HomeMy WebLinkAboutZ-6938-A Map 4MULTI -SECTOR
ROOF FRAME
TRAY SPLICE PER
MANUFACTURER
RECOMMENDATIONS
EXISTING CMU
PENTHOUSE WALL
COAX. CABLE ROUTED ALONG WALL IN APPROVED CABLE
TRAY (WITH COVER) AND 90 DEGREE SWEEPING BEND
SECTION AT TOP, SECURE TRAY TO WALL WITH PAIRS
OF EXP. ANCHORS @ 4'-0" O.C. MAX.
SITE
SUPPORT
(EXTRATALK)
CITYTALK
BASIC
(6 TRX's)
CITY TALK
EXTENSION
(6 TRX's)
CITY TALK
EXTENSION
(6 TRX's)
DOUBLE ROOF
CABINET
EXTENSION CABINET
SITE SUPPORT CABINET
WIDTH
30.3 IN
30.3 IN
30.3 IN
2 SECTION A -A
C-9 SCALE: NTS
COAX ENTRY PORT
PARAPET
INSTALLATION REQUIREMENTS
CONFIGURATION
CITYTALK BASIC
CITYTALK
EXIRATALK AC/DC
DOUBLE ROOF
CABINET
EXTENSION CABINET
SITE SUPPORT CABINET
WIDTH
30.3 IN
30.3 IN
30.3 IN
DEPTH WITH HEAT EXCHANGER
34.7 IN
34.7 IN
COB - 28 KG (61.7 LBS)
DEPTH WITH AIR CONDITIONER
43.7 IN
43.7 IN
43.7 IN
CABINET WEIGHT WITHOUT UNITS, DOORS,
ROOF, HEAT EXCHANGER, OR AIR
224.9 LBS
198.5 LBS
180.8 LBS
CONDITIONER
MAXIMUM OPERATION WEIGHT WITH
630.6 LBS
582.1 LBS
AFX'S AND AIR CONDITIONER
MAXIMUM OPERATION WEIGHT WITH
767.2 LBS
718.7 LBS
882.0 LBS
AFX'S AND AIR CONDITIONER (CITYTALK+)
MAXIMUM OPERATION WEIGHT WITH
604.2 LBS
595.4 LBS
RTCs AND HEAT EXCHANGER
MAXIMUM OPERATION WEIGHT WITH RTCs AND
HEAT EXCHANGER (CITYTALK+)
727.2 LBS
721.0 LBS
MAXIMUM FLOOR LOAD
< 1000 kg/m2 (204.8 LBS/FT2)
WEIGHTS
NOKIA CITYTALK CABINET COMPONENTS
COMPONENT
WEIGHT
SINGLE ROOF
11 KG (24.3 LBS)
DOUBLE ROOF
20 KG (44.1 LBS)
r FRONT DOOR
16 KG (35.3 LBS)
HEAT EXCHANGER
45 KG (99.3 LBS)
AIR CONDITIONER
102 KG (224.9 LBS)
AIC - 65 KG (143.3 LBS)
COB - 28 KG (61.7 LBS)
ASSEMBLY PLATE - 9 KG (19.8 LBS)
3 CABINET SPECIFICATIONS
PROCEDURE FOR SWEEP TESTING
TO BE ATTACHED AND PROVIDED BY OTHER. CHECK WITH PROJECT MANAGER FOR
ADDITIONAL INFORMATION ON RF SWEEP PROCEDURE.
COAXIAL EQUIPMENT ENTRY
TO BE ATTACHED AND PROVIDED BY OTHER. CHECK WITH PROJECT MANAGER FOR
ADDITONAL INFORMATION ON RF SWEEP PROCEDURE.
CarteroBurgess
CARTER & BURGESS, INC.
Brookfield Corporate Center
201 Brookfield Parkway
Suite 200
Greenville, S.C. 29607
(864) 329-8500
.........................
/ III ASATE op
_
ARIeAS
PRO, $ I N
9y N0. 0534 oime
-�.......� �n Z�-01
.........................
�� �F,A•UTyo :,
:v
>
Ho 68zv
0.0
.........................
LU
~ cn
F- w
a Zwu-)
pw Wo
.O �IIesse C-4
�ti 04 H
wQaa��
W 0
w a
U, wMOcn
U) � Q
H
OCl) Luj
LU J
Isss.I:
N'k
0 QTS
J r
in (L �O
C&B JOB NUMBER:
350099.071.1
DATE ISSUED:
10/16/02
INITIAL ISSUE
ISSUES/REVISIONS:
A ISSUE FOR REVIEW 10/10/02
0 INITIAL ISSUE 10/16/02
1 REVISED PER 10/23/02
OWNER COMMENTS
SHEET CONTENTS:
EQUIPMENT
INFORMATION
AND LAYOUT
SHEET NUMBER:
C-3
v1.0 COPYRIGHT®2002 by Carter & Burgess, Inc
wdozst9NlevoI-d110-M-M