HomeMy WebLinkAboutZ-8873 Staff AnalysisITEM NO.: 15.
Z-8873
NAME: Capitol Lofts LLC, the Hall Davidson Building, 201 — 205 Capitol Avenue Short -
form PCD
LOCATION: located at 201 — 205 Capitol Avenue
Planning Staff Comments:
1. Provide notification of the property owners located within 200-feet of the site,
including the certified abstract list, notice form with affidavit executed and proof of
mailing. The notice must be mailed no later than June 26, 2013. The Office of
Planning and Development must receive the proof of notice no later than July 5,
2013.
2. Lighting is to be placed so as to reflect away from adjacent residential structures.
Fixtures adjacent to roadways shall be of a design that minimizes glare to the
motoring public.
3. All ground mounted mechanical systems and trash receptacles and pickup shall be
oriented away from a primary street side of the property and screened from the
public right of way. Ground mounted mechanical systems and trash receptacles
shall be placed adjacent to alleys if alleys are available.
4. Street trees a minimum of three inch caliper shall be required. The trees shall be
located a minimum of 2-feet off the back of curb and 30-feet on center and no closer
than 30-feet to a street intersection with a water source provided. Tree canopy shall
be maintained at least 8-feet above the sidewalk.
5. The ground level (street fronting) floor of nonresidential structures shall have a
minimum surface area of 60 percent transparent or window display.
6. Objects shall not project from the building fagade over the public right of way except
for awnings, balconies and signs as specified in Section 36-553. Awnings shall not
project more than 5-feet from the building fagade and have a minimum clearance of
8-feet above the sidewalk. Balconies over the public right of way shall have a
minimum clearance of 9-feet above the sidewalk. The maximum projection shall be
4-feet.
7. Building signage is allowed as permitted in institutional and office zones. On the
street level, the maximum area of signage may be doubled if at least 50 percent of
the street level office and retail space has direct access to the street. Ground signs
are discouraged but may be permitted as a variance.
8. Will the units be maintained or will the units/suites be sold as condo units?
9. Will there be space available for a food store under 5,000 square feet which may sell
beer or wine?
10. Will there be a restaurant user which will request outdoor dining within the right of
way? If so indicate on the site plan the area proposed for outdoor dining and the
anticipated number of seats.
11.It appears the uses proposed are the uses allowed in the UU, Urban Use Zoning
District. The request is to allow an increase in the overall density of the residential
from 72 units per acre to 143 units per acre.
12. Provide details of the garden court.
Item # 15.
Variance/Waivers:
None requested.
ublic Works Conditions:
1. Repair or replace any curb and gutter or sidewalk that is damaged in the public right-
of-way prior to occupancy.
Utilities and Fire Department/County Planning:
Wastewater: Sewer available to this project. Capacity Contribution Fee Calculation
required. Contact Little Rock Wastewater for additional information.
Entergy: No comment received.
Center -Point Energy: No comment received.
AT & T: No comment received.
Central Arkansas Water:
1. No objections. All Central Arkansas Water requirements in effect at the time of
request for water service must be met.
2. Contact Central Arkansas Water regarding the size and location of the water meter.
3. If there are facilities that need to be adjusted and/or relocated, contact Central
Arkansas Water. That work would be done at the expense of the developer.
4. Contact Central Arkansas Water if additional fire protection or metered water service
is required.
5. The Little Rock Fire Department needs to evaluate this site to determine whether
additional public or private fire hydrant(s) will be required. If additional fire hydrant(s)
are required, they will be installed at the Developer's expense.
6. Due to the nature of this facility, installation of an approved reduced pressure zone
backflow preventer assembly (RPZA) is required on the domestic water service.
This assembly must be installed prior to the first point of use. Central Arkansas
Water requires that upon installation of the RPZA, successful tests of the assembly
must be completed by a Certified Assembly Tester licensed by the State of Arkansas
and approved by Central Arkansas Water. The test results must be sent to Central
Arkansas Water's Cross Connection Section within ten days of installation and
annually thereafter. Contact the Cross Connection Section at 377-1226 if you would
like to discuss backflow prevention requirements for this project.
Fire Department: Place fire hydrant(s) per code. Maintain access. Contact the Little
Rock Fire Department for additional information.
County Planning: No comment.
CATA: Approved as submitted.
Parks and Recreation: No comment received.
Item # 15.
Planning Division This request is located in the Downtown Planning District. The Land
Use Plan shows Mixed Use Urban (MXU) for this property. The Mixed Use Urban
category provides for a mix of residential, office and commercial uses not only in the
same block but also within the same structure. This category is intended for older
"urban" areas to allow dissimilar uses to exist, which support each other to create a vital
area. Development should reinforce the urban fabric creating a 24-hour activity area.
Using the Planned Zoning District or the Urban Use District, high and moderate density
developments that result in a vital (dense) pedestrian oriented area are appropriate. The
applicant has applied for a rezoning from UU (Urban Use District) to PCD (Planned
Commercial District) to a higher density of residential than normally within this mixed -
use development.
Master Street Plan: Capitol Avenue is a Collector on the Master Street Plan. The
primary function of a Collector Street is to provide a connection from Local Streets to
Arterials. This street may require dedication of right-of-way and may require street
improvements for entrances and exits to the site.
Bicycle Plan: There are no bike routes shown in the immediate vicinity.
Landscape:
1. Site plan must comply with the City's landscape and buffer ordinance requirements.
2. Per the UU district standards street trees must be installed with this application,
which will include automatic irrigation and tree grates. If there are currently trees
within this area they must be in good condition or replaced as a part of this
application. If the street trees are being proposed to be removed with this
application they need to be replaced per the Tree Credit Chart in Chapter 15 of the
Landscape Ordinance, City of Little Rock.
3. The street trees along Capitol Avenue will need to be the designated street type for
the Capitol Corridor.
4. Any additional parking must be landscaped in accordance to Chapter 15 of the
Landscape Ordinance, City of Little Rock. It will require additional review and
approval from the Planning Department.
Revised plat/plan� Submit four (4) copies of a revised preliminary plat/plan (to include
the additional information as noted above) to staff on Wednesday, June 26, 2013.
Item # 15.
FILE NO.: Z-8873
NAME: Capitol Lofts LLC, the Hall Davidson Building, 201 — 205 Capitol Avenue
Short -form PCD
LOCATION: Located at 201 — 205 Capitol Avenue
DEVELOPER:
Scott Reed & Capitol Lofts LLC
1001 SW 5tn Avenue, Suite 1100
Portland, OR 97204
FNC,INFFR-
Paul D. Fleming, PE SECB
18 Essay Drive
Little Rock, AR 72223-9142
AREA: 0.3859 acres
CURRENT ZONING
ALLOWED USES
NUMBER OF LOTS: 1 zoning lot
UU, Urban Use District
Residential, Office, Commercial
ROPOSED ZONING: PCD
FT. NEW STREET: 0 LF
PROPOSED USE: Allow multi -family density at a rate greater than the UU Zoning
District
VARIANCES/WAIVERS REQUESTED: None requested.
A. PROPOSAL/REQUEST/APPLICANT'S STATEMENT:
Capitol Lofts LLC is purchasing the Hall and Davidson Building located between
201 — 215 Capitol Avenue at the corner of Louisiana Street from Robert G.
Davidson. Capitol Lofts LLC after closing will remediate the environmental
issues within both the Hall and Davidson Properties and rehab the upper floors of
the 65,000 square foot buildings to allow for 56 multi -family units.
Presently the property is zoned UU, Urban Use District. The UU zoning allows
for 72 apartment units. The site contains 0.3859 acres in the Original City of
Little Rock allowing for a total of 29 apartments. The applicant is proposing a
FILE NO.: Z-8873 (Cont.
rezoning to allow the density to be increased. The UU, Urban Use Zoning
District uses will remain as allowable uses for the property.
The applicant will provide parking via a lease agreement for 60 parking spaces
with the property owner located directly behind the building for the tenants use.
The ground floor will contain commercial and office uses. Floors 2 — 5 will be
developed into 56 apartment units.
B. EXISTING CONDITIONS:
The site is located downtown in the Urban Core of the City. The building is a five
(5) story building with multiple tenant lease spaces on the lower level. This area
of Capitol Avenue is tree lined. There are several multi -story office buildings
located in this block.
C. NEIGHBORHOOD COMMENTS:
As of this writing, staff has not received any comment from area residents. All
property owners located within 200-feet of the site along with the Downtown
Neighborhood Association, the MacArthur Park Neighborhood Association and
the River Market Neighborhood Association were notified of the public hearing.
D. ENGINEERING COMMENTS:
PUBLIC WORKS CONDITIONS:
1. Repair or replace any curb and gutter or sidewalk that is damaged in the
public right-of-way prior to occupancy.
E. UTILITIES AND FIRE DEPARTMENT/COUNTY PLANNING:
Wastewater: Sewer available to this project. Capacity Contribution Fee
Calculation required. Contact Little Rock Wastewater for additional information.
Entergy: No comment received.
Center -Point Energy: No comment received.
AT & T: No comment received.
Central Arkansas Water:
1. No objections. All Central Arkansas Water requirements in effect at the time
of request for water service must be met.
2. Contact Central Arkansas Water regarding the size and location of the water
meter.
2
FILE NO.: Z-8873 (Cont.
3. If there are facilities that need to be adjusted and/or relocated, contact Central
Arkansas Water. That work would be done at the expense of the developer.
4. Contact Central Arkansas Water if additional fire protection or metered water
service is required.
5. The Little Rock Fire Department needs to evaluate this site to determine
whether additional public or private fire hydrant(s) will be required. If
additional fire hydrant(s) are required, they will be installed at the Developer's
expense.
6. Due to the nature of this facility, installation of an approved reduced pressure
zone backflow preventer assembly (RPZA) is required on the domestic water
service. This assembly must be installed prior to the first point of use.
Central Arkansas Water requires that upon installation of the RPZA,
successful tests of the assembly must be completed by a Certified Assembly
Tester licensed by the State of Arkansas and approved by Central Arkansas
Water. The test results must be sent to Central Arkansas Water's Cross
Connection Section within ten days of installation and annually thereafter.
Contact the Cross Connection Section at 377-1226 if you would like to
discuss backflow prevention requirements for this project.
Fire Department: Place fire hydrant(s) per code. Maintain access. Contact the
Little Rock Fire Department for additional information.
County Planning: No comment.
CATA: Approved as submitted.
Parks and Recreation: No comment received.
F. ISSUES/TECHNICAL/DESIGN:
Planning Division: This request is located in the Downtown Planning District.
The Land Use Plan shows Mixed Use Urban (MXU) for this property. The Mixed
Use Urban category provides for a mix of residential, office and commercial uses
not only in the same block but also within the same structure. This category is
intended for older "urban" areas to allow dissimilar uses to exist, which support
each other to create a vital area. Development should reinforce the urban fabric
creating a 24-hour activity area. Using the Planned Zoning District or the Urban
Use District, high and moderate density developments that result in a vital
(dense) pedestrian oriented area are appropriate. The applicant has applied for a
rezoning from UU (Urban Use District) to PCD (Planned Commercial District) to a
higher density of residential than normally within this mixed -use development.
Master Street Plan: Capitol Avenue is a Collector on the Master Street Plan.
The primary function of a Collector Street is to provide a connection from Local
Streets to Arterials. This street may require dedication of right-of-way and may
require street improvements for entrances and exits to the site.
3
FILE NO.: Z-8873 Cont.
Bicycle Plan: There are no bike routes shown in the immediate vicinity.
Landscape:
1. Site plan must comply with the City's landscape and buffer ordinance
requirements.
2. Per the UU district standards street trees must be installed with this
application, which will include automatic irrigation and tree grates. If there are
currently trees within this area they must be in good condition or replaced as
a part of this application. If the street trees are being proposed to be removed
with this application they need to be replaced per the Tree Credit Chart in
Chapter 15 of the Landscape Ordinance, City of Little Rock.
3. The street trees along Capitol Avenue will need to be the designated street
type for the Capitol Corridor.
4. Any additional parking must be landscaped in accordance to Chapter 15 of
the Landscape Ordinance, City of Little Rock. It will require additional review
and approval from the Planning Department.
G. SUBDIVISION COMMITTEE COMMENT: (June 20, 2013)
The applicants were present. Staff presented an overview of the proposed
development questioning several aspects of the development. Staff questioned if
there would be a food store less than 5,000 square feet selling beer or wine.
Staff questioned if the units would be owner occupied or rental units. The
applicant stated the units would not be sold. Staff questioned if the development
would maintain the UU, Urban Use District uses as allowable uses for the
property. The applicant stated the UU, Urban Use Zoning District uses would be
maintained.
Staff noted comments from the other reporting departments and agencies
suggesting the applicant contact them individually for additional clarification.
There was no further discussion of the item. The Committee then forwarded the
item to the full Commission for final action.
H. ANALYSIS:
The applicant submitted revised comments to staff addressing concerns raised at
the June 20, 2013, Subdivision Committee meeting. The applicant has indicated
there will not be a food store less than 5,000 square feet selling beer or wine.
The applicant has also indicated the units will be maintained as rental and will not
be sold. The applicant is requesting to maintain the UU, Urban Use Zoning
District uses as allowable uses for the property. The applicant has indicated any
potential restaurant user will not have outdoor dining within the public right of
way.
4
FILE NO.: Z-8873 (Cont.
The applicant is seeking approval of a PCD zoning for the Hall and Davidson
Building located between 201 — 215 Capitol Avenue. The developer intends to
rehab the upper floors of the 65,000 square foot buildings to allow for
56 multi -family units. The street level will be marketed as retail to users which
are allowed within the UU, Urban Use Zoning District.
The site contains 0.3859 acres. The UU, Urban Use Zoning District typically
allows multi -family to develop at a density of 72 units per acre. The development
as proposed would allow an increase in density to 143 units per acre.
Within the UU, Urban Use Zoning District no off-street parking is required. The
applicant has stated parking will be provide for the residents via a lease
agreement for 60 parking spaces within a parking lot located directly behind the
building.
The applicant has indicated lighting, will be placed so as to reflect away from
adjacent residential structures. The fixtures adjacent to the roadways will be
designed to minimize glare to the motoring public.
Signage will comply with signage allowed within the UU, Urban Use Zoning
District. The applicant does not anticipate the placement of ground signage with
the redevelopment of the site.
Section 36-342.1 states objects shall not project from the building facade over
the public right of way except for awnings, balconies and signs as specified in
Section 36-553. Awnings shall not project more than 5-feet from the building
facade and have a minimum clearance of 8-feet above the sidewalk. Balconies
over the public right of way shall have a minimum clearance of 9-feet above the
sidewalk. The maximum projection shall be 4-feet. The applicant has indicated
no new projections or awnings will be added to the building.
Section 36-342.1 states street trees a minimum of three inch caliper shall be
required. The trees shall be located a minimum of 2-feet off the back of curb and
30-feet on center and no closer than 30-feet to a street intersection with a water
source provided. Tree canopy shall be maintained at least 8-feet above the
sidewalk. The applicant has indicated the development will comply with the
typical requirements of the UU, Urban Use Zoning District.
Staff is supportive of the request. Staff does not feel the rezoning to PCD to
allow an increase in the allowable density of multi -family for this site will
adversely impact the area. To staff's knowledge there are no remaining
outstanding technical issues associated with the request.
I. STAFF RECOMMENDATION;
Staff recommends approval of the request subject to compliance with the
comments and conditions as outlined in paragraphs D, E and F of the agenda
staff report.
FILE NO.: Z-8873 (Cont.
PLANNING COMMISSION ACTION: (JULY 11, 2013)
The applicant was present. There were no registered objectors present. Staff
presented the item with a recommendation of approval of the request subject to
compliance with the comments and conditions as outlined in paragraphs D, E and F of
the agenda staff report.
There was no further discussion of the item. The chair entertained a motion for
approval of the item as presented by staff. The motion carried by a vote of 9 ayes,
0 noes and 2 absent.
0