HomeMy WebLinkAboutZ-8356-A Staff AnalysisMAY 24, 2010
ITEM NO.: 2
File No.: Z-8356-A
Owner: Arvest Bank, Phyllis T. Billingsly and Tri-B Realty, Inc.
Applicant: Robert Brown, Development Consultants, Inc.
Address: 1720 S. University Avenue
Description: Northwest corner of University Avenue and Boyle Park Road
Zoned: C-3
Variance Requested: Variances are requested from the area provisions of Section 36-
301 and the buffer provisions of Section 36-522 to allow construction of a commercial
building with reduced setback and buffers.
Justification: The applicant's justification is presented in an attached letter.
Present Use of Property: Existing commercial building and undeveloped/vacant property.
Proposed Use of Property: Branch Bank Facility
STAFF REPORT
A. Public Works Issues:
a. Boyle Park Road is classified on the Master Street Plan as a collector
street. At time of development, a dedication of right-of-way 30 feet from
centerline will be required.
b. University Avenue is classified on the Master Street Plan as a principal
arterial. At time of development, dedication of right-of-way to 55 feet from
centerline is required.
c. At time of development, a 20 foot radial dedication of right-of-way is
required at the intersection of University Avenue and Boyle Park Road.
d. At time of development, sidewalks with appropriate handicap ramps are
required in accordance with Sec. 31-175 of the Little Rock Code and the
master Street Plan shall be installed on Boyle Park Road at the property
line.
e. At time of development, a new driveway apron should be installed on
Boyle Park Road per city standard detail.
f. At time of development, repair and replace any curb and gutter or
.sidewalk that is damaged in the public right-of-way prior to occupancy.
MAY 24, 2010
ITEM NO.: 2 (Con't.
g. Stormwater from the adjacent subdivision currently drains across this
property. At time of development, a drainage easement should be
provided and this open ditch piped to the University Avenue drainage
system.
h. Public Works has no comments on the building setback and the parking in
the buffer.
B. Landscape and Buffer Issues:
Site plan must comply with the City's minimal landscape and buffer ordinance
requirements.
The zoning buffer ordinance and the landscape ordinance require a nine (9) foot
wide buffer and a six foot nine inch wide landscape strip along the western
perimeter of the site, next to the residentially zoned properties. Easements cannot
be counted toward fulfilling the buffer requirement. Seventy percent (70%) of this
area is to remain undisturbed.
The zoning buffer ordinance requires an average 23 foot wide street buffer along
Boyle Park Road. Currently, the site plan does not meet this minimal amount.
C. Staff Analysis:
The C-3 zoned property at 1720 S. University Avenue is occupied by a one-story
commercial building located within the north portion of the property. The property
is located at the northwest corner of S. University Avenue and Boyle Park Road.
Two (2) other buildings were recently removed from the site in preparation of
redevelopment. The overall property is comprised of several platted lots within
Blocks 6 and 7, Cox's subdivision of Taylor and Bodeman subdivision. There are
no platted building lines.
On June 30, 2008 the Board of Adjustment approved variances for reduced buffers
and setbacks associated with a proposed branch bank development at this
location. The applicant has made minor adjustments to the site plan and is back
before the Board to address the variances for reduced buffers and building
setbacks.
The applicant is requesting three (3) variances with the revised site plan. The first
two (2) are from the buffer provisions of Section 36-522(b)(3)a. and 36-522(b)(3)b.
of the City's Zoning Ordinance. These sections require a minimum land use buffer
along the west property line of nine (9) feet, and an average buffer width of 23 feet
along the Boyle Park Road frontage. The applicant is proposing a buffer width of
eight (8) feet along the west property line, seven (7) feet at the dumpster area.
The ordinance does not allow the west five (5) feet of this area to be counted
toward fulfilling the buffer requirement because it is a utility easement. Therefore,
the applicant is providing a three (3) foot wide buffer outside the easement area.
MAY 24, 2010
ITEM NO.: 2 ICon't.
This buffer area does widen out just north of the drive-thru lanes. The street buffer
along Boyle Park Road is 13 feet in width.
The third variance is from the area provisions of Section 36-301(1) of the City's
Zoning Ordinance. This section requires a minimum front building setback of 25
feet. The proposed building will be located 14.90 feet back from the front (east)
property line at its nearest point. The building previously approved had a front
setback of six (6) feet.
Staff is supportive of the requested variances. Staff feels the proposed
redevelopment plan for the property will be quality improvement within this corridor
of S. University Avenue. The shallow depth of the property, being only
approximately 110 feet, makes redevelopment with minimum building setbacks
and buffers being met very difficult. The existing northernmost and southernmost
(as previously existed) commercial buildings on the site do/did not conform to the
minimum front and rear setback requirements. Any future redevelopment of the
site would likely face the same issues as this proposed development. Additionally,
any variances from the City's Landscape Ordinance will require approval from the
City Beautiful Commission. Staff feels the proposed redevelopment plan for this
property will have no adverse impact on the adjacent properties or the general
area.
D. Staff Recommendation:
Staff recommends approval of the requested setback and buffer variances, subject
to the following conditions:
a. Compliance with the Public Works requirements as noted in paragraph A.
of the Agenda staff report, including any variances which may be granted
by the City's Board of Directors.
b. Compliance with the Landscape and Buffer Ordinance requirements with
the exception of the buffer variances as approved by the Board.
Variances from the Landscape Ordinance must be approved by the City
Beautiful Commission.
c. The dumpster area must be screened as per ordinance requirements.
d. Any signage must conform to ordinance standards. Any ground sign must
meet the minimum sign setback requirements after any additional right-of-
way dedication.
BOARD OF ADJUSTMENT: (MAY 24, 2010)
The applicant was present. There were no objectors present. Staff presented the
item and a recommendation of approval as noted in the "staff recommendation"
above. There was no further discussion. The item was placed on the consent
agenda and approved as recommended by staff. The vote was 5 ayes, 0 noes and
0 absent.
JUNE 30, 2008
ITEM NO.- 5
File No.: Z-8356
Owner: Phyllis T. Billingsley, Tri-B Realty, Baird Inc., Barnes Revocable Trust
Applicant: Dickson Flake, Colliers International
Address: 1716-1818 S. University Avenue
Description: Northwest Corner of S. University Ave. and Boyle Park Road
(W. 19th Street)
Zoned: C-3
Variance Requested: Variances are requested from the area provisions of Section 36-301
and the buffer provisions of Section 36-522 to allow a bank development with reduced
setbacks and buffers.
Justification: The applicant's justification is presented in an attached letter.
Present Use of Property: Commercial
Proposed Use of Property: Branch Bank
STAFF REPORT
A. Public Works Issues:
1. Boyle Park Road is classified on the Master Street Plan as a collector
street. At time of development, a dedication of right-of-way 30 feet from
centerline will be required.
2. University Ave. is classified on the Master Street Plan as a principal
arterial. At time of development, dedication of right-of-way to 55 feet
from centerline will be required.
3. At time of development, a 20 foot radial dedication of right-of-way is
required at the intersection of University Ave. and Boyle Park Road.
4. Driveway locations and widths do not meet the traffic access and
circulation requirements of Sections 30-43 and 31-210. At time of
development, the island in the driveway on Boyle Park Road must be
removed and the width of driveway must not exceed 36 feet.
5. At time of development, sidewalks with appropriate handicap ramps are
required in accordance with Sec. 31-175 of the Little Rock Code and the
Master Street Plan shall be installed on Boyle Park Road at the property
line.
JUNE 30, 2008
ITEM NO.: 5 CQN'T.
6. At time of development, a new driveway apron should be installed on
Boyle Park Road per city standard detail.
7. At time of development, repair or replace any curb and gutter or
sidewalk that is damaged in the public right-of-way prior to occupancy.
8. The northern most angled parking space is not maneuverable for
vehicles to access successfully.
9. Stormwater from the adjacent subdivision currently drains across this
property. At time of development, a drainage easement should be
provided and this open ditch piped to the University Ave. drainage
system.
10. Public Works has no comments on the building setback and the parking
in the buffer.
B. Landscape and Buffer Issues:
Site plan must comply with the City's minimal landscape and buffer ordinance
requirements.
Currently, the dumpster is located within both the required landscape perimeter
strip and the zoning buffer land use strip. This dumpster needs to be moved
east allowing for a six foot nine inch wide (6-9") landscape strip. A variance
must be obtained from both the Board of Adjustment and the City Beautiful
Commission prior to the issuance of a building permit.
The zoning buffer ordinance and the landscape ordinance require a six foot
nine inch wide landscape strip along the western perimeter of the site, next to
the residentially zoned properties. Currently, the parking lot shown in located
within the minimal landscape strip. Seventy percent (70%) of this area is to
remain undisturbed.
The reduction of the backup area for the parking lot along Boyle Park Road will
result in additional landscape and buffer area long the western perimeter of the
site, next to the residentially zoned property. This is a requirement of both the
landscape ordinance and the zoning buffer ordinance. The minimal amount
allowed by ordinance is six foot nine inches (6-9"). A variance must be
obtained from both the Board of Adjustment and the City Beautiful Commission
prior to the issuance of a building permit.
The zoning buffer ordinance requires an average 23 foot wide street buffer
along Boyle Park Road. Currently, the site plan does not meet this minimal
amount.
The zoning buffer ordinance and the landscape ordinance require a six foot
nine inch wide (6'-9") street buffer along University Avenue. it appears that a
portion of the middle parking lot falls below this minimal amount. A variance
must be obtained from both the Board of Adjustment and the City Beautiful
Commission prior to the issuance of a building permit.
JUNE 30, 2008
ITEM NO.: 5 (CON'T.
C. Staff Analysis:
The C-3 zoned property at 1716-1818 S. University Avenue is occupied by
three (3) one-story commercial buildings. The property is located at the
northwest corner of S. University Avenue and Boyle Park Road (W. 191h
Street). There are existing driveways from S. University Avenue and Boyle
Park Road which serve as access to the commercial buildings. There is paved
parking along all sides of the two (2) southernmost commercial buildings and
on the east side of the north building. The overall property is comprised of
several platted lots within Blocks 6 and 7, Cox's Subdivision of Taylor and
Bodeman Subdivision. There are no platted building lines.
The applicant proposes to remove the existing buildings and parking and
redevelop the site for a branch bank facility as shown on the attached site
plan. The development includes a 4,000 square foot branch bank building
located within the south half of the property with a future expansion on its east
side as shown. Drive through lanes with a covered canopy are located on the
north side of the building. A customer parking lot is located on the south side
of the building with an access drive from Boyle Park Road. An employee
parking lot and dumpster area are located within the north portion of the
property, with an access drive from S. University Avenue. A circular driveway
will serve the drive through area from S. University Avenue. A screening fence
will be ,located along the west property line. The proposed building will be
located six (6) feet from the front (east) property line (after expansion), 8.5 feet
from the rear (west) property line, 68 feet from the south side property line and
over 180 feet from the north side property line. A billboard which exists within
the north half of the property will remain.
The applicant is requesting two4.2) variances'with the proposed redevelopment
plan. The first is from the buffer provisions of Sections 36-522(b)(3)a. and 36-
522(b)(3)b. of the City's Zoning Ordinance. These sections require minimum
street and land use buffers along the east and west property lines of nine (9)
feet, and an average buffer width of 23 feet (at no point less than 11.5 feet)
along the Boyle Park Road frontage. The parking area near the center of the
property along S. University (adjacent to the drive through area) has a street
buffer ranging from zero (0) feet to six (6) feet. T-be land use buffer along the
w-sLpraperty-line-drops to less -than nine (9)-feet"at two (2) points; the'
dumpster area adjacent to the northernmost parking area (6'-9") and along the
west -side of the southernmost parking area�(6'4 ). The street buffer along
Boyle Park Road is 13 feet in width, averaging less than the 23 feet as
requirect.
The second variance is from the area provisions of Secfions 36-301(e)(1) and
36-301(e)(3). These sections require minimum front and rear building
setbacks of 25 feet -A— -noted. previously,-tlie proposed building will have a six
(6) foot setback from the front (east) property line (after future extension) and
an 8.5 foot setback from the west (rear) property line.
JUNE 30, 2008
ITEM NO.: 5 (CON'T.
Staff is supportive of the requested variances. Staff feels the proposed
redevelopment plan for the property will be quality improvement within this
corridor of S. University Avenue. The shallow depth of the property, being only
approximately 110 feet, makes redevelopment with minimum building setbacks
and buffers being met very difficult. The existing northernmost and
southernmost commercial buildings on the site do not conform to the minimum
front and rear setback requirements. Any future redevelopment of the site
would likely face the same issues as this proposed development. With respect
to the requested front setback of six (6) feet, staff will support the requested
front setback after dedication of any additional right-of-way along S. University
Avenue. Additionally, any variances from the City's Landscape Ordinance will
require approval from the City Beautiful Commission. Staff feels the proposed
redevelopment plan for this property will have no adverse impact on the
adjacent properties or the general area.
D. Staff Recommendation:
Staff recommends approval of the requested setback and buffer variances,
subject to the following conditions:
1. Compliance with the Public Works requirements as noted in paragraph
A. of the Agenda staff report.
2. Compliance with the Landscape and Buffer requirements as noted in
paragraph B. of the Agenda staff report. Variances from the Landscape
Ordinance must be approved by the City Beautiful Commission.
3. Staff supports the requested reduced front building setback after
dedication of any additional right-of-way along the S. University Avenue
frontage.
4. The dumpster area must be screened as per ordinance requirements.
5. Any signage must conform to ordinance standards. The ground sign at
the southeast corner of the property must meet the minimum sign
setback requirements after any additional right-of-way dedication.