRCUIT) FLUORESCENT LIGHT FIXTURE - WALL MOUNTED 0 DOWNLIGHT FIXTURE - CEILING MOUNTED G DOWNLIGHT FIXTURE - EQUIPPED WITH SELF-CONTAINED EMERGENCY BATTERY PACK (OR W/ EMERGENCY POWER CIRCUIT) g LIGHT FIXTURE - WALL MOUNTED .s EMERGENCY LIGHT FIXTURE rStf ® Y EXIT LIGHTS - WALL MT. & CEILING MT. SHOWN -SHADING INDICATES FACE(S), DIRECTIONAL ARROWS SHALL BE AS SHOWN ON PLANS S TOGGLE SWITCH MOUNTED AT48"A.F.F. 3 - THREE-WAY SWITCH 4 - FOUR-WAY SWITCH D - DIMMER M - MOTOR RATED K - KEY OPERATED ab - MULTI LEVEL SWITCHING LV - LOW VOLTAGE SWITCH UC - UNDER COUNTER DW - DISHWASHER TV- TELEVISION OUTLET REF -REFRIGERATOR DUPLEX RECEPTACLE MOUNTED AT 18" AF.F. UNLESS INDICATED OTHERWISE GFI - GROUND FAULT CIRCUIT INTERRUPTING WP- WEATHERPROOF'IN-USE' TYPE COVER AC -ABOVE COUNTER, VERIFY EXACT MOUNTING HEIGHT WITH ARCH EWC- WATER COOLER OUTLET CONCEALED BEHIND UNIT, POWER FROM GFCI BRKR > QUADRUPLEX RECEPTACLE DUPLEX RECEPTACLE FLUSH MOUNTED AT CEILING QUADRUPLEX RECEPTACLE, SUSPENDED FROM CEILING ® DUPLEX RECEPTACLE IN FLUSH MOUNTED FLOOR BOX ® QUADRUPLEX RECEPTACLE IN FLUSH MOUNTED FLOOR BOX SPECIAL PURPOSE OUTLET- NEMA CONFIGURATION (VOLTAGE, AMPACITY) UJ AS NOTED ON DRAWINGS l MUSHROOM HEAD PUSHBUTTON © JUNCTION BOX �— SURFACE MOUNTED PANELBOARD —� FLUSH MOUNTED PANELBOARD TELEPHONE TERMINAL BOARD - DISCONNECT SWITCH COMBINATION MOTOR STARTER/ DISCONNECT SWITCH MOTOR STARTER TRANSFORMER BRANCH CIRCUIT IN CONDUIT - SWITCHED HOT THROUGH LIGHTING CONTACTOR, SWITCH LEG, PHASE LEG, NEUTRAL, EQUIPMENT GROUND, AND ISOLATED GROUND BRANCH CIRCUIT HOMERUN - PANEL AND CIRCUIT NUMBER INDICATED . TELEPHONE OUTLET AT I8'A.F.F. UNLESS INDICATED OTHERWISE PROVIDE J-BOX WITH 3/4" CONDUIT STUB UP FOR OWNER PROVIDED CABLE ® TELEPHONE OUTLET- FLUSH MOUNTED IN FLOOR SLAB OR CEILING 0 DATA OUTLET AT 18' A.F.F. UNLESS INDICATED OTHERWISE PROVIDE J-BOX WITH 3/4" CONDUIT STUB UP FOR OWNER PROVIDED CABLE ® DATA OUTLET- FLUSH MOUNTED IN FLOOR SLAB OR CEILING Q COMBINATION DATAGELEPHONE OUTLET AT 18" A.F.F. UNLESS INDICATED OTHERWISE PROVIDE J-BOX WITH 3/4" CONDUIT STUB UP FOR OWNER PROVIDED CABLE TELEVISION OUTLET, REFER TO PLANS FOR INFORMATION PROVIDE J-BOX WITH 3/4" CONDUIT STUB UP FOR OWNER PROVIDED CABLE p �� REG�S PEFTIT & PER �Q CONSULTING Z ENGINEERS, INC. J �mm Ov CD O z = v♦ �W�Q _I 0 0 z a I W�=a V Y 0 J W 01 m J o0 aJ ° Z Z a.- J JOB NO. S-IN DATE 04/09A8 SF EEr NO. E0.1 ® 2018 PETTIT & PETTIT C0161Lm BwEm% NG PMtT & PETTFIT CUa`d5JL:3R1i��dU`IN EkSl7�'t4 i3TTLE 90{:k5, 3';Rd:,A