Loading...
HomeMy WebLinkAboutZ-9108 Staff AnalysisITEM NO.: 15. Z-9108 NAME: Paul Short -form PID LOCATION: located at 1401 East 9th Street Planning Staff Comments: 1. Provide notification of the property owners located within 200-feet of the development including the certified abstract list, notice form with affidavit executed and proof of mailing. The notice must be mailed no later than February 10, 2016. The Office of Planning and Development must receive the proof of notice no later than February 19, 2016. 2. Provide the quantitative data including the parcel size, types and number of permitted uses and floor areas according for each of the uses proposed. 3. Provide details of any proposed fencing, walls the purpose of these elements. Provide the construction materials, total height and location. 4. Provide the location, dimensions, nature of all existing and proposed easements, utility and streets, and public improvements, drainage, sewer, water. 5. Indicate the location of structures and structure dimensions, dimensioned distances between buildings and distances from structure to property line. 6. Provide a development schedule indicating the approximately date when construction of the planned unit development or stages of the planned unit development can be expected to begin and be completed. 7. Will there be a dumpster located on the site? If so provide the location of the proposed dumpster facility. Will the hours of service be limited for the dumpster? If so note the hours of dumpster service. 8. Provide the total square footage of the building proposed for the events center and the total square footage proposed for other uses. 9. Parking for an events center is based on one (1) parking space per 100 square feet of floor area. The site plan indicates the only parking is located along the western side of the building and is currently backing into the right of way. How will parking be addressed? 10. Separation requirements for event centers shall be determined by the planning commission so as not to adversely impact the neighborhood. Event center review shall consider the following additional requirement: a. An event center shall not be located within seven hundred fifty (750) feet of the following: 1. A church or other religious facility. 2. A sexually -oriented business as defined by Chapter 17 of the Code of Ordinances. 3. A public or private elementary, secondary or postsecondary school, a day care center or any facility that operates programs for children or youth. ITEM NO.: 15, Z-9108 4. Any single-family or multifamily residential use, except a hotel or motel, or a residential use that is within a unified development that contains both the event center and the residential use. b. For the purposes of subsection (a), measurement shall be made in a straight line, without regard to intervening structures or objects, from the nearest portion of a building or structure proposed for occupancy as an event center to the nearest property line of any use listed in subsection (a). Variance/Waivers: None requested. Public Works Conditions: 1. Due to the proposed use of the property, the Master Street Plan specifies that Shall Street for the frontage of this property must meet commercial street standards. Dedicate right-of-way to 30 feet from centerline. Do not include the building in the dedication. 2. A 20 foot radial dedication of right-of-way is required at the intersection of Shall Street and East 9th Street. 3. Nearly the entire west frontage other than adjacent to the building is a curb cut for head in parking. Vehicles backing into Shall Street right-of-way is not safe. Show the proposed driveway location and parking plan so vehicles no longer back into the right-of-way. 4. Insufficient sight distance exists on Shall Street at the Shall Street/East 9th Street intersection due to existing building structures. 5. Repair or replace any curb and gutter or sidewalk that is damaged in the public right- of-way prior to occupancy. 6. Obtain a franchise agreement from Public Works Bennie Nicolo, bnicolo@littlerock.org or 501.371.4818) for the private improvements located in the right-of-way. Utilities and Fire Department/County Planning: Wastewater: Sewer available to this site. Contact Little Rock Wastewater if additional information is required. Entergy: Entergy does not object to this proposal. Electrical service can be provided to the existing building from the north or west sides of the property where existing service lines are already provided. There do not appear to be any conflicts with existing Entergy facilities. Contact Entergy in advance if electrical service needs change as a result of the change in allowable use. Centerpoint Energy: No comment received. AT & T: No comment received. Central Arkansas Water: ITEM NO.: 15. Z-9108 All Central Arkansas Water requirements in effect at the time of request for water service must be met. 2. Please submit plans for water facilities and/or fire protection system to Central Arkansas Water for review. Plan revisions may be required after additional review. Contact Central Arkansas Water regarding procedures for installation of water facilities and/or fire service. Approval of plans by the Arkansas Department of Health Engineering Division and the Little Rock Fire Department is required. 3. A Capital Investment Charge based on the size of meter connection(s) will apply to this project in addition to normal charges. This fee will apply to all connections including metered connections off the private fire system. 4. If there are facilities that need to be adjusted and/or relocated, contact Central Arkansas Water. That work would be done at the expense of the developer. 5. Due to the nature of this facility, installation of an approved reduced pressure zone backflow preventer assembly (RPZA) is required on the domestic water service. This assembly must be installed prior to the first point of use. Central Arkansas Water requires that upon installation of the RPZA, successful tests of the assembly must be completed by a Certified Assembly Tester licensed by the State of Arkansas and approved by Central Arkansas Water. The test results must be sent to Central Arkansas Water's Cross Connection Section within ten days of installation and annually thereafter. Contact the Cross Connection Section at 501.377.1226 if you would like to discuss backflow prevention requirements for this project. 6. The facilities on -site will be private. When meters are planned off private lines, private facilities shall be installed to Central Arkansas Water's materials and construction specifications and installation will be inspected by an engineer, licensed to practice in the State of Arkansas. Execution of a Customer Owned Line Agreement is required. 7. Fire sprinkler systems which do not contain additives such as antifreeze shall be isolated with a double detector check valve assembly. If additives area used, a reduced pressure zone back flow preventer shall be required. Fire Department: Full plan review must meet current code. Parks and Recreation: No comment received. County Planning: No comment. Rock Region Metro: Locations served by Route 12 East 9th Street and by future flex service. Maintain pedestrian access as shown in plan for potential employees. Building Code: Project is subject to full commercial plan review and approval prior to issuance of a building permit. For information on submittal requirements and the review process, contact a commercial plans examiner: Curtis Richey at 501.371.4724; crichey@littlerock.org or Mark Alderfer at 501.371.4875; malderfer(a_littlerock. org. ITEM NO.: 15, Z-9108 Project may require separation of building occupancies and/or ambulatory care requirements to be met. As an Assembly Occupancy fire sprinkler installations may be required. Planning Division: This request is located in the 1-30 Planning District. The Land Use Plan shows Mixed Use Urban (MXU). The Mixed Use -Urban category provides for a mix of residential, office and commercial uses not only in the same block but also within the same structure. This category is intended for older "urban" areas to allow dissimilar uses to exist, which support each other to create a vital area. Development should reinforce the urban fabric creating a 24-hour activity area. Using the Planned Zoning District or the Urban Use District, high and moderate density developments that result in a vital (dense) pedestrian oriented area are appropriate. The applicant has applied for a rezoning from 1-2 (Light Industrial District) to PID (Planned Industrial District) to add an event center in the existing building as an allowable uses. Master Street Plan: North side of the property is East 9th Street and it is a Collector, west side of the property is Shall Avenue and it is a Local Street on the Master Street Plan. The primary function of a Collector Street is to provide a connection from Local Streets to Arterials. The primary function of a Local Street is to provide access to adjacent properties. Local Streets that are abutted by non-residential zoning/use or more intensive zoning than duplexes are considered as "Commercial Streets". A Collector design standard is used for Commercial Streets. These streets may require dedication of right-of-way and may require street improvements for entrances and exits to the site. Bicycle Plan: There are no bike routes shown in the immediate vicinity. Landscape: 1. Site plan must comply with the City's landscape and buffer ordinance requirements. 2. If building rehabilitation exceeds fifty percent (50%) of the replacement cost then the landscaping and buffer must also come into compliancy accordingly. 3. The City Beautiful Commission recommends preserving as many existing trees as feasible on sites. Credit toward fulfilling Landscape Ordinance requirements can be given when preserving trees of six (6) inch caliper or larger. Revised plat/plan: Submit four (4) copies of a revised preliminary plat/plan (to include the additional information as noted above) to staff on Wednesday, February 10, 2016. 511