HomeMy WebLinkAboutZ-6659 Map 7M
-RICAL SPECIFICATIONS
1. General
Box
All electrical work shall
be performed
in accordance with local, state and national codes
and standards, including
but not limited
to:
no. PG2436CA00 with telephone logo
* The National Electrical
Code (NFPA
70 -
latest edition)
* The National Electrical
Safety Code
(ANSI
C-2, latest edition)
* The Life Safety Code
(NFPA 101 -
latest
edition)
2. Conduit
2" Rigid galvanized schedule 40 conduit shall be used for exterior installation
2" EMT with compression type fittings shall be used for interior installation
4" PVC schedule 40 (check with respective utility companies to insure conformance with
local requirements) shall be used for direct burial only.
Reduced type and size of conduit for entry into panels will be specified on drawings.
3. Wiring
Feeders
Minimum size conductors shall be #1/0 or #3/0 (based on required amperage) type THWN,
THW, or XHHW with no reduction in the neutral conductor. Minimum size grounding
conductor shall be #2 AWG. The electrical engineer shall be responsible for performing
voltage drop calculations and sizing feeders accordingly.
Sub -feeders
Minimum size conductors for 100 amp sub -feed shall be #3 AWG with no reduction in the
neutral conductor. Minimum size grounding conductor shall be #2 AWG.
Branch Circuits
Minimum wire size #12 AWG THHN or THWN. All branch circuits shall carry a full size
ground conductor; conduits shall not be used as a grounding conductor. A separate neutral
shall be run for each branch circuit. All branch wiring shall be installed in a raceway; no
romex or bx type wiring shall be permitted.
Terminations
All conductor lug/terminations shall have anti -oxidant applied
All spring type wire connectors used in exterior boxes will be silicone filled.
All terminations requiring flexible connections shall be done in 1" liquid tight metal conduit.
4. Metering
All sub -meters will be of the Watt -watcher odometer type. The local utility company shall
meter all new service.
5. Junction Boxes
All outlet and junction boxes shall be 4" square minimum
6. A/C Power Distribution
Panel boards will be Square D or General Electric. All panels shall have copper bus
components; no aluminum components will be accepted. They will be main breaker type,
with an isolated neutral and have a full size equipment ground bar.
A 150 -amp main distribution panel shall be provided with the following characteristics:
208/240 VAC, single phase, 4 wire, 12 conduit (20 space), with NEMA 3R locking enclosure.
Branch circuits will be numbered and labeled on inside access panel.
Fusible Disconnect
A Square D or General Electric service rated fusible disconnect switch with the following
characteristics will be used:
150A (125A fused)
208/240 VAC
1 phase
22,000 AIC rated
7. Lighting
Exterior lighting: Day -Brite #11W -150-G; 120V Glass and metal cage waterproof fixture
with 100 watt bulb.
Interior lighting: General Electric or Sylvania; 120V, 4'-2 Lamp surface mounted fixtures
with wrap around acrylic lenses
8. Keyed Switches
20A, 120 VAC Hart Arrow # 1 191 LGRY with 7420 plate. 2000 series key.
TELCO REQUIREMENTS
1. Conduit
1 1/4!' rigid galvanized steel; schedule 40 shall be used for all exterior installation.
1 1/4" EMT with setscrew type fittings shall be used for all interior installation.
4' PVC schedule 40 (minimum) shall be used for all direct burial (check with respective
Telephone Company to insure conformance with local requirements).
1" liquid tight flexible metal conduit shall be provided from the telco box to the equipment
cabinet for rooftop installations. 1" PVC conduit shall be provided from the telco box below
grade to the equipment cabinet for cabinet on grade installation.
Nylon bond bushings shall be provided at all open ends of conduits to protect nicking/cutting
of telco cable.
Nylon pull strings will be provided in all telco conduits.
2. Telco Cable
One (1) - 4 pair, 24 gauge, separately shielded copper conductors for the receive side of the
T-1 span shall be installed. Ore (1) - 6 pair, 24 gauge, separately shielded, copper conductor
for the transmit side of the T-1 span shall be installed.
15 ft. of telco cable will be newly coiled and secured at the T-1 end of the conduit for
installation use by the local Telephone Company. The cable shall be clearly tagged to identify
ownership by Telecorp.
3. Telco Box
A Hoffman 36% 30% 12" NEMA 4R rated telco box shall be installed unless local telephone
company requirements differ. (Check with respective telco jurisdiction before installation).
For interior telco box installation a 4'x 4'x 3/4', plywood backboard will be installed.
4. Service
Box
38 x 26
x 24
Quasite composite service box (part
no. PG2436BB24) include locking cover
with logo
(part
no. PG2436CA00 with telephone logo
#43)
5. Cabinet on Rooftop
Telephone service shall be run in 11/4" conduit from the existing building MPOP and
terminated in a weatherproof telco box mounted on the panel backboard, which is mounted
to the equipment platform. The telco box shall have a dedicated duplex receptacle and
telephone smart jack mounted inside. A 1" liquid tight flexible metal conduit shall be provided
from the telco box to the equipment cabinet for telephone service.
GROUNDING
1. Ground Bars
Main Ground Bar
Harger (or equal) 1/4" x 4' x 20" copper ground bar, 27 pre -drilled 7/16" holes with
insulators and brackets (part no. GBI14420C).
Sector Bus Bar
Harger (or equal) 1/4" x 2" x 15" copper ground bar, 24 pre -drilled 7/16" holes with
insulators and brackets (part no. GBI14215TES).
2. Grounding Wire
All ground wire will be #2 stranded and green insulated with the exception of the home run.
The home run will be #2/0 up to 500 ft. After 500 ft. it will increase to #4/0.
3. Grounding Lugs
With the exception of the grounding kits, all lugs will be long barrel compression lugs, with
3/8" holes.
All lugs shall be double crimped.
4. Grounding Kits
All ground kits shall be Cablewave with 2 -hole crimp -on lug and 3 ft. tails.
All lugs will be double crimped.
5. Ground Rods
Ground Rods shall be Harger (or equal) 5/8" x 10' copper -clad steel.
In cases where sufficiently low ground resistance cannot be attained such as driving deeper
rods, XIT or Chem -rod chemical rods shall be used.
6. Grounding Clamps
Two clamps will be provided for grounding to the water main on rooftop sites. T&B and
SEPCO clamps (or approved equal) shall be used.
7. Compression Taps
C -Type copper compression taps shall be used when connecting copper conductors.
Compression taps will be applied using a mechanical crimping tool.
Aluminum taps will not be accepted.
8. Resistance
All terminations shall be grounded to an approved main ground source (i.e. water main,
ground ring) with a maximum resistance of 5 ohms.
9. Connections
A good connection insures that the ground conductor connection point is clean and free
from oxidation. The two must meet bare metal to bare metal with a protective coating of
NO -OX (or equal) to prevent future oxidation. All connecting hardware shall be secured
tight to prevent loosening due to mechanical or chemical reaction.
10. Bolted Connections
Properly removed paint, clean and apply an anti -oxidant to all mating surfaces when using
lug type bolt connections. Use proper size bolts and compression fittings for all mechanical
type connections. All connection hardware shall be stainless steel. All fasteners should be
of the bolt, nut and self-locking washer type (self -tapping screws shall not be used).
11. Exothermic Welds (Cadwelds)
All conductors/surfaces to be exothermically welded shall be clean and dry to insure proper
bonding of materials. All ground connections to antenna masts, antenna skids, fence posts,
panel backboards, ice bridge post, platforms, and monopoles shall be exothermically welded.
All above ground welds shall be parallel type. Below grade welds (i.e. ground ring) shall be
T or X type connections.
All welds shall be clean and complete.
Welds shall receive an approved zinc cold galvanizing application.
12. Coax Cable Grounding
The sector bus bar will be attached to the Ice Bridge with standoff brackets and insulators.
Each antenna sector shall have a sector ground bus that is grounded to the main bus bar via
#2 stranded, green insulated wire. The ground wire from the sector bus to the main will be
run parallel to the ice bridge with attachments to the sleepers utilizing nylon straps with
eyelets for bolt, self-locking washers and nut.
Grounding kits shall be installed within 10' of the antenna. Additional ground kits will be
installed for every 200' of cable.
900 S. SHACKLEFORD
SUITE 600
LITTLE ROCK, AR 72211
OFFICE- (501) 312-2455
4A
GEM ENGINEERING COMPi
10970 Standiff
Houston, Texas 77099-4206
Phone(281) 561-9225
Fax (281) 561-9399
PROJECT NON LTR002B
DRAWN BY- GVS
CHECKED BY- TA/HM
SUBMITTALS
DATE DESCRIPTION REV.
4-29-98 PERMIT
ARKANSASIN
REGIST, RED
QFII I
¢fa�1Rpoo9e, zR•48 osri�iril
SCALES
0 1/2 1 2
1 ii 1 i 1
GRAPHIC SCALE IN INCHES
LTRO02B
CI Iir���il;T
600 INTERSTATE 30
LITTLE ROCK, AR 72202
SHEET TITLE
ELECTRICAL
SPECIFICATIONS
SHEET NUMBER
SHEET 6 OF 6 SHEETS