HomeMy WebLinkAbout2023-11-07 1513 email Attachment - Permit Plans_Bricky, Danny_11072023_REV-BVICINITY MAP
CUSTOMER INFORMATION
NAME:DANNY BRICKY
DATE:11/7/2023
SCALE:AS NOTED REV:B
AHJ:AR-CITY OF LITTLE ROCK
PRN NUMBER:SNS-85385
DRAFTED BY:
C.KOWSALYA
QC'ED BY:ABU.S
PAPER SIZE:17"X11"
UTILITY:ENTERGY(AR)
ADDRESS:1402 COMMERCE ST, LITTLE
ROCK, AR 72202
34.734565, -92.268403
APN: 34L0200314300
·ELECTRIC CODE:NEC 2020
·FIRE CODE:IFC 2021
·BUILDING CODE:IBC 2021
·RESIDENTIAL CODE:IRC 2021
COVER PAGE
T-01SCALE:1"=30'-0"
LICENSE NUMBER: 2020012960
1.MODULES ARE LISTED UNDER UL 1703/61730
AND CONFORM TO THE STANDARDS.
2.INVERTERS ARE LISTED UNDER UL 1741 AND
CONFORM TO THE STANDARDS.
3.DRAWINGS ARE DIAGRAMMATIC, INDICATING
GENERAL ARRANGEMENT OF THE PV SYSTEM AND
THE ACTUAL SITE CONDITION MIGHT VARY.
4.WORKING CLEARANCES AROUND THE NEW PV
ELECTRICAL EQUIPMENT WILL BE MAINTAINED IN
ACCORDANCE WITH NEC 110.26.
5.ALL GROUND WIRING CONNECTED TO THE MAIN
SERVICE GROUNDING IN MAIN SERVICE PANEL/
SERVICE EQUIPMENT.
6.ALL CONDUCTORS SHALL BE 600V, 90°C
STANDARD COPPER UNLESS OTHERWISE NOTED.
7.WHEN REQUIRED, A LADDER SHALL BE IN PLACE
FOR INSPECTION IN COMPLIANCE WITH OSHA
REGULATIONS.
8.THE SYSTEM WILL NOT BE INTERCONNECTED BY
THE CONTRACTOR UNTIL APPROVAL FROM THE
LOCAL JURISDICTION AND/OR THE UTILITY.
9.ROOF ACCESS POINT SHALL BE LOCATED IN
AREAS THAT DO NOT REQUIRE THE PLACEMENT
OF GROUND LADDERS OVER OPENINGS SUCH AS
WINDOWS OR DOORS, AND LOCATED AT STRONG
POINTS OF BUILDING CONSTRUCTION WHERE THE
ACCESS POINT DOES NOT CONFLICT WITH
OVERHEAD OBSTRUCTIONS SUCH AS TREES,
WIRES OR SIGNS.
10.PV ARRAY COMBINER/JUNCTION BOX
PROVIDES TRANSITION FROM ARRAY WIRING TO
CONDUIT WIRING
GENERAL NOTES
SITE PLAN LAYOUT
ENGINEERING SCOPE OF WORK
1.ILLUMINE INDUSTRIES INC. HAS ONLY PROVIDED DRAFTING SERVICES FOR THE PERMIT DRAWINGS. NO ACTUAL ENGINEERING WORK, ENGINEERING REVIEW OR ENGINEERING
APPROVAL HAS BEEN CONDUCTED BY ILLUMINE INDUSTRIES INC UNLESS NOTED OTHERWISE.
2.WHEN A PROFESSIONAL ENGINEER APPROVES AND SEALS THE DESIGN FOR COMPONENTS OF THEIR RESPECTIVE DISCIPLINE (STRUCTURAL/ELECTRICAL) SHOWN ON THESE PERMIT
DRAWINGS, HE/SHE:
a.TAKES FULL DIRECT CONTROL OF THE ENGINEERED DESIGN
b.IS GIVEN ACCESS TO PERSONALLY SUPERVISE AND RECTIFY ANY ASPECT OF THE ENGINEERED DESIGN
c.HAS FULLY ACCEPTED RESPONSIBILITY FOR THE ENGINEERED DESIGN
SHEET CATALOG
INDEX NO.DESCRIPTION
T-01 COVER PAGE
G-01 GENERAL NOTES
S-01 MOUNTING DETAIL
S-02 STRUCTURAL DETAIL
E-01 THREE LINE DIAGRAM
E-02 ELECTRICAL CALCULATIONS
PL-01 CIRCUIT MAP
PL-02 WARNING PLACARDS
SS SPEC SHEET(S)
PHOTOVOLTAIC ARRAY ON THE ROOF
DANNY BRICKY - 6.400 kW DC, 4.760 kW AC
SCOPE OF WORK
APPLICABLE CODES
RESIDENCE
(E) UTILITY METER WITH MAIN SERVICE PANEL (EXTERIOR)
(N) PV AC DISCONNECT (EXTERIOR)
(N) LOAD CENTER (EXTERIOR)
(E) MAIN LUG PANEL (INTERIOR)
PERIMETER FENCE
GATE WITH FENCE
DRIVEWAY
PROPERTY LINE
DETACHED STRUCTURE
GATE WITH FENCE
DECK
POOL
WALKWAY
154'-10"
153'-9"
39'-6"
13'
39'-2"
44'-10"COMMERCE ST103'
GATE WITH FENCE
PORCH
GENERAL SYSTEM INFORMATION:
SYSTEM SIZE:
6.400kW DC, 4.760 kW AC
MODULES:
(16)SILFAB SIL-400NU (400W)
INVERTER:
(2)HOYMILES HM-1200N (240V)
(3)HOYMILES HM-600N (240V)
(2)HOYMILES HM-300N (240V)
BRANCH DETAILS:
1X3 , 1X4 MICROINVERTER BRANCHES
GENERAL NOTES
CUSTOMER INFORMATION
NAME:DANNY BRICKY
DATE:11/7/2023
SCALE:AS NOTED REV:B
AHJ:AR-CITY OF LITTLE ROCK
PRN NUMBER:SNS-85385
DRAFTED BY:
C.KOWSALYA
QC'ED BY:ABU.S
PAPER SIZE:17"X11"
UTILITY:ENTERGY(AR)
ADDRESS:1402 COMMERCE ST, LITTLE
ROCK, AR 72202
34.734565, -92.268403
APN: 34L0200314300
LICENSE NUMBER: 2020012960
GENERAL NOTES
G-01
ROOF ACCESS PATHWAYS AND SETBACKS:
1205.1 GENERAL:
SOLAR PHOTOVOLTAIC (PV) SYSTEMS SHALL BE INSTALLED WITH THE INTERNATIONAL BUILDING CODE OR INTERNATIONAL RESIDENTIAL CODE. THE ELECTRICAL PORTION OF SOLAR PV SYSTEMS SHALL BE INSTALLED IN ACCORDANCE WITH
NFPA 70. ROOFTOP-MOUNTED SOLAR PHOTOVOLTAIC SYSTEMS SHALL BE INSTALLED IN ACCORDANCE WITH SECTIONS 1205.2 THROUGH 1205.4.3. GROUND-MOUNTED SOLAR PHOTOVOLTAIC SYATEMS SHALL COMPLY WITH SECTION 1205.5.
1205.2 ACCESS AND PATHWAYS
ROOF ACCESS, PATHWAYS, AND SPACING REQUIREMENTS SHALL BE PROVIDED IN ACCORDANCE WITH SECTIONS 1205.2.1 THROUGH 1205.3.3. PATHWAYS SHALL BE OVER AREAS CAPABLE OF SUPPORTING FIRE FIGHTERS ACCESSING THE
ROOF. PATHWAYS SHALL BE LOCATED IN AREAS WITH MINIMAL OBSTRUCTIONS, SUCH AS VENT PIPES, CONDUIT OR MECHANICAL EQUIPMENT.
EXCEPTIONS:
1.DETACHED, NONHABITABLE GROUP U STRUCTURES INCLUDING, BUT NOT LIMITED TO, DETACHED GARAGES SERVING GROUP R-3 BUILDINGS, PARKING SHADE STRUCTURES, CARPORTS, SOLAR TRELLISES AND SIMILAR STRUCTURES.
2.ROOF ACCESS, PATHWAYS AND SPACING REQUIREMENTS NEED NOT BE PROVIDED WHERE THE FIRE CODE OFFICIAL HAS DETERMINED THAT ROOFTOP OPERATIONS WILL NOT BE EMPLOYED.
3.BUILDING-INTEGRATED PHOTOVOLTAIC (BIPV) SYSEMS WHERE THE BIPV SYSTEMS ARE APPROVED, INTEGRATED INTO THE FINISHED ROOF SURFACE AND ARE LISTED IN ACCORDANCE WITH A NATIONAL TEST STANDARD DEVELOPED TO
ADDRESS SECTION 690.12(B)(2) OF NFPA 70. THE REMOVAL OR CUTTING AWAY OF PORTIONS OF THE BIPV SYSTEM DURING FIRE-FIGHTING OPERATIONS SHALL NOT EXPOSE A FIRE FIGHTER TO ELECTRICAL SHOCK HAZARDS.
1205.2.1 SOLAR PHOTOVOLTAIC (PV) SYSTEMS FOR GROUP R-3 BUILDINGS:
SOLAR PHOTOVOLTAIC (PV) SYSTEMS FOR GROUP R-3 BUILDINGS SHALL COMPLY WITH SECTIONS 1205.2.1.1 THROUGH 1205.2.3.
EXCEPTIONS:
1.THESE REQUIREMENTS SHALL NOT APPLY TO STRUCTURES DESIGNED AND CONSTRUCTED IN ACCORDANCE WITH THE INTERNATIONAL RESIDENTIAL CODE.
2.THESE REQUIREMENTS SHALL NOT APPLY TO ROOFS WITH SLOPES OF 2 UNITS VERTICAL IN 12 UNITS HORIZONTAL (16.7-PERCENT) OR LESS.
1205.2.1.1 PATHWAYS TO RIDGE:
NOT FEWER THAN TWO 36-INCH-WIDE (914 MM) PATHWAYS ON SEPARATE ROOF PLANES, FROM LOWEST ROOF EDGE TO RIDGE, SHALL BE PROVIDED ON ALL BUILDINGS. NOT FEWER THAN ONE PATHWAY SHALL BE PROVIDED ON THE STREET
OR DRIVEWAY SIDE OF THE ROOF. FOR EACH ROOF PLANE WITH A PHOTOVOLTAIC ARRAY, NOT FEWER THAN ONE 36-INCH-WIDE (914 MM) PATHWAY FROM LOWEST ROOF EDGE TO RIDGE SHALL BE PROVIDED ON THE SAME ROOF PLANE AS
THE PHOTOVOLTAIC ARRAY, ON AN ADJACENT ROOF PLANE OR STRADDLING THE SAME AND ADJACENT ROOF PLANES.
1205.2.1.2 SETBACKS AT RIDGE:
FOR PHOTOVOLTAIC ARRAYS OCCUPYING 33 PERCENT OR LESS OF THE PLAN VIEW TOTAL ROOF AREA, A SETBACK OF NOT LESS THAN 18 INCHES (457 MM) WIDE IS REQUIRED ON BOTH SIDES OF A HORIZONTAL RIDGE. FOR PHOTOVOLTAIC
ARRAYS OCCUPYING MORE THAN 33 PERCENT OF THE PLAN VIEW TOTAL ROOF AREA, A SETBACK OF NOT LESS THAN 36 INCHES (457 MM) WIDE IS REQUIRED ON BOTH SIDES OF A HORIZONTAL RIDGE.
1205.2.1.3 ALTERNATIVE SETBACKS AT RIDGE:
WHERE AN AUTOMATIC SPRINKLER SYSTEM IS INSTALLED WITHIN THE DWELLING IN ACCORDANCE WITH SECTION 903.3.1.3, SETBACKS AT THE RIDGE SHALL CONFORM TO ONE OF THE FOLLOWING:
1.FOR PHOTOVOLTAIC ARRAYS OCCUPYING 66 PERCENT OR LESS OF THE PLAN VIEW TOTAL ROOF AREA, A SETBACK OF NOT LESS THAN 18 INCHES (457 MM) WIDE IS REQUIRED ON BOTH SIDES OF A HORIZONTAL RIDGE.
2.FOR PHOTOVOLTAIC ARRAYS OCCUPYING MORE THAN 66 PERCENT OF THE PLAN VIEW TOTAL ROOF AREA, A SETBACK OF NOT LESS THAN 36 INCHES (914 MM) WIDE IS REQUIRED ON BOTH SIDES OF A HORIZONTAL RIDGE.
1205.2.2 EMERGENCY ESCAPE AND RESCUE OPENINGS:
PANELS AND MODULES INSTALLED ON GROUP R-3 BUILDINGS SHALL NOT BE PLACED ON THE PORTION OF A ROOF THAT IS BELOW AN EMERGENCY ESCAPE AND RESCUE OPENING. A PATHWAY OF NOT LESS THAN 36 INCHES (914 MM) WIDE
SHALL BE PROVIDED TO THE EMERGENCY ESCAPE AND RESCUE OPENING.
1205.3 OTHER THAN GROUP R-3 BUILDINGS:
WHERE BUILDING-INTEGRATED PHOTOVOLTAIC (BIPV) SYSTEMS ARE INSTALLED IN A MANNER THAT CREATES WITH ELECTRICAL HAZARDS FROM VIEW, MARKINGS SHALL BE PROVIDED TO IDENTIFY THE HAZARDOUS AREAS TO AVOID. THE
MARKINGS SHALL BE REFLECTIVE AND BE VISIBLE FROM GRADE.
EXCEPTION: BIPV SYSTEMS LISTED IN ACCORDANCE WITH SECTION 690.12(B)(2) OF NFPA 70, WHERE THE REMOVAL OR CUTTING AWAY PORTIONS OF THE BIPV SYSTEM DURING FIRE-FIGHTING OPERATIONS HAVE BEEN DETERMINED TO
NOT EXPOSE A FIRE FIGHTER TO ELECTRICAL SHOCK HAZARDS.
1205.3 OTHER THAN GROUP R-3 BUILDINGS:
ACCESS TO SYSTEMS FOR BUILDINGS, OTHER THAN THOSE CONTAINING GROUP R-3 OCCUPANCIES, SHALL BE PROVIDED IN ACCORDANCE WITH SECTIONS 1205.3.1 THROUGH 1205.3.3.
EXCEPTION:
WHERE IT IS DETERMINED BY THE FIRE CODE OFFICIAL THAT THE ROOF CONFIGURATION IS SIMILAR TO THAT OF A GROUP R-3 OCCUPANCY, THE RESIDENTIAL ACCESS AND VENTILATION REQUIREMENTS IN SECTIONS 1205.2.1.1 THROUGH
1205.2.1.3 ARE A SUITABLE ALTERNATIVE.
1205.3.1 PERIMETER PATHWAYS:
THERE SHALL BE A MINIMUM 6-FOOT-WIDE (1829 MM) CLEAR PERIMETER AROUND THE EDGES OF THE ROOF.
EXCEPTION:
WHERE EITHER AXIS OF THE BUILDING IS 250 FEET (76 200 MM) OR LESS, THE CLEAR PERIMETER AROUND THE EDGES OF THE ROOF SHALL BE PERMITTED TO BE REDUCED TO A MINIMUM WIDTH OF 4 FEET (1219 MM).
1205.3.2 INTERIOR PATHWAYS
INTERIOR PATHWAYS SHALL BE PROVIDED BETWEEN ARRAY SECTIONS TO MEET THE FOLLOWING REQUIREMENTS:
1.PATHWAYS SHALL BE PROVIDED AT INTERVALS NOT GREATER THAN 150 FEET (45 720 MM) THROUGHOUT THE LENGTH AND WIDTH OF THE ROOF.
2.A PATHWAY NOT LESS THAN 4 FEET (1219 MM) WIDE IN A STRAIGHT LINE TO ROOF STANDPIPES OR VENTILATION HATCHES.
3.A PATHWAY NOT LESS THAN 4 FEET (1219 MM) WIDE AROUND ROOF ACCESS HATCHES, WITH NOT FEWER THAN ONE SUCH PATHWAY TO A PARAPET OR ROOF EDGE.
1205.3.3 SMOKE VENTILATION:
THE SOLAR INSTALLATION SHALL BE DESIGNED TO MEET THE FOLLOWING REQUIREMENTS:
1.WHERE NONGRAVITY-OPERATED SMOKE AND HEAT VENTS OCCUR, A PATHWAY NOT LESS THAN 4 FEET (1219 MM) WIDE SHALL BE PROVIDED BORDERING ALL SIDES.
2.WHERE GRAVITY-OPERATED DROPOUT SMOKE AND HEAT VENTS OCCUR, A PATHWAY NOT LESS THAN 4 FEET(1219MM) WIDE ON NOT FEWER THAN ONE SIDE.
3.SMOKE VENTILATION OPTIONS BETWEEN ARRAY SECTIONS SHALL BE ONE OF THE FOLLOWING:
3.1 A PATHWAY NOT LESS THAN 8 FEET (2438 MM) WIDE.
3.2 A PATHWAY NOT LESS THAN 4 FEET (1219 MM) WIDE BORDERING 4-FOOT BY 8-FOOT (1219 MM BY 2438 MM) VENTING CUTOUTS EVERY 20 FEET (6096 MM) ON ALTERNATING SIDES OF THE PATHWAY.
AERIAL VIEW
CUSTOMER INFORMATION
NAME:DANNY BRICKY
DATE:11/7/2023
SCALE:AS NOTED REV:B
AHJ:AR-CITY OF LITTLE ROCK
PRN NUMBER:SNS-85385
DRAFTED BY:
C.KOWSALYA
QC'ED BY:ABU.S
PAPER SIZE:17"X11"
UTILITY:ENTERGY(AR)
ADDRESS:1402 COMMERCE ST, LITTLE
ROCK, AR 72202
34.734565, -92.268403
APN: 34L0200314300
LICENSE NUMBER: 2020012960
MOUNTING DETAIL
S-01SCALE:1"=10'-0"
NOTE(N):PENETRATIONS ARE STAGGERED
ALUMINUM RAILS
SITE INFORMATION - WIND SPEED: 105 MPH AND SNOW LOAD: 10 PSF
SR.
NO AZIMUTH PITCH NO. OF
MODULES
ARRAY AREA
(SQ. FT.)ROOF TYPE ATTACHMENT ROOF
EXPOSURE FRAME TYPE FRAME
SIZE
FRAME
SPACING
MAX RAIL
SPAN
OVER
HANG
MP-01 189 °34°2 43.9 COMPOSITION
SHINGLE
SPLICE FOOT
X (DECK
MOUNT)
ATTIC RAFTERS 2 X 6 1'-10"4'-0"1'-6"
MP-02 279 °34°3 65.8 COMPOSITION
SHINGLE
SPLICE FOOT
X (DECK
MOUNT)
ATTIC RAFTERS 2 X 6 1'-10"4'-0"1'-6"
MP-03 189 °34°9 197.5 COMPOSITION
SHINGLE
SPLICE FOOT
X (DECK
MOUNT)
ATTIC RAFTERS 2 X 6 1'-10"4'-0"1'-6"
MP-04 279 °33°2 43.9 COMPOSITION
SHINGLE
SPLICE FOOT
X (DECK
MOUNT)
ATTIC RAFTERS 2 X 6 1'-10"4'-0"1'-6"
ARRAY MP-03
ARRAY MP-02
ARRAY MP-01
ARRAY MP-04
4'
MID CLAMPMODULE MODULEEND CLAMP
CUSTOMER INFORMATION
NAME:DANNY BRICKY
DATE:11/7/2023
SCALE:AS NOTED REV:B
AHJ:AR-CITY OF LITTLE ROCK
PRN NUMBER:SNS-85385
DRAFTED BY:
C.KOWSALYA
QC'ED BY:ABU.S
PAPER SIZE:17"X11"
UTILITY:ENTERGY(AR)
ADDRESS:1402 COMMERCE ST, LITTLE
ROCK, AR 72202
34.734565, -92.268403
APN: 34L0200314300
LICENSE NUMBER: 2020012960
STRUCTURAL DETAIL
S-02
MID-CLAMP AND END-CLAMP ANATOMY
5/16"-18 SS BOLT
SS SPLIT LOCK WASHER
(TORQUE TO 16FT-LBS)
GROUNDING LUG
BOUNDING
CHANNEL NUT
RAIL
6-12 AWG BARE
COPPER WIRE
NOTES:
·ALL HARDWARE IS INCLUDED FROM MANUFACTURER
·A MINIMUM OF ONE GROUND LUG IS TO BE INSTALLED ON EVERY CONTINUOUS
ROW OF MODULES
·GROUNDING LUG MAY BE INSTALLED IN EITHER RAIL CHANNEL
·GROUNDING LUG MAY BE INSTALLED SO GROUND WIRE IS PARALLEL OR
PERPENDICULAR TO RAIL
·ENSURE SPLIT LOCK WASHER IS INSTALLED ON TOP OF COPPER WIRE.
SCALE:NTS
GROUNDING
SS BONDING PIN
MID CLAMP
ASSEMBLY
MODULE
FRAME
PEGASUS RAIL
CHANNEL NUT
MODULE TO MODULE & MODULE TO RAIL
GROUNDING MID-CLAMP
SCALE: NTS
GROUNDING DETAILS
PEGASUS RAIL
PEGASUS INTERNAL SPLICE
SELF-DRILLING SCREW
SCALE: NTS
RAIL TO RAIL
INSTALLATION NOTES
1.STRUCTURAL ROOF MEMBER LOCATIONS
ARE ESTIMATED AND SHOULD BE LOCATED
AND VERIFIED BY THE CONTRACTOR WHEN
LAG BOLT PENETRATION OR MECHANICAL
ATTACHMENT TO THE STRUCTURE IS
REQUIRED.
2.ROOFTOP PENETRATIONS FOR SOLAR
RACKING WILL BE COMPLETED AND SEALED
WITH APPROVED SEALANT PER CODE BY A
LICENSED CONTRACTOR.
3.LAGS MUST HAVE A MINIMUM 7/16"
THREAD EMBEDMENT INTO THE
STRUCTURAL MEMBER.
4.ALL PV RACKING ATTACHMENTS SHALL BE
STAGGERED BY ROW BETWEEN THE ROOF
FRAMING MEMBERS AS NECESSARY.
5.ROOF MOUNTED STANDARD RAIL
REQUIRES ONE THERMAL EXPANSION GAP
FOR EVERY RUN OF RAIL GREATER THAN
40'.
6.ALL CONDUCTORS AND CONDUITS ON
THE ROOF SHALL BE MINIMUM 1-1/2"
ABOVE THE ROOF SURFACE (INCLUDING
CABLES UNDERNEATH MODULES AND
RACKING).
7.THE PV INSTALLATION SHALL NOT
OBSTRUCT ANY PLUMBING, MECHANICAL
OR BUILDING ROOF VENTS.
SCALE:NTS
MODULES DATA
SILFAB SIL-400NU (400W)
MODULE DIMS 79.8 "x39.6"x1.5"
LAG SCREWS M5x60: 7/16" MIN EMBEDMENT
SPLICE FOOT X
SOLAR MODULE
PEGASUS RAIL
6" MAX
4 STAINLESS STEEL M5x60 LAG SCREW
7/16" MIN EMBEDMENT TO ROOF DECK
DECK
ATTACHMENT DETAIL-K2 SPLICE FOOT X (DECK MOUNT)
LOAD BEARING WALL SCALE:NTS
2 X 6 RAFTERS
@1'-10" SPACING
COMPOSITION SHINGLE ROOF
MODULE
M5x60 LAG SCREWS
4 LAG SCREWS PER ATTACHMENT
ROOF FRAMING DETAILS
DEAD LOAD CALCULATIONS
BOM QUANTITY LBS/UNIT TOTAL WEIGHT
(LBS)
MODULES 16 49.1 785.60
MID-CLAMP 22 0.170 3.74
END-CLAMP 20 0.300 6.00
RAIL LENGTH 126 0.790 99.54
SPLICE BAR 2 0.650 1.30
SPLICE FOOT X
(DECK MOUNT)40 1.45 58.00
MICRO-INVERTER-1
HOYMILES
HM-1200N (240V)
2 8.26 16.52
MICRO-INVERTER-2
HOYMILES HM-600N
(240V)
3 6.61 19.83
MICRO-INVERTER-3
HOYMILES HM-300N
(240V)
2 4.36 8.72
TOTAL WEIGHT OF THE SYSTEM (LBS)999.25
TOTAL ARRAY AREA ON THE ROOF (SQ. FT.)351.12
WEIGHT PER SQ. FT.(LBS)2.85
WEIGHT PER PENETRATION (LBS)24.98
3 1
G G
DC CONDUCTORS
AC CONDUCTORS
HOYMILES HM-1200N (240V)
MICROINVERTER
HOYMILES HM-600N (240V)
MICROINVERTER
(N)JUNCTION
BOX.
G
1A
(N)JUNCTION
BOX.
G
2
G
20A
BRP12L125R LOAD CENTER,
INSTALL (2)20A PV 2P BREAKERS
(ONLY FOR SOLAR, NO LOADS TO
BE ADDED)
(N)125A LOAD CENTER
(N)60A AC
DISCONNECT
G
40A FUSE
EATON DG222NRB
PV SYSTEM AC
DISCONNECT KNIFE
BLADE FUSED, 60A,
120/240V 2P
20A
N
(1)BRANCH OF 3 MICROINVERTERS((2)HOYMILES HM-1200N (240V)(1)HOYMILES HM-300N (240V))
3
(1)BRANCH OF 4 MICROINVERTERS((3)HOYMILES HM-600N (240V)(1)HOYMILES HM-300N (240V))
UTILITY
GRID
(E) GROUND
ELECTRODE
N
G
EXISTING 120/240V 1PH 60HZ
METER#:ENTERGY(AR)
AM11690897M
(E)200A LUG FED
MAIN PANEL
PV BREAKER AT THE
OPPOSITE END OF
BUSBAR
(N)30A 2P
PV BREAKERN
G
LOADS
(E)225A END FED
MAIN PANEL
(E)200A MAINBREAKERE
LOADS
G
HOYMILES HM-300N (240V)
MICROINVERTER
ELECTRICAL NOTES
CUSTOMER INFORMATION
NAME:DANNY BRICKY
DATE:11/7/2023
SCALE:AS NOTED REV:B
AHJ:AR-CITY OF LITTLE ROCK
PRN NUMBER:SNS-85385
DRAFTED BY:
C.KOWSALYA
QC'ED BY:ABU.S
PAPER SIZE:17"X11"
UTILITY:ENTERGY(AR)
ADDRESS:1402 COMMERCE ST, LITTLE
ROCK, AR 72202
34.734565, -92.268403
APN: 34L0200314300
LICENSE NUMBER: 2020012960
THREE LINE DIAGRAM
E-01
MODULE SPECIFICATION
MODEL SILFAB SIL-400NU
(400W)
MODULE POWER @ STC 400W
OPEN CIRCUIT VOLTAGE:Voc 48.7 V
MAX POWER VOLTAGE:Vmp 40V
SHORT CIRCUIT CURRENT:Isc 10.5A
MAX POWER CURRENT:Imp 10.1A
NOTE(N): EACH MICROINVERTER IS RAPID SHUTDOWN COMPLIANT
THREE LINE DIAGRAM: DC SYSTEM SIZE - 6.400 kW, AC SYSTEM SIZE - 4.760 kW AC
1.CONDUCTORS EXPOSED TO WET
LOCATIONS SHALL BE SUITABLE FOR
USE IN WET LOCATIONS PER NEC
310.10(C).
2.CONDUCTORS EXPOSED TO SUNLIGHT
SHALL BE LISTED AS SUNLIGHT
RESISTANT PER NEC 310.10(D).
3.MAXIMUM DC/AC VOLTAGE DROP SHALL
BE NO MORE THAN 3%.
4.ALL CONDUCTORS SHALL BE IN
CONDUIT UNLESS OTHERWISE NOTED.
5.BREAKER/FUSES SIZED ACCORDING
PER NEC ARTICLE 240.
6.AC GROUNDING ELECTRODE
CONDUCTOR (GEC) SIZED PER NEC
250.66.
7.EQUIPMENT GROUNDING CONDUCTOR
(EGC) SIZED PER NEC 250.122.
8.AMBIENT TEMPERATURE ADJUSTMENT
FACTOR IS BASED ON
TABLE NEC 310.15(B)(1).
9.CURRENT CARRYING CONDUCTOR
ADJUSTMENT FACTOR IS BASED ON NEC
310.15(C)(1).
10.MAX. SYSTEM VOLTAGE CORRECTION
IS PER NEC 690.7.
11.CONDUCTORS ARE SIZED PER NEC
310.16.
SPECIFICATIONS MICROINVERTER-1 MICROINVERTER-2 MICROINVERTER-3
MODEL HOYMILES HM-1200N (240V)HOYMILES HM-600N (240V)HOYMILES HM-300N (240V)
POWER RATING 1200W 590 W 295W
MAX OUTPUT CURRENT 5A 2.46A 1.23A
CEC WEIGHTED EFFICIENCY 96.5%96.5%96.5%
MAX NO OF
MICROINVERTERS/BRANCH 3 6 13
MAX DC VOLTAGE 60V 60V 60V
NOTE(N):
*NO LINE SIDE TAPS.
*SOLAR DISCONNECT IS PREFERRED TO BE 5' FROM THE METER
UNLESS PERMISSION IS GRANTED.
5' MAX
NOTE(N):
1.EACH HOYMILES HM-1200N (240V) IS CONNECTED TO 4 MODULES.
2.EACH HOYMILES HM-600N (240V) IS CONNECTED TO 2 MODULES.
3.EACH HOYMILES HM-300N (240V) IS CONNECTED TO 1 MODULE.
(16)SILFAB SIL-400NU (400W) MODULES WITH,
(2)HOYMILES HM-1200N (240V) MICROINVERTERS.
(3)HOYMILES HM-600N (240V) MICROINVERTERS.
(2)HOYMILES HM-300N (240V) MICROINVERTERS.
ELECTRICAL CALCULATIONS
CUSTOMER INFORMATION
NAME:DANNY BRICKY
DATE:11/7/2023
SCALE:AS NOTED REV:B
AHJ:AR-CITY OF LITTLE ROCK
PRN NUMBER:SNS-85385
DRAFTED BY:
C.KOWSALYA
QC'ED BY:ABU.S
PAPER SIZE:17"X11"
UTILITY:ENTERGY(AR)
ADDRESS:1402 COMMERCE ST, LITTLE
ROCK, AR 72202
34.734565, -92.268403
APN: 34L0200314300
LICENSE NUMBER: 2020012960
ELECTRICAL CALCULATIONS
E-02
CONDUIT SCHEDULE
TAG ID CONDUIT SIZE CONDUCTOR NEUTRAL GROUND
1 FREE AIR (2) 12 AWG AC END CABLE
PER BRANCH CIRCUIT NONE (1) 12 AWG BARE COPPER
1A FREE AIR (2) 12/2 ROMEX WIRE
2 1"EMT (4) 10 AWG THHN/THWN-2 NONE (1) 10 AWG THHN/THWN-2
3 1"EMT (2) 6 AWG THHN/THWN-2 (1) 6 AWG THHN/THWN-2 (1) 6 AWG THHN/THWN-2
ELECTRICAL NOTES
1.CONDUCTORS EXPOSED TO WET
LOCATIONS SHALL BE SUITABLE FOR
USE IN WET LOCATIONS PER NEC
310.10(C).
2.CONDUCTORS EXPOSED TO SUNLIGHT
SHALL BE LISTED AS SUNLIGHT
RESISTANT PER NEC 310.10(D).
3.MAXIMUM DC/AC VOLTAGE DROP SHALL
BE NO MORE THAN 3%.
4.ALL CONDUCTORS SHALL BE IN
CONDUIT UNLESS OTHERWISE NOTED.
5.BREAKER/FUSES SIZED ACCORDING
PER NEC ARTICLE 240.
6.AC GROUNDING ELECTRODE
CONDUCTOR (GEC) SIZED PER NEC
250.66.
7.EQUIPMENT GROUNDING CONDUCTOR
(EGC) SIZED PER NEC 250.122.
8.AMBIENT TEMPERATURE ADJUSTMENT
FACTOR IS BASED ON
TABLE NEC 310.15(B)(1).
9.CURRENT CARRYING CONDUCTOR
ADJUSTMENT FACTOR IS BASED ON NEC
310.15(C)(1).
10.MAX. SYSTEM VOLTAGE CORRECTION
IS PER NEC 690.7.
11.CONDUCTORS ARE SIZED PER NEC
310.16.
NOTE(N):
MAIN PANEL RATING:200A, MAIN BREAKER RATING:200A
120% RULE: (200AX1.2)-200A=40A =<ALLOWABLE BACKFEED IS 40A
OCPD CALCULATIONS:
INVERTER OVERCURRENT PROTECTION=
INVERTER O/P I X CONTINUOUS LOAD(1.25)X #OF INVERTERS
=(5x1.25x2)+(2.46X1.25X3)+(1.23*1.25*2)=24.80 A =PV BREAKER = 30A
ALLOWABLE BACKFEED 40A =>30A PV BREAKER
THE DESIGNED INTERCONNECTION MEETS THE 705.12(B)(3)(2) REQUIREMENTS.
AC WIRE SIZING CALCULATIONS BASED ON THE FOLLOWING EQUATIONS >>
REQUIRED CONDUCTOR AMPACITY:
INVERTER OUTPUT CURRENT * #OF INVERTERS = MAX CURRENT PER 690.8(A)(1)(e)* 125%
= MAX CURRENT PER 690.8(B)(1)
CORRECTED AMPACITY CALCULATIONS:
DERATED CONDUCTOR AMPACITY PER 690.8(B)(2) = AMPACITY * TEMPERATURE DERATE FACTOR *
CONDUIT FILL DERATE
DERATED CONDUCTOR AMPACITY CHECK: MAX CURRENT PER 690.8(B)(1) <DERATED
CONDUCTOR AMPACITY
AC WIRE CALCULATIONS:- MATERIAL:COPPER, ALUMINUM & TEMPERATURE RATING:90°C
TAG ID REQUIRED CONDUCTOR AMPACITY CORRECTED AMPACITY CALCULATION DERATED CONDUCTOR
AMPACITY CHECK
1
5 X 2 =10.00
=11.23 X 1.25 =14.04A 30 X 0.91 X 1 =27.30A 14.04A <27.30A+
1.23 X 1 =1.23
2
5 X 2 =10.00
=11.23 X 1.25 =14.04A 40 X 0.91 X 0.8 =29.12A 14.04A <29.12A+
1.23 X 1 =1.23
3
5 X 2 =10.00
=19.84 X 1.25 =24.80A 75 X 0.91 X 1 =68.25A 24.80A <68.25A
+
2.46 X 3 =7.38
+
1.23 X 2 =2.46
CIRCUIT MAP
CUSTOMER INFORMATION
NAME:DANNY BRICKY
DATE:11/7/2023
SCALE:AS NOTED REV:B
AHJ:AR-CITY OF LITTLE ROCK
PRN NUMBER:SNS-85385
DRAFTED BY:
C.KOWSALYA
QC'ED BY:ABU.S
PAPER SIZE:17"X11"
UTILITY:ENTERGY(AR)
ADDRESS:1402 COMMERCE ST, LITTLE
ROCK, AR 72202
34.734565, -92.268403
APN: 34L0200314300
CIRCUIT MAP
PL-01
LICENSE NUMBER: 2020012960
STRING CONFIGURATION
BRANCH DETAILS
9 MODULES STRING 1
7 MODULES STRING 2
WARNING PLACARD
CUSTOMER INFORMATION
NAME:DANNY BRICKY
DATE:11/7/2023
SCALE:AS NOTED REV:B
AHJ:AR-CITY OF LITTLE ROCK
PRN NUMBER:SNS-85385
DRAFTED BY:
C.KOWSALYA
QC'ED BY:ABU.S
PAPER SIZE:17"X11"
UTILITY:ENTERGY(AR)
ADDRESS:1402 COMMERCE ST, LITTLE
ROCK, AR 72202
34.734565, -92.268403
APN: 34L0200314300
WARNING PLACARDS
PL-02
LICENSE NUMBER: 2020012960
POWER TO THIS BUILDING IS ALSO
SUPPLIED FROM THE FOLLOWING
SOURCES WITH DISCONNECTS LOCATED
AS SHOWN
1402 COMMERCE ST, LITTLE ROCK, AR 72202
SYSTEM UTILIZES MICROINVERTERS LOCATED UNDER SOLAR MODULE
CAUTION: SOLAR ELECTRIC
SYSTEM CONNECTED
ELECTRIC SHOCK HAZARD
IF GROUND FAULT IS INDICATED ALL NORMALLY
GROUNDED CONDUCTORSMAY BE UNGROUNDED
AND MAY BE ENERGIZED
ELECTRIC SHOCK HAZARD
TERMINALS ON BOTH LINE AND LOAD SIDES
MAY BE ENERGIZED IN THE OPEN POSITION
WARNING
LABEL LOCATION
AC DISCONNECT,POINT OF INTERCONNECTION
[PER CODE: NEC 690.13(B)]
LABEL LOCATION
WEATHER RESISTANT MATERIAL, DURABLE
ADHESIVE, UL969 AS STANDARD TO WEATHER
RATING (UL LISTING OF MARKINGS NOT
REQUIRED), MIN 38 " LETTER HEIGHT AERIAL OR
SIMILAR FONT NON-BOLD,PLACED WITHIN THE
MAIN SERVICE DISCONNECT,PLACED ON THE
OUTSIDE OF THE COVER WHEN DISCONNECT IS
OPERATED WITH THE SERVICE PANEL CLOSED.
!
AC JUNCTION BOX FOR
PHOTOVOLTAIC
CIRCUIT
PHOTOVOLTAIC SYSTEM LOAD CENTER
DO NOT ADD LOADS
LABEL LOCATION
LOAD CENTER
[PER CODE: NEC 690.4(B)]
INVERTER OUTPUT CONNECTION
DO NOT RELOCATE THIS
OVERCURRENT DEVICE
INVERTER OUTPUT CIRCUIT
LABEL LOCATION
ADJACENT TO PV BREAKER
[PER CODE: 705.12(B)(3)(2)]
PHOTOVOLTAIC
SOLAR BREAKER
TURN OFF PHOTOVOLTAIC AC DISCONNECT
PRIOR TO WORKING INSIDE PANEL
LABEL LOCATION:
MAIN SERVICE PANEL
[PER CODE: NEC 110.27(C)]
WARNING!
WARNING!
WARNING!
WARNING!
WARNING!
CAUTION
SOLAR POINT OF CONNECTION
DUAL POWER SUPPLY
SOURCES: UTILITY GRID AND
PV SOLAR ELECTRIC SYSTEM
LABEL LOCATION
[PER CODE: NEC 705.12(C)]
WARNING!
TURN OFF PHOTOVOLTAIC AC DISCONNECT
PRIOR TO WORKING INSIDE PANEL
LABEL LOCATION
AC DISCONNECT , POINT OF INTERCONNECTION
[PER CODE: NEC 690.54]
RATED AC OPERATING CURRENT
AC NOMINAL OPERATING VOLTAGE
19.84
240
AMPS AC
VAC
PHOTOVOLTAIC SYSTEM AC DISCONNECT SWITCH
!!CAUTION:MULTIPLE SOURCES
OF POWER
LABEL LOCATION
SERVICE PANEL
PER CODE: NEC 705.101.PLACARDS SHALL MEET THE
REQUIREMENTS OF ARTICLES 690 AND
705, UNLESS OTHERWISE SPECIFIED
PER LOCAL AHJ REQUIREMENTS.
2.PLACARDS SHALL MEET THE
REQUIREMENTS OF SECTION 110.21(B)
AS REQUIRED AND SHALL COMPLY WITH
ANSI Z535.4-2011, PRODUCT SAFETY
SIGNS AND LABELS.
3.PLACARDS SHALL BE PERMANENTLY
AFFIXED TO THE EQUIPMENT OR WIRING
METHOD.
4.PLACARDS SHALL BE OF SUFFICIENT
DURABILITY TO WITHSTAND THE
ENVIRONMENT INVOLVED AND SHALL BE
HANDWRITTEN.
5.PLACARDS SHALL NOT COVER
EXISTING MANUFACTURER LABELS.
NOTES(N)
TURN RAPID SHUTDOWN
SWITCH TO THE
"OFF" POSITION TO
SHUT DOWN PV SYSTEM
AND REDUCE
SHOCK HAZARD
IN THE ARRAY
SOLAR ELECTRICPV PANELS
SOLAR PV SYSTEM EQUIPPED
WITH RAPID SHUTDOWN
INSTALLED ON: WITHIN 3 FT OF SERVICE
DISCONNECTING MEANS. MIN 3/8" BLACK TEXT ON
YELLOW BACKGROUND & 3/16" BLACK TEXT ON WHITE
BACKGROUND.
APPLICABLE CODE(S): NEC 690.56(C)
RAPID SHUTDOWN
SWITCH FOR SOLAR PV
SYSTEM
INSTALLED ON: MAIN SERVICE PANEL. REFLECTIVE.
MIN 3/8" WHITE TEXT ON RED BACKGROUND.
APPLICABLE CODE(S): NEC 690.56(C)(2)
PHOTOVOLTAIC ARRAY
ON THE ROOF
(E) UTILITY METER WITH MAIN SERVICE PANEL (EXTERIOR)
(N) PV AC DISCONNECT (EXTERIOR)
(N) LOAD CENTER (EXTERIOR)
(E) MAIN LUG PANEL (INTERIOR)
SPEC SHEET
CUSTOMER INFORMATION
NAME:DANNY BRICKY
DATE:11/7/2023
SCALE:AS NOTED REV:B
AHJ:AR-CITY OF LITTLE ROCK
PRN NUMBER:SNS-85385
DRAFTED BY:
C.KOWSALYA
QC'ED BY:ABU.S
PAPER SIZE:17"X11"
UTILITY:ENTERGY(AR)
ADDRESS:1402 COMMERCE ST, LITTLE
ROCK, AR 72202
34.734565, -92.268403
APN: 34L0200314300
MODULE SPEC SHEET
SS-01
LICENSE NUMBER: 2020012960
SPEC SHEET
CUSTOMER INFORMATION
NAME:DANNY BRICKY
DATE:11/7/2023
SCALE:AS NOTED REV:B
AHJ:AR-CITY OF LITTLE ROCK
PRN NUMBER:SNS-85385
DRAFTED BY:
C.KOWSALYA
QC'ED BY:ABU.S
PAPER SIZE:17"X11"
UTILITY:ENTERGY(AR)
ADDRESS:1402 COMMERCE ST, LITTLE
ROCK, AR 72202
34.734565, -92.268403
APN: 34L0200314300
INVERTER-1 SPEC SHEET
SS-02
LICENSE NUMBER: 2020012960
SPEC SHEET
CUSTOMER INFORMATION
NAME:DANNY BRICKY
DATE:11/7/2023
SCALE:AS NOTED REV:B
AHJ:AR-CITY OF LITTLE ROCK
PRN NUMBER:SNS-85385
DRAFTED BY:
C.KOWSALYA
QC'ED BY:ABU.S
PAPER SIZE:17"X11"
UTILITY:ENTERGY(AR)
ADDRESS:1402 COMMERCE ST, LITTLE
ROCK, AR 72202
34.734565, -92.268403
APN: 34L0200314300
INVERTER-2 SPEC SHEET
SS-03
LICENSE NUMBER: 2020012960
SPEC SHEET
CUSTOMER INFORMATION
NAME:DANNY BRICKY
DATE:11/7/2023
SCALE:AS NOTED REV:B
AHJ:AR-CITY OF LITTLE ROCK
PRN NUMBER:SNS-85385
DRAFTED BY:
C.KOWSALYA
QC'ED BY:ABU.S
PAPER SIZE:17"X11"
UTILITY:ENTERGY(AR)
ADDRESS:1402 COMMERCE ST, LITTLE
ROCK, AR 72202
34.734565, -92.268403
APN: 34L0200314300
INVERTER-3 SPEC SHEET
SS-04
LICENSE NUMBER: 2020012960
SPEC SHEET
CUSTOMER INFORMATION
NAME:DANNY BRICKY
DATE:11/7/2023
SCALE:AS NOTED REV:B
AHJ:AR-CITY OF LITTLE ROCK
PRN NUMBER:SNS-85385
DRAFTED BY:
C.KOWSALYA
QC'ED BY:ABU.S
PAPER SIZE:17"X11"
UTILITY:ENTERGY(AR)
ADDRESS:1402 COMMERCE ST, LITTLE
ROCK, AR 72202
34.734565, -92.268403
APN: 34L0200314300
AC DISCONNECT SPEC
SHEET
SS-05
LICENSE NUMBER: 2020012960
SPEC SHEET
CUSTOMER INFORMATION
NAME:DANNY BRICKY
DATE:11/7/2023
SCALE:AS NOTED REV:B
AHJ:AR-CITY OF LITTLE ROCK
PRN NUMBER:SNS-85385
DRAFTED BY:
C.KOWSALYA
QC'ED BY:ABU.S
PAPER SIZE:17"X11"
UTILITY:ENTERGY(AR)
ADDRESS:1402 COMMERCE ST, LITTLE
ROCK, AR 72202
34.734565, -92.268403
APN: 34L0200314300
MOUNT SPEC SHEET
SS-06
LICENSE NUMBER: 2020012960
SPEC SHEET
CUSTOMER INFORMATION
NAME:DANNY BRICKY
DATE:11/7/2023
SCALE:AS NOTED REV:B
AHJ:AR-CITY OF LITTLE ROCK
PRN NUMBER:SNS-85385
DRAFTED BY:
C.KOWSALYA
QC'ED BY:ABU.S
PAPER SIZE:17"X11"
UTILITY:ENTERGY(AR)
ADDRESS:1402 COMMERCE ST, LITTLE
ROCK, AR 72202
34.734565, -92.268403
APN: 34L0200314300
RAIL SPEC SHEET
SS-07
LICENSE NUMBER: 2020012960
SPEC SHEET
CUSTOMER INFORMATION
NAME:DANNY BRICKY
DATE:11/7/2023
SCALE:AS NOTED REV:B
AHJ:AR-CITY OF LITTLE ROCK
PRN NUMBER:SNS-85385
DRAFTED BY:
C.KOWSALYA
QC'ED BY:ABU.S
PAPER SIZE:17"X11"
UTILITY:ENTERGY(AR)
ADDRESS:1402 COMMERCE ST, LITTLE
ROCK, AR 72202
34.734565, -92.268403
APN: 34L0200314300
LOAD CENTER SPEC SHEET
SS-08
LICENSE NUMBER: 2020012960