ol ONE LINE DIAGRAM
I SCALE: N.T.S.
LIQUID TIGHT FLEXIBLE
CONDUIT (IF REQUIRED)
CONDUIT BODY
CONCRETE PAD
(SHOWN) OR
PLATFORM
RIGID STEEL
CONDUIT /— R=24" MIN.
PVC SCHEDULE 40 SIZE
AS SHOWN ON LAYOUTS
►� CONDUIT DETAIL
%J SCALE: N.T.S.
*DETAIL PROVIDED BY OWNER*
2'-0"
TRENCH
FROM POWER SOURCE
(3) #3/0, (1) #6G, 2" CONDUIT M
JPR
(120/240V, 10, 3W).
TI '=' UNDISTURBED SOIL
0 9/11/14 CONST ISSUE
(3) #3/0 2" CONDUIT
_:
:
� lli•��
T
1O
200A METER TO BE FURNISHED
_ - _.I COMPACTED BACKFILL PER
---1 EARTHWORK SPECIFICATIONS
BY UTILITY COMPANY AND
UTILITY WARNING TAPE,
!
INSTALLED BY CONTRACTOR
J2 INSULATED COPPER
.
I ��
FUSIBLE SAFETY SWITCH 2O0A, 2P,
GROUND WIRE I
1
S/N TO BE FURNISHED BY
PIONEER CELLULAR AND INSTALLED
J
J
BY CONTRACTOR
- —
— J
(3) #3/0, (1) #6G, 2" CONDUIT
250A GENERATOR RECEPTACLE -
200A PPC, TO BE FURNISHED BY
(FURNISHED WITH PPC)
PIONEER CELLULAR AND INSTALLED
BY CONTRACTOR
F — —
� t �
NOTES:
1. ALL ELECTRICAL WORK SHALL CONFORM
TO REQUIREMENTS OF THE NATIONAL
ELECTRICAL CODE AS A MINIMUM
I
STANDARD.
1
I
2. ALL ABOVE GROUND CONDUIT SHALL BE
RIGID GALVANIZED STEEL (RGS) UNLESS
OTHERWISE INDICTED.
3. ALL UNDERGROUND CONDUIT SHALL BE
SCH, 40 PVC UNLESS OTHERWISE
INDICATED OR AS REQUIRED BE LOCAL
1
UTILITY COMPANY, ALL UNDERGROUND
J-.. — — — —
— — — J
ELBOWS SHALL BE SWEEPING BENDS.
ol ONE LINE DIAGRAM
I SCALE: N.T.S.
LIQUID TIGHT FLEXIBLE
CONDUIT (IF REQUIRED)
CONDUIT BODY
CONCRETE PAD
(SHOWN) OR
PLATFORM
RIGID STEEL
CONDUIT /— R=24" MIN.
PVC SCHEDULE 40 SIZE
AS SHOWN ON LAYOUTS
►� CONDUIT DETAIL
%J SCALE: N.T.S.
*DETAIL PROVIDED BY OWNER*
2'-0"
TRENCH
I^I I
I� 1 2" PVC ELECTRICAL CONDUIT.
T: t •ffi COORDINATE SIZE AND
2" PVC TELCO CONDUIT. INSTALLATION WITH POWER
COMPANY
COORDINATE INSTALLATION' -0"
WITH TELEPHONE COMPANY MI1N. OR
AS REQUIRED
BY POWER
COMPANY
t) TRENCH DETAIL
SCALE: N.T.S.
PROPOSED 2" RAJNT10HT
EMT ANCHORED TO SIDE
OF CONCRETE PAD WITH
A DOUBLE PIPE CLAMP
ABOVE GRADE
A CONDUIT ATTACHMENT DETAIL
'• SCALE: N.T.S.
T • •111rIoY����•
12980 FOSTER, SUITE 200
OVERLAND PARK, KS 66213
�TOWER ENGINEERING ONS
6445 FREEPORT PARKWAY,
SUITE 375
IRVING, TX 75063
PHONE: (972) 635-8238
CDA / 2705 EXP. 12/31/2015
BY:
COMMON/04770N3.LLC
BRANCH COMMUNICATIONS
1516 S BOSTON AVE SIE 215
TULSA, OKLAHOMA 74119
(910) 949-4551
I WEST LITTLE ROCK
AR01218_A
SITE ADDRESS:
2525 JOHN BARROW RD
LITTLE ROCK_AR-32294_
No. 7784 *♦dam
t
PE / 7784 EXP. 12/31/2014
NO DATE DESCRIPTION
BY
FINISHED GRADE
JPR
�-I i� ± I� f
TI '=' UNDISTURBED SOIL
0 9/11/14 CONST ISSUE
- i=L- L—
—Q ,fir:.=::;_;..<�,
_:
:
� lli•��
T
1O
I IlW
2i1
_ - _.I COMPACTED BACKFILL PER
---1 EARTHWORK SPECIFICATIONS
UTILITY WARNING TAPE,
SHEET q:
E2
12" MIN. DEPTH
I^I I
I� 1 2" PVC ELECTRICAL CONDUIT.
T: t •ffi COORDINATE SIZE AND
2" PVC TELCO CONDUIT. INSTALLATION WITH POWER
COMPANY
COORDINATE INSTALLATION' -0"
WITH TELEPHONE COMPANY MI1N. OR
AS REQUIRED
BY POWER
COMPANY
t) TRENCH DETAIL
SCALE: N.T.S.
PROPOSED 2" RAJNT10HT
EMT ANCHORED TO SIDE
OF CONCRETE PAD WITH
A DOUBLE PIPE CLAMP
ABOVE GRADE
A CONDUIT ATTACHMENT DETAIL
'• SCALE: N.T.S.
T • •111rIoY����•
12980 FOSTER, SUITE 200
OVERLAND PARK, KS 66213
�TOWER ENGINEERING ONS
6445 FREEPORT PARKWAY,
SUITE 375
IRVING, TX 75063
PHONE: (972) 635-8238
CDA / 2705 EXP. 12/31/2015
BY:
COMMON/04770N3.LLC
BRANCH COMMUNICATIONS
1516 S BOSTON AVE SIE 215
TULSA, OKLAHOMA 74119
(910) 949-4551
I WEST LITTLE ROCK
AR01218_A
SITE ADDRESS:
2525 JOHN BARROW RD
LITTLE ROCK_AR-32294_
No. 7784 *♦dam
t
PE / 7784 EXP. 12/31/2014
NO DATE DESCRIPTION
BY
A B 13 14 PRELIM ISSUE
JPR
B 9/10/14 PRELIM ISSUE
NDP
0 9/11/14 CONST ISSUE
NDP
SHEET TITLE:
ELECTRICAL
DETAILS
SHEET q:
E2
PROJECT 0:
AR01218. A
.
JWM
CKO:
JWM
u` so• oo-
MIIJ': r•�D'
BAsrs nF REAR$f�'i
rOETrr am ro 6rFi'd
N 1/1 Sr ,/A SP T/p. SECTION 11, rDINS7NF + NORra. rANCr 1] 1657 CONrADrrNC M AMC NOES OR
AND ALL 01NER IXISRh'C MCMr-Or-EATAr rm FOAO.S AND/OR 3fRdm. MD)rAT[O OR cT £ WE= AKO 7D ANY
R 110
���ltfA0
rNi GOPCUGDPC+7L As CYl1I!'S 0117CCs. FOJAs1V L'OONUl
1T AkrANSAS LrM fN S 1NIt.
Y O►NSNlP 1 NORTH- BOOK 844' PAGN RANOr
ra ASST AND AXW YORE PART7C0.[ ALA DISC
A8 fOLL01Y;
LONNrNOr AT A r' CRfNF PlPX MOND A' PhW4 AT WE NORWITST CMWBR OF LOT I. DLOCr ,, SANDON
ADDI77ON: THENCE N m-or.Ta' N A D7SrANCi Of OTr.T+ FAST TO A 6/6- RELW Si! fSNIJ AND "M FOINT
OF rrCINNO,6; TRENCa N DT'r6'0Y r A DMANB OF 60.00 r"T TO A 6/a' AMR Err (SNI); TNSNCC S
A9V1'6T' E A AtEANC$ "T 00,00 FEAT TO A $A' RraAR SET (SNF)'-TNENCr S 0A'16'DY ■ A DISTAMCi
Or
Or 7rr to A , ADOM r laxl : PARM�+ CWIus ci i •/rAis. YWol F oRaia'Ss 00 r►[l` n7 Par
AR01218
�I
I
I
I�
{
I
I
I
I
�
I
I
�I
I
"I�
I
—
_
T — �•.• — —
— — —
— — SBT6CN-r ,r6T.11'
— — — — —
= ptl _ T
Os ' s
rRp�rEpL'R
yj�ErOAx 1,rTA
`IRP.
ASPIULT
— —
— — —L — — — — — — —
— — — •—-- --...
Lys
rouNa r�� Rr14iN
N[•L'ORIfXR
IrZ
r/A Sr r/ I
S6YTION r1
I
r -,-N E -IS -r
I
1
Arman SCALE ,-_,D•
t
IIsr
70V= AACr TO CONFOUND PENCE
Er.r m/ER PALS ro LEASE Z"lr
!6D' 1DIER PALS f0 PIREM' PIRC6L LO,r
aFOUND
6/8' RSRA
SHRUBS
I
I
c�
SaV41'S9'8 80.00•
TR
IsrE
Do=
I
�
I�
%IMW
ORAYSL
/,.r rVVJR PACE TO MVPOONO "MW
491.0' IVFM PACS TO L UM LINT
m
$
r,"6• Town TACE To AUXWr AIR= I=
Ix
�I
I
I
I�
{
I
I
I
I
�
I
I
�I
I
"I�
I
�+I
rom fA. ALM ArrTA
1
I or 7 PRC"'
rDpray1D ,/�E• yETsl
= ptl _ T
Os ' s
rRp�rEpL'R
yj�ErOAx 1,rTA
`IRP.
FO B LVAS
F', 771
.s H FRAME
8' HOOD FENCE
mraR PACE OG OONPOf/ND 721W POUND
r. TIOIBR FACE TO WS: Lwjr
O' TOPM PACT TO MUFF F,1RCr6 Il NE
LEGEND
r
raucam oe.Aaa---
ivar Nrr
ernrvAa arAcrAle As—ems � � M w
wmOraeo® Af/W!C Aw--a--�— � � 11111
rwrA.� O O I
U � ■ ti
5 25
�t,o
RICHT Or IAY LDTE
04
3Jlr•6r"7'E 7rw 6r- — — — — —
D fXNCE
TOIER FACE TO LE09
MA r
M&rOrrR PACE 1;
fN c
PARCEL 11Nr
Nide
eFApOmyFxga,'re ry�rr�,.ra�� l
KEO �1
a ��
511R4EYlHC
o "r
TTrrE PACT TO rARiNT x
SANDON ADATTOON $�ufDoADDMDN
EI.0 v -
E� Z
= ptl _ T
Os ' s
FO B LVAS
F', 771
.s H FRAME
8' HOOD FENCE
mraR PACE OG OONPOf/ND 721W POUND
r. TIOIBR FACE TO WS: Lwjr
O' TOPM PACT TO MUFF F,1RCr6 Il NE
LEGEND
r
raucam oe.Aaa---
ivar Nrr
ernrvAa arAcrAle As—ems � � M w
wmOraeo® Af/W!C Aw--a--�— � � 11111
rwrA.� O O I
U � ■ ti
5 25
�t,o
RICHT Or IAY LDTE
3Jlr•6r"7'E 7rw 6r- — — — — —
— — ...`^�
—
8 :era srxlar
c
�— 8ST'61 r .—aAP6T —�
FOrIND r' CRlNP PIFs'
Nr LnrkrE L"r I. OLOpC r rorrNo I• L��pmT'w PIFr
r
eFApOmyFxga,'re ry�rr�,.ra�� l
KEO �1
a ��
511R4EYlHC
= F"
SANDON ADATTOON $�ufDoADDMDN
EI.0 v -
E� Z
= ptl _ T
Os ' s
On
SVRK e�1+�
plan CELIA&AULA=
5 N rf. r0►N5N, f OVM71. AUXZ f'J wl MVUWL f: YO ACRS. MAW OR
ANa ArL OTNOR aA75Tara xv#F-&F—FFAA)' FFw Awm "DAR Smsn, ICATTR eR &mRAr"S'µ❑ Ta ANY
I1la}
A PARrxL BT1NC A POR7fON aP rfLr LSRTATN 7RALT orrwm wscRmso aura i�ior�rFxr Rwcs
rrrr ruCarrs tarxa's orrns Prusxl tauxr�; '
u rtyY ANa ril11D lroRi FArmruuaDr �e'scRuan A.s rauora:
coraraNca Ar a r' CR/YP PST FIXING p+ FACT Ar rae >,�aMNFrar NRNrR [v Lor r. sLOPC r. sANnaN
ADDr170N.fBTNr2 N a2'oYsa• r A au-rARrr OF 872.T� FaL7 m A aJa' uAAR Sar (sArF) AXa Tarr PONrr
OF FapNN7NC: f7ANCr N O2'rr07• r / wsrlN� ar eOAW PTrr Yn A a/a' ROAAR SST fslrr}: 11fdN[S s
ereor�a.rai r rvA s� � s�rr�f��N� x ��r �� orrea�oa iraA-raro
PWNF aF rluNNwa SAID ABOrO Gas PARCIL caIYAtKs ar r AdrTS; xaas oR rASY.
AR01218
LEGEND
��
rrAr4u Pv1Yr—�
emWsr p.eu��
Wv alr+
m errrn.�.
orLdC WLlrIC •� — I/ry7 w
mawlr l+Afn'�— e
I
g 1�
%offer.vj' la w RrcBT oP r�r Lara — — — — — — —
—I
cum— — — — — — — —-w5fftr Tfsa.a— — — — — — — — —
— — — — —
g 26x8 S"WX?
e
8a7'a8 a'r "_ 2e—
nrxr'21'S .".
r
R gH y0�
— —
—
— — — — —
—
— — —
— — — — Serie rrr I2estr' — —
�
�f
e H0. 15M
ASPHALT
KNSA
A
�
— — —
— — — — — — —— — —
— -- — — —
I
cum
"0"' r/r'
ss r`�ACT}ON'�r
r-r-rr ]1 -r7 -F I
I+
I
as= aCALT r'-fO'
I
iit' form IACs to COxPMM "NO
2{tf rOFM FACE TO LUM I"S
sed' Tumm FAL7T To MUNT PAR= ON
I
I
e4
a POUND 6/8' MBA
iS
SHRUBS
SW"tf'53"6 00.00'
I
Isra
arra
r
$
CRIY6L
r.6' rVI= FACT MCV'MICS
r
Ih
IA ->n L
d IIaF TOUR FICd !0 PARTPM M PARCTL LTNa
I
PAP.
s
IAt
I' YOUR FACS YO COWIN= PAM
�
f
AOw' =I= PACO TO Is= lag
las• MW FACT ro PAOINr PARCEL Lr"
ONOPO&R TOAb'R
I
N PRAYS
I
I
8' WOOD JrVV=
i
>; I
I
Nera•ss-ir eD.DD•
I
bl�
PO(
POUND 6/B' R8
9
20.2' 70UR FACT TD f".qV ND PfHCr
1
27.6' 0VFM PACT TD LIAeT PAR
9a0' YOUR FICs TO PARTM' PIRCTL LWa
I rcuND r/r' RTOAR 1137/
i
af'ara mo
YayNa +J2' RrBeR �rsT.l
��rkra�°i'rsr.
I
I
LEGEND
��
rrAr4u Pv1Yr—�
emWsr p.eu��
Wv alr+
m errrn.�.
orLdC WLlrIC •� — I/ry7 w
mawlr l+Afn'�— e
I
g 1�
%offer.vj' la w RrcBT oP r�r Lara — — — — — — —
—I
cum— — — — — — — —-w5fftr Tfsa.a— — — — — — — — —
— — — — —
g 26x8 S"WX?
e
8a7'a8 a'r "_ 2e—
nrxr'21'S .".
r
R gH y0�
i
� Arsov
O
FwNa r' tRRrP mIr
� aaua r rouRn r cRu� PM
�-�
$l1RLLCYI*tG �y
sm"N ArArm�"r.
S DAN AAWMW a
F
�
�f
e H0. 15M
KNSA
A
�
T -MOBILE SITE NUMBER: AR01218 A
>� T -MOBILE SITE NAME: VEST LITTLE ROCK
sMobile TOWER VENTURES SITE NUMBER: UNKNOWN
12980 FOSTER, SUITE 200, OVERLAND PARK, KS 66213 TOWER VENTURES SITE NAME: UNKNOWN
SITE ADDRESS: 2525 JOHN BARROW RD
LITTLE ROCK AR 72204
NEW EQUIPMENT AND ANTENNAS ON: EXISTING 120' MONOPOLE
54a�gre
SITE INFORMATION ,k DRAWING INDEX
n u seiti>Be .' f
eD4MdanNle 1 h7ai48 Bno�
NO DESCRIPTION
SITE TYPE: MONOPOLE R A N S A S
• C-. �� T1 TITLE SHEET
SITE NAME- WEST LITRE ROCK -
oe: n,e AR -01218 I GNI GENERAL NOTES
SITE NUMBER: AR01218J� AR -01218 34.73070°N42.37200°W
V N 1 T E D 34.730709N 92.37200 R Z4Lfi�l I- GN2 GENERAL NOTES
SITE ADDRESS: 2525 JOHN BARROW RD Ou0�e dpcLaawle I
LITTLE ROCK, AR 72204 N6Li" J S-1 SURVEY
Foram eLar' <e e0eval {
COUNTY: PULASKI Rock CMatn+don + Cl OVERALL AND ENLARGED SITE PLANS
C2 ANTENNA ORIENTATION, MOUNT AND SCHEDULE
JURISDICTION: CITY LITTLE ROCK r
OCCUPANCY TYPE: UNMANNED wSpTlrw 8futtlaft ►y C3 WAVEGUIDE DETAILS
�-1 rTo 1�8y Sf S1 CONCRETE PAD DETAILS
A.D.A. COMPLIANCE: FACILITY IS UNMANNED AND NOT FOR
HUMAN HABITATION. From El UTILITY PLAN AND CONDUIT LAYOUT DIAGRAM
E2 ELECTRICAL DETAILS
APPLICANT: T -MOBILE • '
Met sr
12980 FOSTER, SUITE 200 wt E3 PPC H -FRAME DETAILS
OVERLAND PARK, KS 66213 -
CUSTOMER SERVICE asudeloh1A r Gl COMPOUND GROUNDING PLAN
877-878-7326f
PROPERTY OWNER: G2 GROUNDING DETAILS
LITTLE ROCK SCHOOL DISTRICT 'J RkOn St., CITY G3 GROUNDING DETAILS
504-447-5250 o�mss I'
SITE COORDINATES 63]: VICINITY MAP N.T.S. LOCATION MAP N.T.S. r -
LATITUDE N. 34.7307
LONGITUDE: W.2 DRIVING DIRECTIONS GROUND ELEVATION:
400 400' ' (AMSC) ....E _ EL
TOWER OWNER:L , d II Ove ❑pIT1BTi Staft
TOWER VENTURES DEPART LITTLE ROCK NATIONAL AIRPORT EXIT ROAD NAME CHANGES TO ANNIE M BANKHEAD DR [BANKHEAD DR] 0.3 MI, TAKE RAMP (RIGHT)
4091 VISCOUNT AVE ONTO 1-440 2.3 MI, 1-30 / DOWNTOWN HOT SPRINGS / TEXARKANA AT EXIT 138A, TAKE RAMP (RIGHT) ONTO 1-30 [US -167] 1.3 MI, 1-30 , i .
MEMPHIS, TN. 38118 E / US -167 N / US -65 N / DOWNTOWN AT EXIT 1398, TAKE RAMP (RIGHT) ONTO 1-630 5.5 MI, 1-630 AT EXIT 6B, TURN RIGHT ONTO --
nFC1GNFR; RAMP 0.2 MI, BARROW ROAD KEEP LEFT TO STAY ON RAMP 65 YDS, KANIS RD. TURN LEFT (SOUTH) ONTO JOHN BARROW RD 1.2 MI, TURN -
LEFT (EAST) ONTO LOCAL ROAD(S) 65 YDS, ARRIVE AR -01218. r
BRANCH COMMUNICATIONS, LLC
1516 SOUTH BOSTON AVE. STE 215
TULSA, OK. 74119
CONTACT: JAMES W MCCOY ONE CALL NUMBER:
PHONE: (918) 261-1875 A&E DRAWING REVIEW CODE COMPLIANCE
AEHTTECT/ENGINEER: CALL ARKANSAS
TOWER ENGINEERING SOLUTIONS, LLC TITLE: SIGNATURE: DATE: ALL WORK SHALL. BE PERFORMED AND MATERIALS INSTALLED IN
8445 FREEPORT PARKWAY SUITE 375 ONE CALL 811 ACCORDANCE. WITH THE CURRENT EDITIONS OF THE FOLLOWING
IRVING. TX 75063 PROPERTY OWNER: CODES AS ADOPTED BY THE LOCAL GOVERNING AUTHORITIES.
CONTACT: JAIME REYES 800) 482-8998 NOTHING IN THESE PLANS IS TO BE CONSTRUED TO PERMfI
PHONE: (972) 635-8238 T -MOBILE CONSTRUCTION MGR: I -- CALL 3 WORKING DAYS
ZONING APPROVAL: '� BEFORE YOU DIG! WORK NOT CONFORMING TO THESE CODES.
TELEPHONE COMPANY:
BUILDING/DWELLING CODE: IBC 2009
N/A RF ENGINEER:
SITE ACQUISITION: STRUCTURAL CODE: IBC 2009
Ni SER D°MP'wY: �ATUS °°°E: D O NOT SCALE DRAWING S
PLUMBING CODE: IPC 2009
1 ACCEPTED—WITH OR NO COMMENTS, CONSTRUCTION MAY PROCEED MECHANICAL CODE: IMC 2009
2 1 NOT ACCEPTED—RESOLVE COMMENTS AND RESUBMIT CONTRACTOR SHALL VERIFY ALL PLANS AND EXISTING DIMENSIONS ELECTRIC CODE: NEC 2011
N AND CONDITIONS ON THE JOB SITE AND SHALL IMMEDIATELY NOTIFY
rAE FOUAWNtf PARAES Mrt7 EVY APPROVE AM AGCIEPT THS EH
D00UMrS AM ALM40la2E THE ENGINEER IN WRITING OF ANY DdSCREPANCIFS BEFORE
- 'A c JM 101 TO 'WB
ROCEED TA
'CA
HE eaNsTRuaTIa« Ot5CW6EA I+[Rsx ALL ootwmtrs
AHE sualErl m REwEw B•r THE Loral guaDrrG OFPARiYENT Ae+O tAr nMaA5E rwv+GEs PROCEEDING WITH THE WORK OR BE RESPONSIBLE FOR SAME. FIRE/LIFE SAFETY CODE: IBC 2009, IFC 2009, NFOA 101
OR Y010IMRG710N5. 1 —1 j
T • -Mobile-
12980 FOSTER, SUITE 200
OVERLAND PARK, KS 66213
I�Qfl PD�
TOWER ENGINEERING O S
8445 FREEPORT PARKWAY.
SUITE 375
IRVING. TX 75063
PHONE: (972) 635-8238
COA / 2705 EXP. 12/31/2015
BR NCH
COMMUMCA77ON8,LLC
BRANCH COMMUNICATIONS
1516 S BOSTON AVE STE 215
TULSA, OKLAHOMA 74119
(918) 949-4551
WEST LITTLE ROCK
BTS NUMBER:
AR01218_A
2525 JOHN BARROW RD
LITTLE ROCK AR 72204
1E
PE Mf 7784 EXP. 12/31/2014
IVO DATE I DESCRIPTION
BY
A 8/13/14 PRFI M ISSUE
JPR
B 9/10/14 PRELIM ISSUE
NDP
0 9/11/14 CONST ISSUE
NDP
SHEET TIRE:
TITLE SHEET
SHEET 1:
T 1
PROJECT #:
ARO 121
•
0
BY: SWM
DIVISION 1 - GENERAL REQUIREMENTS
1.1 INTENT
A. THESE SPECIFICATIONS AND CONSTRUCTION DRAWINGS ACCOMPANYING THEM
DESCRIBE THE WORK TO BE DONE AND THE MATERIALS TO BE FURNISHED FOR
CONSTRUCTION,
B. THE DRAWINGS AND SPECIFICATIONS ARE INTENDED TO BE FULLY EXPLANATORY
AND SUPPLEMENTARY. HOWEVER. SHOULD ANYTHING BE SHOWN. INDICATED OR
SPECIFIED ON AND NOT THE OTHER, IT SHALL BE ACCOMPLISHED AS IF SHOWN,
INDICATED OR SPECIFIED IN BOTH.
C. THE INTENTION OF THE DOCUMENTS IS TO INCLUDE ALL LABOR AND MATERIALS
REASONABLY NECESSARY FOR THE PROPER EXECUTION AND COMPLETION OF THE
WORK STIPULATED IN THE CONTRACT.
D. THE PURPOSE OF THE SPECIFICATIONS IS TO INTERPRET THE INTENT OF THE
DRAWINGS AND TO DESIGNATE THE METHOD OF THE PROCEDURE, TYPE AND
QUALITY OF MATERIALS REQUIRED TO COMPLETE THE WORK.
E. MINOR DEVIATIONS FROM THE DESIGN LAYOUT ARE ANTICIPATED AND SHALL BE
CONSIDERED AS PART OF THE WORK. NO CHANGES THAT ALTER THE CHARACTER
OF THE WORK WILL BE MADE OR PERMITTED BY THE OWNER WITHOUT ISSUING A
CHANGE ORDER.
1. 1.2 CONFLICTS
A THE CONTRACTOR SHALL BE RESPONSIBLE FOR VERIFICATION OFF ALL
MEASUREMENTS AT THE SITE BEFORE ORDERING ANY MATERIALS OR DOING ANY
WORK, NO EXTRA CHARGE OR COMPENSATION SHALL BE ALLOWED DUE TO
DIFFERENCE BETWEEN ACTUAL DIMENSIONS AND DIMENSIONS fNOICATED ON THE
CONSTRUCTION DRAWINGS. ANY SUCH DISCREPANCY IN DIMENSION WHICH MAY BE
FOUND SHALL BE SUBMITTED TO THE OWNER FOR CONSIDERATION BEFORE THE
CONTRACTOR PROCEEDS WITH THE WORK IN THE AFFECTED AREAS.
B. THE BIDDER, IF AWARDED THE CONTRACT, WILL NOT BE ALLOWED ANY EXTRA
COMPENSATION BY REASON OF ANY MATTER OR THING CONCERNING WHICH SUCH
BIDDER MIGHT HAVE BEEN FULLY INFORMED PRIOR TO BIDDING.
C. NO PLEA OF IGNORANCE OF CONDITIONS THAT EXIST, OR OF DIFFICULTIES OR
CONDITIONS THAT MAY BE ENCOUNTERED OR OF ANY OTHER RELEVANT MATTER
CONCERNING THE WORK TO BE PERFORMED IN THE EXECUTION OF THE WORK
WILL BE ACCEPTED AS AN EXCUSE FOR ANY FAILURE OR OMISSION ON THE PART
OF THE CONTRACTOR TO FULFILL EVERY DETAIL OF ALL THE REQUIREMENTS OF
THE CONTRACT DOCUMENTS GOVERNING THE WORK,
1.3 CONTRACTS AND WARRANTIES
A. EACH CONTRACTOR IS RESPONSIBLE FOR OBTAINING THE BUILDING PERMIT AT THE
LOCAL JURISDICTION AS THE CONTRACTDR-OF-RECORD, AND PRONDING
JURISDICTION WITH ALL PROOF REQUIRED TO OPERATE AS A CONTRACTOR IN THAT
JURISDICTION. THE CONTRACTOR SHALL BE REIMBURSED ONLY THE AMOUNT OF
ANY FEE PAID AS FOLLOWS:
1. PLAN REVIEW FEE.
2. BUILDING PERMIT FEE.
3. CONNECTIONS AND INSPECTIONS FEE.
B. CONTRACTOR IS RESPONSIBLE FOR APPLICATION AND PAYMENT OF CONTRACTOR
LICENSES AND BONDS.
1.4 STORAGE
ALL MATERIALS MUST BE STORED IN A LEVEL AND DRY FASHION AND IN A
MANNER THAT DOES NOT NECESSARILY OBSTRUCT THE FLOW OF OTHER WORK.
ANY STORAGE METHOD MUST MEET ALL RECOMMENDATIONS OF THE ASSOCIATED
MANUFACTURER.
II 1.5 CLEAN UP
A. THE CONTRACTORS AT ALL TIME SHALL KEEP THE SITE FREE FROM ACCUMULATION
OF WASTE MATERIALS OR RUBBISH CAUSED BY THEIR EMPLOYEES AT WORK AND
AT THE COMPLETION OF THE WORK. THEY SHALL REMOVE ALL RUBBISH FROM
AND ABOUT THE BUILDING AREA. INCLUDINC ALL THEIR TOOLS. SCAFFOLDING AND
SURPLUS MATERIALS AND SHALL LEAVE THEIR WORK CLEAN AND READY FOR USE
B. EXTERIOR: VISUALLY INSPECTED EXTERIOR SURFACES AND REMOVE ALL TRACES OF
SOIL.. WASTE MATERIALS, SMUDGES AND OTHER REGION MATTER.
1. REMOVE ALL TRACES OF SPLASHED MATERIALS FROM ADJACENT SURFACES.
2. IF NECESSARY TO ACHIEVE A UNIFORM DEGREE OF CLEANLINESS, HOES DOWN
THE EXTERIOR OF THE STRUCTURE.
C. INTERIOR: VISUALLY INSPECT INTERIOR SURFACES AND REMOVE ALL TRACES OF
SOIL, WASTE MATERIALS, SMUDGES AND OTHER FOREIGN MATTER FROM
WALLS/FLOOR/CEIUNG.
1. REMOVE ALL TRACES OF SPLASHED MATERIALS FROM ADJACENT SURFACES.
2. REMOVE PAINT DROPPINGS, SPOTS, STAINS AND DIRT FROM FINISHED SURFACES.
1.6 CHANGE ORDER PROCEDURE
A. THE CONTRACTOR CHANGE ORDERS MAY BE INITIATEO BY THE OWNER AND/ OR
THE CONTRACTOR INVOLVED. THE CONTRACTOR. UPON VERBAL REQUEST FROM
THE OWNER SHALL PREPARE A WRITTEN PROPOSAL DESCRIBING THE CHANGE IN
WORK OR MATERIALS AND ANY CHANGES IN THE CONTRACT AMOUNT AND
PRESENT TO THE OWNER WITHIN 72 HOURS FOR APPROVAL. SUBMIT REQUESTS
FOR SUBSTITUTIONS IN THE FORM AND IN ACCORDANCE WITH PROCEDURE
REQUIRED FOR CHANGE ORDER PROPOSALS. ANY CHANGES IN SCOPE OF WORK
OR MATERIALS WHICH ARE PERFORMED BY THE CONTRACTOR WITHOUT WRITTEN
CHANGE ORDER AS DESCRIBED AND APPROVED BY THE OWNER SHALL PLACE
FULL RESPONSIBILITY OF THESE ACTIONS ON THE CONTRACTOR.
1.7 RELATED DOCUMENTS AND COORDINATION
A. GENERAL CARPENTRY, ELECTRICAL AND ANTENNA DRAWINGS ARE INTERRELATED. IN
PERFORMANCE OF THE WORK, THE CONTRACTOR MUST REFER TO ALL DRAWINGS.
ALL COORDINATION TO BE RESPONSIBILITY OF THE CONTRACTOR.
1.8 SHOP DRAWINGS
A. CONTRACTOR SHALL SUBMIT SHOP DRAWINGS AS REQUIRED AND LISTED IN THESE
SPECIFICATIONS TO THE OWNER FOR APPROVAL.
B. ALL SHOP DRAWINGS SHALL BE REVIEWED, CHECKED AND CORRECTED BY
CONTRACTOR PRIOR TO SUBMITTED TO THE OWNER.
1.9 PRODUCTS AND SUBSTITUTIONS
A. SUBMIT 3 COPIES OF EACH REQUEST FOR SUBSTITUTION. IN EACH REQUEST
JDENTIFY THE PRODUCT OR FABRICATION OR INSTALLATION METHOD TO BE
REPLACED BY THE SUBSTITUTION. INCLUDE RELATED SPECIFICATION SECTION AND
DRAWING NUMBERS AND COMPLETE DOCUMENTATION SHOWING COMPLIANCE WITH
THE REQUIREMENTS FOR SUBSITTUTIONS.
B. SUBMIT ALL NECESSARY PRODUCT DATA AND CUT SHEETS WHICH PROPERLY
INDICATE AND DESCRIBE THE ITEMS, PRODUCTS ANO MATERIALS BEING INSTALLED.
THE CONTRACTOR SHALL. IF DEEMED NECESSARY BY THE OWNER SUBMIT ACTUAL
SAMPLES TO THE OWNER FOR APPROVAL IN LIEU OF CUT SHEETS,
1.10 QUALITY ASSURANCE
A. ALL SHALL BE IN ACCORDANCE WITH APPLICATION LOCAL, STATE AND FEDERAL
REGULATIONS. THESE SHALL INCLUDE BUT NIT BE LIMITED TO THE LATEST
VERSION OF THE FOLLOWING:
• ANSI TLA/EIA -- 222 - G
• 2009 INTERNATIONAL BUILDING CODE
• BUILDING OFFICIALS AND CODE ADMINISTRATORS (BOCA) 1990
• NATIONAL ELECTRICAL CODE (NEC) WITH LOCAL AMENDMENTS 2009
• UNDERWRITER LABORATORIES APPROVED ELECTRICAL PRODUCTS
• AMERICAN INSTITUTE OF STEEL CONSTRUCTION
• SPECIFICATIONS (RISC)
0 LIFE SAFETY CODE NFPA - 101-1990
1.11 ADMINISTRATION
A. BEFORE THE COMMENCEMENT OF ANY WORK. THE CONTRACTOR WILL ASSIGN A
PROJECT MANAGER WHO WILL ACT AS A SINGLE POINT OF CONTRACT FOR ALL
PERSONNEL INVOLVED IN THIS PROJECT. THIS PROJECT MANAGER WILL DEVELOP A
MASTER SCHEDULE FOR THE PROJECT WHICH WILL BE SUBMITTED TO THE OWNER
PRIOR TO THE COMMENCEMENT OF ANY WORK.
B. SUBMIT A BAR UKE PROGRESS CHART NOT MORE THAN 3 DAYS AFTER THE DATE
ESTABLISHED FOR COMMENCEMENT OF THE WORK ON THE SCHEDULE, INDICATING
A TIME BAR FOR EACH MAJOR CATEGORY OR UNIT OF WORK TO BE PERFORMED
AT SITE. PROPERLY SEQUENCED AND COORDINATED WITH OTHER ELEMENTS IN
ADVANCE OF THE DATE ESTABLISHED FOR SUBSTANTIAL COMPLETION OF THE
WORK,
C. PRIOR TO COMMENCING CONSTRUCTION, THE OWNER SHALL SCHEDULE AN
ON-SITE MEETING WITH ALL MAJOR PARTIES. THIS WOULD INCLUDE (THOUGH NOT
LIMITED TO) THE OWNER, PROJECT MANAGER, CONTRACTOR, LAND OWNER
REPRESENTATIVE, LOCAL TELEPHONE COMPANY, TOWER ERECTION FOREMAN (IF
SUBCONTRACTED).
D. CONTRACTOR SHALL BE EQUIPPED WITH SOME MEANS OF CONSTANT
COMMUNICATIONS. SUCH AS A MOBILE PHONE OR A BEEPER, THIS EQUIPMENT
WILL NOT BE SUPPLIED BY THE OWNER, NOR WILL WIRELESS SERVICE BE
ARRANGED.
E. DURING CONSTRUCTION, CONTRACTOR MUST ENSURE THAT EMPLOYEES AND
SUBCONTRACTORS WILL WEAR HARD HATS AT ALL TIMES. CONTRACTOR WILL
COMPLY WITH ALL WPCS SAFETY REQUIREMENTS IN THEIR AGREEMENT.
F. CONTRACTOR MUST PROVIDE WRITTEN DAILY UPDATES ON SITE PROGRESS TO THE
OWNER.
G. A COMPLETE INVENTORY OF CONSTRUCTION MATERIALS AND EQUIPMENT IS
REQUIRED PRIOR TO START OF CONSTRUCTION.
H. NDTIFY THE OWNER / PROJECT MANAGER IN WRITING NO LESS THAN 48 HOURS
IN ADVANCE OF CONCRETE POURS, TOWER ERECTIONS, AND EQUIPMENT CABINET
PLACEMENTS.
1.12 INSURANCE AND BONDS
A. CONTRACTOR AT THEIR OWN EXPENSE CARRY AND MAINTAIN FOR THE DURATION
OF THE PROJECT ALL INSURANCE AS REQUIRED AND LISTED AND SHALL NOT
COMMENCE WITH THEIR WORK UNTIL THEY HAVE PRESENTED AN ORIGINAL
CERTIFICATE OF INSURANCE STATING ALL COVERAGE TO THE OWNER, REFER TO
THE MASTER AGREEMENT FOR REQUIRED INSURANCE LIMITS.
B. THE OWNER SHALL BE NAMED AS AN ADDITIONAL INSURED ON ALL POUCIES.
C. CONTRACTOR MUST PROVIDE PROOF OF INSURANCE.
DIVISION 2 - SITE WORK AND DRAINAGE
1.1 WORK INCLUDED:
REFER TO THE SURVEY AND SITE PLAN FOR WORK INCLUDED.
1.2 RELATED WORK
B. INSTALLATION OF ANTENNA SUPPORT SYSTEM
1.5 SEQUENCING
A. CONFIRM SURVEY STAKES AND SET ELEVATION STAKES PRIOR TO ANY
CONSTRUCTION.
B. IF REQUIRED, GRADE, SEED, FERTIUZED AND MULCH DISTURBED AREAS
IMMEDIATELY AFTER BRINING THE SITE AND ACCESS ROAD TO BASE COURSE
ELEVATION. WATER TO ENSURE GROWTH,
C. REMOVE GRAVEL FROM TEMPORARY CONSTRUCTION ZONE.
1.7 WARRANTY
A. IN ADDITION TO THE WARRANTY ON ALL CONSTRUCTION COVERED IN THE
CONTRACT DOCUMENTS, THE CONTRACTOR SHALL REPAIR ALL DAMAGE TO
SURROUNDING PROPERTY CAUSED BY CONSTRUCTION.
B. DISTURBED AREAS WILL REFLECT GROWTH ON NEW GRASS COVER PRIOR TO FINAL
INSPECTION,
2.1 MATERIALS
A. SITE MATERIALS: FILL MATERIAL - ACCEPTABLE SELECT FILL SHALL BE IN
ACCORDANCE WITH LOCAL DEPARTMENT OF HIGHWAY AND PUBLIC TRANSPORTATION
STANDARDS SPECIFICATION.
B. SOIL STABILIZER FABRIC SHALL BE MIRAFI - 500X.
C. NON-STRUCTURAL S1TE CONCRETE SHALL BE 3000 PSI BREAKING STRENGTH AT
28 DAYS. COMPLY WITH GENERAL PROVISIONS OF DIVISION 3 CONCRETE
SPECIFICATIONS.
2.2 EQUIPMENT
A. COMPACTING SHALL BE ACCOMPLISHED BY MECHANICAL MEANS. LARGER AREA
SHALL BE COMPACTED BY SHEEPS FOOT, VIBRATOR OR RUBBER TIRED ROLLERS
WEIGHING AT LEAST FIVE TONS. WATER TREATMENT MAY REQUIRED TO OBTAIN
COMPACTION. SMALLER ARES SHALL BE COMPACTED BY POWER -DRIVE, HAND
HELD TAMPERS.
3.1 INSPECTIONS
LOCAL BUILDING INSPECTION SHALL BE NOTIFIED NO LESS THAN 48 HOURS IN
ADVANCE OF CONCRETE POURS,
3.2 PREPARATION
A. PRIOR TO OTHER EXCAVATION AND CONSTRUCTION EFFORTS GRUB ORGANIC
MATERIAL TO A MINIMUM OF SIX INCHES BELOW ORIGINAL GROUND LEVEL.
B. UNLESS OTHERWISE INSTRUCTED BY THE OWNER, REMOVE TREES. BRUSH AND
DEBRIS FORM THE PROPERTY TO AN AUTHORIZED LANDFILL,
C. PRIOR TO PLACEMENT OF FILL OR BASE MATERIALS, REMOVE SOFT SPOTS AND
COMPACT TO 85% STANDARD PROCTOR.
D. WHERE UNSTABLE SOIL CONDITIONS ARE ENCOUNTERED, LINE THE GRUBBED
AREAS WITH STABILIZER MAT PRIOR TO REPLACEMENT OF FILL OR BASE MATERIAL.
MOO.
12980 FOSTER, SUITE 200
OVERLAND PARK, KS 66213
TOWER ENGINEERING ONS
8445 FREEPORT PARKWAY,
SUITE 375
IRVING. TX 75063
PHONE: (972) 635-8238
COA ! 2705 EXP. 12/31/2015
BY:
BJH NCH
COMMUN/CA770NS,L.GC
BRANCH COMMUNICATIONS
1518 S BOSTON AVE STE 215
TULSA. OKLAHOMA 74119
(918) 949-4551
SITE NAME:
WEST LITTLE ROCK
AR01218 A
SITE ADDRESS:
2525 JOHN BARROW RD
LITTLE ROCK AR 72204
LICENSE
PitOFESXE �0
RNLI
J No. 7784
qAM E
�&E ,
PE 0 7784 EXP. 12/31/2014
:JO DATE DESCRIPTION
BY
A 8/13/14 PRELIM ISSUE
JPR
B 9110114 PRELIM ISSUE
NDP
0 P/1 1 14 CONST ISSUE
NDP
i
SHEET TIRE:
GENERAL NOTES
SHEET #:
G N 1
PROJECT #;
18
R0I2�
A R 2T8
Ev:
JWM
JWM
3.2 PREPARATION
A. PRIOR TO OTHER EXCAVATION AND CONSTRUCTION EFFORTS GRUB ORGANIC
MATERIAL TO A MINIMUM OF SIX INCHES BELOW ORIGINAL GROUND LEVEL.
B. UNLESS OTHERWISE INSTRUCTED BY THE OWNER, REMOVE TREES, BRUSH AND
DEBRIS FORM THE PROPERTY TO AN AUTHORIZED LANDFILL.
C. PRIOR TO PLACEMENT OF FILL OR BASE MATERIALS, REMOVE SOFT SPOTS AND
COMPACT TO 85% STANDARD PROCTOR.
D. WHERE UNSTABLE SOIL CONDITIONS ARE ENCOUNTERED, LINE THE GRUBBED AREAS
WITH STABILIZER MAT PRIOR TO REPLACEMENT OF FILL OR BASE MATERIAL
3.3 INSTALLATION
A. CLEAR EXCESS SPOILS, IF ANY, FROM JOB SITE AND DO NOT SPREAD BEYOND THE
LIMITS OF THE OWNERS LEASE PROPERTY UNLESS AUTHORIZED BY PROJECT
MANAGER, IN WRITING.
B. THE FINISH GRADE, INCLUDING TOP SURFACE COURSE, SHALL EXTEND TO LEASE
LINE.
3.4 FIELD QUALITY CONTROL
A. COMPACTION SHALL BE 90% MAXIMUM DENSITY IN ACCORDANCE WITH ASTM
D-1557 FOR SITE WORK AND 95% UNDER PLATFORM AREA. SETTLEMENT WILL BE
EXCAVATED AND REFILLED AT CONTRACTOR'S EXPENSE.
3.5 QUALITY ASSURANCE
A ALL STEEL MATERIALS UTILIZED IN CONJUNCTION WITH THIS SPECIFICATION WILL BE
GALVANIZED OR STAINLESS STEEL. WEIGHT OF ZINC COATING ON THE FABRIC SHALL
NOT BE LESS THAN 12 OUNCES PER SQUARE FOOT OF MATERIAL COVERED. POSTS
SHALL BE HOT -DIPPED IN GRADE E ZINC, 1.8 OUNCES PER SQUARE FOOT.
3.6 APPLICABLE STANDARDS
A. ASTM -A120 SPECIFICATION FOR PIPE, STEEL BLACK AND HOT -DIPPED ZINC COATED
(GALVANIZED) WELDED AND SEAMLESS FOR ORDINARY USES.
B. ASTM -123 ZINC (HOT -DIP GALVANIZED) COATING ON IRON AND STEEL PRODUCTS.
C. ASTM -A153 STANDARD SPECIFICATION FOR ZINC COATING (HDT-DIP) ON IRON AND
STEEL HARDWARE.
D. ASTM -A392 SPECIFICATION FOR ZINK-COATED STEEL CHAIN LINK FENCE FABRIC.
E. ASTM -A491 SPECIFICATION FOR ALUMINUM -COATED CHAIN LINK FENCE FABRIC.
F. ASTM -A525 STANDARD SPECIFICATION FOR STEEL SHEET ZINC COATED (GALVANIZED)
BY THE HOT -DIPPED PROCESS.
G. ASTMOA570 SPECIFICATION FOR HOT -ROLLED CARBON STEEL SHEET AND STRIP
STRUCTURAL QUALITY.
H. ASTM -A585 SPECIFICATION FOR ALUMINUM COATED STEEL BARBED WIRE.
EXCAVATE POST HOLES WITH MECHANICAL AUGER EQUIPMENT. EXCAVATE POST HOLES
PER CONSTRUCTION DOCUMENTS. CONFIRM PROPER DEPTH AND DIAMETER OF POST
HOLE EXCAVATIONS.
SPECIAL CONSTRUCTION TOWER & ANTENNA
INSTALLATION
1.1 WORK INCLUDED
A. IF REQUIRED, ERECT FURNISHED TOWER.
B. GROUND TOWER TEMPORARILY DURING ERECTION. GROUNDING SHOULD INCLUDE
BASE(S) AND ANCHORS
C. IF REQUIRED, INSTALL THREE (3) SIDE ARMS, CONSISTING OF OWNER
REPRESENTATIONS.
D. INSTALL ANTENNAS AS INDICATED ON DRAWINGS AND OWNER SPECIFICATION.
E. INSTALL GALVANIZED STEEL ANTENNA MOUNTS AS INDICATED ON DRAWINGS.
F. INSTALL FURNISHED GALVANIZED STEEL WAVE GUIDE LADDER.
G. INSTALL WAVE GUIDE BRIDGE AS INDICATED ON DRAWING.
H. SUPPLY AND INSTALL ONE INSULATED GROUND BAR AT EQUIPMENT CABINET.
I. SUPPLY AND INSTALL GROUNDING KITS WITH LONG BARREL DOUBLE CRIMPED
COMPRESSION LUGS. (SIM. TO ANDREW-223700TOD OF APPROVED EQUAL) ATOP
TOWER BASE BEFORE ENTERING THE EQUIPMENT, GROUNDING LEADS TO BE
CONNECTED TO INSULATED GROUND BAR.
A. ASSIST OWNER TECHNICIANS IN PERFORMING SWEEP TEST OF INSTALLED COAX.
B. CONCRETE PIERS FOR FOUNDATIONS SHALL BE DRILLED AND POURED ON THE
SAME DAY.
2.2 RELATED WORK
2.3 REQUIREMENTS OF REGULATOR AGENCIES
A. FURNISH U.L. LISTED EQUIPMENT WHERE SUCH LABEL IS AVAILABLE, INSTALL IN
CONFORMANCE WITH U.L STANDARDS WHERE APPLICABLE.
B. INSTALL ANTENNA, ANTENNA CABLES AND GROUNDING SYSTEM IN ACCORDANCE WITH
DRAWINGS AND SPECIFICATION IN EFFECT AT PROJECT LOCATION AND
RECOMMENDATIONS OF STATE AND LOCAL BUILDING CODES, SPECIAL CODES HAVING
JURISDICTION OVER SPECIFIC PORTIONS OF WORK. THIS INCLUDES BUT IS NOT
LIMITED TO THE FOLLOWING:
1. EIA - ELECTRONIC INDUSTRIES ASSOCIATION TIA-EIA-222-G. STRUCTURAL
STANDARDS FOR STEEL ANTENNA TOWERS AND ANTENNA SUPPORTING STRUCTURES.
2. FAA - FEDERAL AVIATION ADMINISTRATION ADVISORY CIRCULAR AC 70/7460 -IH,
OBSTRUCTION MARKING AND LIGHTING.
3. FCC - FEDERAL COMMUNICATIONS COMMISSION RULES AND REGULATIONS FORM
715, OBSTRUCTION MARKING NAD LIGHTING SPECIFICATIONS FOR ANTENNA
STRUCTURES.
4. AISC - AMERICAN INSTITUTE OF STEEL CONSTRUCTION SPECIFICATION FOR
STRUCTURAL JOINTS USING ASTM A325 OR A490 BOLTS.
5. NEC - NATIONAL ELECTRICAL CODE - ON TOWER LIGHTING KITS.
6. UL - UNDERWRITER'S LABORATORIES APPROVED ELECTRICAL PRODUCTS.
7. IN ALL CASES, PART 77 OR THE FAA RULES AND PARTS 17 AND 22 OF THE
FCC RULES ARE APPLICABLE AND IN THE EVENT OF CONFLICT, SUPERSEDE ANY
OTHER STANDARDS OD SPECIFICATIONS.
8. 1990 LIFE SAFETY CODE NFPA - 101
3.3 INSTALLATION
A. THE ACCESS ROAD SHALL BE BROUGHT TO BASE COURSE ELEVATION PRIOR TO
FOUNDATION CONSTRUCTION.
B. AVOID CREATING DEPRESSIONS WHERE WATER MAY POND.
C. THE CONTRACT INCLUDES ALL NECESSARY GRADING, BANKING, DITCHING AND
UNLESS OTHERWISE INDICATED, COVERING TWO INCHES OF SURFACE COURSE. ALL
ROADS OR ROUTES UTILIZED FOR ACCESS TO THE SITE, COMMENCING AT THE
POINT OF INTERSECTION WITH THE NEAREST PUBLIC THOROUGHFARE, ARE INCLUDED
IN SCOPE UNLESS OTHERWISE NOTED.
D. WHEN APPROVING A EXISTING ACCESS ROAD, GRADE THE EXISTING ROAD TO
REMOVE ANY ORGANIC MATTER AND SMOOTH THE SURFACE BEFORE PLACING FILL
OR STONE.
E. PLACE FILL OR STONE IN 6 INCH MAXIMUM LIFTS AND COMPACT BEFORE PLACING
NEXT LIFT.
F. THE FINISH GRADE, INCLUDING TOP SURFACE COURSE, SHALL EXTEND A MINIMUM
OF ONE FOOT BEYOND THE SITE FENCE AND SHALL COVER THE AREA AS
INDICATED.
G. RIP RAP SHALL BE APPLIED TO THE SIDES SLOPES OF ALL FENCED SITE AREAS,
PARKING ARES AND TO ALL OTHER SLOPES GREATER THAN 2 : 1.
H. RIP RAP SHALL BE APPLIED TO THE SIDES OF SIDES OF DITCHES 05 DRAINAGE
SWALES AS INDICATED ON PLANS.
I. RIP RAP ENTIRE DITCH FOR SIX FEET IN ALL DIRECTIONS AT CULVERT OPENINGS.
J. SEED, FERTILIZER AND STRAW COVER SHALL BE APPLIED TO ALL OTHER DISTURBED
AREAS AND DITCHES, DRAINAGE. SWALES, NOT OTHERWISE RIP -RAPPED.
K. UNDER NO CIRCUMSTANCES WILL DITCHES, SWALES OR CULVERTS BE PLACED SO
THEY DIRECT WATER TOWARDS, OR PERMIT STANDING WATER IMMEDIATELY ADJACENT
TO SITE. IF OWNER DESIGNS OR ELEVATIONS CONFLICT WITH THIS GUIDANCE ADVISE
THE OWNER IMMEDIATELY, IN WRITING.
L. IF DITCH LIES WITH SLOPES GREATER THAN TEN PERCENT, MOUND DIVERSIONARY
HEADWALLS IN THE DITCH AND RIP RAP THE UPSTREAM SIDE OF THE HEADWALL AS
WELL AS THE DITCH FOR SIX FEET ABOVE THE CULVERT ENTRANCE.
M. SEED AND FERTILIZER SHALL BE APPLIED TO SURFACE CONDITIONS WHICH WILL
ENCOURAGE ROOTING. RAKE AREAS TO BE SEEDED TO EVEN THE SURFACE AND
LOOSEN THE SOIL.
N. SOW SEED IN TWO DIRECTIONS IN TWICE THE QUANTITY RECOMMENDED BY THE
SEED PRODUCER.
0. IT IS THE CONTRACTOR'S RESPONSIBILITY TO ENSURE GROWTH OF SEEDED AND
LANDSCAPED AREAS BY WATERING UP TO THE POINT OF RELEASE FROM THE
CONTRACT. CONTINUE TO REWORK BARE AREAS UNTIL COMPLETE COVERAGE IS
OBTAINED.
3.5 PROTECTION
A. PROTECT SEEDED AREAS FROM EROSION BY SPREADING STRAW TO A UNIFORM
LOOSE DEPTH OF 1-2 INCHES, STAKE AND TIE DOWN AS REQUIRED. USE OF
EROSION CONTROL MESH OR MULCH NET WILL BE AN ACCEPTABLE ALTERNATE.
B. ALL TREES PLACED IN CONJUNCTION WITH A LANDSCAPE CONTRACT WILL BE
WRAPPED, TIED WITH HOSE PROTECTION WIRE AND SECURED TO 2 1 INCH x 2
INCH x 4 FOOT STEEL ANGLE EXTENDING TWO FEET INTO THE GROUND ON FOUR
SIDES OF THE TREE.
C. ALL EXPOSED AREAS SHALL BE PROTECTED AGAINST WASHOUTS AND SOIL EROSION.
T - -Mobile`
12980 FOSTER, SUITE 200
OVERLAND PARK, KS 66213
PRODUCED BY:
AAA
TOWER ENGiNEIRI,VG SOLUTIONS
8445 FREEPORT PARKWAY,
SUITE 375
IRVING. TX 75063
PHONE: (972) 635-8238
COA j 2705 EXP. 12/31/2015
BR NCH
COMML/NICA77ONS,LLC
BRANCH COMMUHIUTKINS
1516 S BOSTON AVE $TE 215
TULSA. OKLAHOMA 74119
(916) 949-4551
WEST LITTLE ROCK
BTS NUMBER:
AR01218_A
SITE ADDRESS:
2525 JOHN BARROW RD
LITTLE ROCK AR 72204
PROJECT NU p4��
AR j TAOF
LICE S
i PRO SI
IL
EN
Jqo. 7784{ +is
�'1E R�•
PE j 7784 EXP. 12/31/2014 1
VO DATE I DESCRIPTION
BY
A 8 13 14 PRELIM ISSUE
JPR
B 9/12Z14 PRELIM ISSUE
NDP
D 9/11/14 CONST ISSUE
NAP
I
SHEET TITLE:
GENERAL NOTES
SHEET j: PROJECT j:
A01218J10
JWWMGN2
.
u 61•
x
68'-0"
10'-7' 16'-0" 8'-0' 3'--O' 7'-7" 21'-0" 1'- Q'
x
EXISTING 21'-0'
WOOD GATE b
r - PROPOSED T -MOBILE c
10'-O"x12'-0" CONCRETE x
EQUIPMENT PAD AND
{ EXISTING LEASE AREA RE: 2/C1
AT&T ! ' o
SHELTER ZR ~
Lm 9i
SSCPROPCAB NET OSED MOBILE
x o
I
PROPOSED T -MOBILE
PROPOSED LOWER r 23'-0' ICE BRIDGE,
COVP BOX RE: SHEET C4
EXISTING ICE : K
BRIDGE � I
EXISTING
-- EMPTY
CONCRETE EXISTING 8'-O' c
PAD _ WOOD FENCE o c
EXISTING ICE �c o x c
BRIDGE S
EXISTING I
24 -B 4d
BRIDGE a
'r EXISTING 120'
MONOPOLE_
EXISTING — x
H-FRAMEv
v
z�
EXISTING - EXISTING `
AT&Ti Z H -FRAME
SHELTER I x 'o
i
12'-0' 16'-6' 7'-0" 4'-0' 28'-6'
TRUE NORTH
OVERALL SITE PLAN (0 MAG E)
SCALE:
0' 10' 20' 30• 40'
PROPOSED GPS ANTENNA,
RE: 4/C4
PROPOSED DISCONNECT -
PROPOSED METER
12'-0
5'-0"
6-0" 1 ■ ..1'-0'
2'-2" 6'-10"
PROPOSED LOWER
COVP BOX
TRUE NORTH
2ENLARGED SITE PLAN (0.MAGE)
SCALE:
o. 1. s 10'
T - "Mobile-
12980 FOSTER, SUITE 200
OVERLAND PARK, KS 66213
PRODUCED BY:
QRI"EDS
TOWER ENGINEERING SOLUi16N5
8445 FREEPORT PARKWAY,
SLME 375
IRVING. TX 75063
PHONE: (972) 635-6238
COA / 2705 EXP. 12/31/2015
PRODUCED BY:
BR NCH
COMMUM/CA770MS,LLC
BRANCH COMMUNICATIONS
1516 S BOSTON AVE STE 215
TUSA. OnMOMA 74119
(918) 949-4551
SITE NAME:
WEST LITTLE ROCK
BTS NUMBER:
AR01218_A
SITE ADDRESS:
2525 JOHN BARROW RD
LITTLE ROCK AR 72204
PROJECT NUMBER:
AROJOSr>� o '4r,
LICEN
p I
ENG1
.J fro. 7794
PE / 7784 EXP. 12/31/2014
NO DATE DESCRIPTION
BY
7-8713114 PRELIM $SSUE
io
B ?Z101 14 PRELIM JSSUE
NDP
0000
to
NDP
^
PROPOSED H -FRAME
ATTACHED TO CONCRETE
SHEET.9:
C /
'I
PROJecr
ARO 1;
:
O
PAD, RE: 3/S1
CKOCKO
JWM
PROPOSED T -MOBILE
CABINET, RE: E3
—PPC
io
PROPOSED.
M1
, t ++ + T -MOBILE
F♦
+ t + Y SSD
N
* • CABINET + x f.c f
'
r
2'-2" 6'-10"
PROPOSED LOWER
COVP BOX
TRUE NORTH
2ENLARGED SITE PLAN (0.MAGE)
SCALE:
o. 1. s 10'
T - "Mobile-
12980 FOSTER, SUITE 200
OVERLAND PARK, KS 66213
PRODUCED BY:
QRI"EDS
TOWER ENGINEERING SOLUi16N5
8445 FREEPORT PARKWAY,
SLME 375
IRVING. TX 75063
PHONE: (972) 635-6238
COA / 2705 EXP. 12/31/2015
PRODUCED BY:
BR NCH
COMMUM/CA770MS,LLC
BRANCH COMMUNICATIONS
1516 S BOSTON AVE STE 215
TUSA. OnMOMA 74119
(918) 949-4551
SITE NAME:
WEST LITTLE ROCK
BTS NUMBER:
AR01218_A
SITE ADDRESS:
2525 JOHN BARROW RD
LITTLE ROCK AR 72204
PROJECT NUMBER:
AROJOSr>� o '4r,
LICEN
p I
ENG1
.J fro. 7794
PE / 7784 EXP. 12/31/2014
NO DATE DESCRIPTION
BY
7-8713114 PRELIM $SSUE
JPR
B ?Z101 14 PRELIM JSSUE
NDP
0 9/11/14 CONST ISSUE
NDP
SHEET TITLE:
OVERALL AND ENLARGED
SITE PLANS
SHEET.9:
C /
'I
PROJecr
ARO 1;
:
O
BY:
JWM
CKOCKO
JWM
Rim
THESE DRAWINGS ARE NOT INTENDED TO REFLECT THE STRUCTURAL
INTEGRITY OF THE TOWER. THE PROPOSED ANTENNAS AND TRANSMISSION
LINES SHOWN ARE REPRESENTATIVE IN NATURE AND 00 NOT REFLECT THE
ACTUAL CONFIGURATIONS REQUIRED. THE CONTRACTOR SHALL REFER TO THE
STRUCTURAL ANALYSIS OF THIS TOWER SITE FOR THE APPROVED LOCATION
AND CONFIGURATION OF ALL ANTENNAS AND TRANSMISSION LINES. ALL
ANTENNAS MUST BE MOUNTED AND THE TRANSMISSION LINES CONFIGURED IN
STRICT ACCORDANCE WITH THE STRUCTURAL ANALYSIS. (TOWER BY OTHERS)
TOP OF TOWER
ELEV. - 120
EXISTING ANTENNAS
T -MOBILE ANTENNAS
ELEV. - 90
2/C2
PROPOSED:
(9) NEW ANTENNAS
(1) NEW MW DISH
(5) NEW RRU'S
(2) NEW COUP/HYBRID J -BOX
(1) NEW PLATFORM W/HANDRAILS
(2) NEW 1 5/8" HYBRID UNE
(2) NEW 7/8- COAX LINE
(1) NEW 1/2' COAX MW FEEDER
PROPOSED T -MOBILE ANTENNAS
EXISTING 120' MONOPOLE
3/C2
•' PROPOSED TOWER ELEVATION
I SCALE: N.T.S.
ANDREW TMBXX-6517-A2M
ANTENNAS TYPICAL OF (9).
RE: 4/C2
(3) PROPOSED FRIG
C-1
ALPHA
AZIMUTH 0'
M-1
A-3 A-2 , FUTURE /A-1
FUTURE
FGAMMA
ZIMUTH 240 C-2
COMMSCOPE LNX 6515 DS VTM
ANTENNAS TYPICAL OF (3)
PROPOSED ALT FABRICATION PLATFORM
WITH HANDRAILS PART # 2123LD-12HR
r) ANTENNA AZIMUTH PLAN
4- SCALE: N.T.S.
CABLE NOTE:
I- HYBRID CABLE ATTACHMENTS
SHOULD FOLLOW MANUFACTURER
SPECIFICATIONS FOR ATTACHMENT
AND HANGING SPECS.
2. ROUTE COAX UP TOWER PER
STRUCTURAL ANALYSIS.
PROPOSED COAX:
(1) 1/2' MW FEE
EXISTING MONOPOi
(1) PROPOSED LARGE COVP BOX
MOUNTED TO 2 3/8" O.D. MOUNTING
PIPE AND CROSSOVER PLATE
Rw
r F. PROPOSED FXFC RRU MOUNTED ON
)
RRU MOUNTING PIPE. TYP. OF
FUTURE
-0-- COAX:
7/8" COAX CABLE
IOSED COAX:
1 5/8" HYBRID LINE
0 TRANSMISSION LINE DIAGRAM
y SCALE: N.T.S.
1/2" COAX JUMPEI
FROM RRU TO ANI
JUMPER SUPPORT
STAND-OFF WITH
CUSHION HANGERS
OR STEEL BRACKE
WITH SNAP -IN
HANGER
TRUE NORTH
(0.63' E)
MAG
A ANTENNA MOUNT DETAIL
`'I~ SCALE: N.T.S.
PROPOSED
T -MOBILE
ANTENNA
2 3/8"
O.D. PIPE
FIBER JUMPER
TO COVP BOX
#6 AWG GREEN
INSULATED GROUND
CABLE FROM RRU
TO GROUND BAR
12980 FOSTER, SUITE 200
OVERLAND PARK, KS 66213
dA A
TOWER ENGINEERING 50LUTKlN5
8445 FREMPORT PARKWAY,
SUITE 375
IRVING, TX 75063
PHONE (972) 635-8236
COA % 2705 EXP. 12/31/2015
BY:
BR NCH
COMMU, V/CA 770/VS, LL C
BRANCH COMMUNICATIONS
1516 S BOSTON AVE STE 215
TULSA, OKLAHOMA 74119
(918) 949-4551
SITE NAME:
WEST LITTLE ROCK
BTS NUMBER:
AR01218_A
SITE ADDRESS:
2525 JOHN BARROW RD
LITTLE ROCK AR 72204
•
1J�N O. 7754 �7y♦►
PE 1 7784 EXP. 17./31/([2•,014
IVO DATE I DESCRIPTION
BY
A B 13 14 PREUM ISSUE
JPR
B 9/10/14 PRELIM ISSUE
NDP
0 9 11 14 CONST ISSUE
NDP
SHEET TIRE:
TOWER ELEVATIONS
SHEET:
C
PROJECT:
AR012111-A
O
W
JWM
ANTENNA NOTES
1. ANTENNA CONTRACTOR SHALL INSURE THAT ALL ANTENNA
MOUNTING PIPES ARE PLUMB.
2. COAXIAL FEEDER & FIBER LENGTHS INDICATED ARE
APPROXIMATE.
3. ANTENNA COAXIAL FEEDERS & ANTENNA JUMPERS SHALL
BE COLOR CODED PER T—MOBILE REQUIREMENTS. IN
ADDITION TO THE COLOR CODE IN THE ANTENNA KEY
THE FOLLOWING CHECKER STRIPE SHALL BE ADDED TO
EACH ANTENNA COAXIAL FEEDER & ANTENNA JUMPER.
LTE 700 — RED—BLACK CHECKER STRIPE
LTE PCS — RED—GREEN CHECKER STRIPE
LTE AWS — YELLOW—BLACK CHECKER STRIPE
UMTS PCS — RED—WHITE CHECKER STRIPE
UMTS AWS — GREEN—WHITE CHECKER STRIPE
GSM PCS — BLACK—WHITE CHECKER STRIPE
4. MULTI PORT ANTENNAS: TERMINATE UNUSED ANTENNA
PORTS WITH CONNECTOR CAP & WEATHERPROOF
THOROUGHLY. JUMPERS FROM TMA'S MUST TERMINATE TO
OPPOSITE POLARIZATIONS IN EACH SECTOR.
5. CONTRACTOR MUST FOLLOW ALL MANUFACTURERS'
RECOMMENDATIONS REGARDING THE INSTALLATION OF
COAXIAL CABLES, CONNECTORS, AND ANTENNAS.
rd:G7:7.101191..1
LDF4-50A (1/2" HARD LINE) - 5"
FSJ4-50B (1/2- SUPER FLEX) - 1 1 /4'
AVA5-50A (7/8" HARD UNE) - TO-
AVA7-50A (1 5/8" HARD LINE) = 15"
LDF7-50A (1 5/8' HARD UNE) - 20-
7. CONTRACTOR SHALL RECORD THE SERIAL y, SECTOR,
AND POSITION OF EACH ACTUATOR INSTALLED AT THE
ANTENNAS AND FURNISH THE INFORMATION TO T—MOBILE.
8. WEATHERPROOF ALL ANTENNA CONNECTORS WITH SEL'
AMALGAMATING TAPE.
9. ANTENNA CONTRACTOR SHALL PERFORM A 'TAPE DROP"
MEASUREMENT TO CONFIRM/VALIDATE ANTENNA CENTER
UNE (ACL) HEIGHT. CONTRACTOR SHALL SUBMIT A
COMPLETED HEIGHT VERIFICATION FORM TO THE
CONSTRUCTION MANAGER.
10. ALL FIBER RUNS TO BE CONTAINED IN TWO COMMSCOPE
HYBRID DC—FIBER CABLES (MODEL MU9325TYP01)
FROM LOWER COVP TO UPPER COVP. HYBRID CABLES
SHALL BE COLOR CODED PER T—MOBIL: REQUIREMENTS.
ANTENNA SCHEDULE
SCALE: N.T.S.
12980 FOSTER, SUITE 200
OVERLAND PARK, KS 66213
BY:
01*ES.
TOWER EkGINEERINC SOLUTIONS
8445 FREEPORT PARKWAY,
SURE 375
WNG. TX 75063
PHONE: (972) 635-8238
CAA / 2705 EYP, 12/31/2015
BR NCH
C0AIMUN/C477ON3,LLC
BRANCH COMMUNICATIONS
1516 S BOSTON AVE STE 215
TULSA, OKLAHOMA 74119
(918) 949-4551
WEST LITTLE ROCK
AR01218_A
SITE ADDRESS:
2525 JOHN BARROW RD
LITTLE ROCK AR 72204
ARO
No. 7784��l
ZA?E ]�
PE 111 7784 EXP. 1
NO DATE I DESCRIPTION
BY
RRU & COUP KEY
JPR
8 9 10 14 PREUM ISSUE
NDP
ANTENNA
SECTOR
VENDOR EQUIPMENT
MODEL NO.
EQUIPMENT
ELEVATION
OTY.
STATUS
ALPHA
NOKIA RRU
FRIG
g0'
(1)
PROPOSED
BETA
NOKIA RRU
FRIG
g0'
(1)
PROPOSED
GAMMA
NOKIA RRU
FRIG
9o'
(1)
PROPOSED
ALPHA
NOKIA RRU
FRLB
go'
(1)
FUTURE
BETA
NOKIA RRU
FRLB
90'
(1)
FUTURE
GAMMA
NOKIA RRU
FRL13
90'
(1)
FUTURE
MULTI
SECTOR
NOKIA RRU
FXFC
9D'
(2)
PROPOSED
MULTI
SECTOR
RA1.1.�P Cpyp
RNSDC-7771—PF-48
9o'
(2)
PROPOSED
12980 FOSTER, SUITE 200
OVERLAND PARK, KS 66213
BY:
01*ES.
TOWER EkGINEERINC SOLUTIONS
8445 FREEPORT PARKWAY,
SURE 375
WNG. TX 75063
PHONE: (972) 635-8238
CAA / 2705 EYP, 12/31/2015
BR NCH
C0AIMUN/C477ON3,LLC
BRANCH COMMUNICATIONS
1516 S BOSTON AVE STE 215
TULSA, OKLAHOMA 74119
(918) 949-4551
WEST LITTLE ROCK
AR01218_A
SITE ADDRESS:
2525 JOHN BARROW RD
LITTLE ROCK AR 72204
ARO
No. 7784��l
ZA?E ]�
PE 111 7784 EXP. 1
NO DATE I DESCRIPTION
BY
A 15113 14 JPRELIM ISSUE
JPR
8 9 10 14 PREUM ISSUE
NDP
0 9 11 14 CONST ISSUE
NDP
SHEET TITLE:
TOWER ELEVATIONS
SHEET:
C3
PROJECT g:
ARO 1218—A
.
O
JWM
CKD:
JWM
1 1 WAVEGUIDE BRIDGE ISOMETRIC
1 SCALE: N.T.S.
(1) GPS ANTENNA
(PROVIDED EY OWI'
GPS MOUNTING PIF
mnirR.
COORDINATE GPS ANTENNA
LOCATION WITH CONSTRUCTION
MANAGER.
MAINTAIN MINIMUM BEND RADIUS
ON COAX CABLE AT ALL TIMES.
ENSURE LOCATION OF GPS
ANTENNA ALLOWS FOR CLEAR
VIEW OF SOUTHERN HORIZON.
GPS MOUNT TO BE PROVIDED
BY OWNER.
GPS ANTENNA TO BE INSTALLED
BY CONTRACTOR.
GPS ANTENNA DETAIL
'T SCALE: N.T.S.
SEAL VOID BETWEEN
PIPE AND CABLE
3/8"0 COAX CABLE
e) WAVEGUIDE BRIDGE SECTION
L SCALE: N.T.S.
ALT FABRICATION
GUIDE BRIDGE KIT
APPROVED EQUAL
EZE SUPPORT KR
COAX CABLES. ATTACH
STAINLESS STEEL
—IN HANGERS
TED GRADE
PSI
RETE PIER
LEGEND
AR01218AX—X—X—X—X
LD — LTE 700
B — LTE PCS
L — LTE AWS
P — UMTS PCS
U — UMTS AWS
G — GSM PCS
ACTUATOR NUMBER
ANTENNA NUMBER
SECTOR LETTER
CANDIDATE LETTER
SITE NUMBER
U' Ci
to
303
N N N [C N N
9gIDIA i'G,�7G 1
SS'Gt�,$ �G,�ra,•
3 RET ACTUATOR NAMING CONVENTION
SCALE: N.T.S.
T - -mobile
12980 FOSTER, SUITE 200
OVERLAND PARK, KS 66213
FS
TOWER ENGINEERING SOLURONS
8445 FREEPORT PARKWAY.
SUITE 375
IRVING, TX 75063
PHONE (972) 635-8238
COA / 2705 EXP. 12/31/2015
BR NCH
COMMU/V/C.4 T70AlS,LLC
BRANCH COMMUNICATIONS
1516 S BOSTON AVE S1E 215
TULSk OKIANOMA 74119
(916) 949-4551
WEST LITTLE ROCK
BTS NUMBER;
AR01218 A
SITE ADDRESS:
2525 JOHN BARROW RD
LITTLE ROCK AR 72204
PROJECT NUMBER-
ARO
y!
LIC
PROF N
E I R
'k,,> 7784 ,� ►�
PE / 7784 EXP. 12/31/2014
IND DATE I DESCRIPTION
BY
A 8 13 14 PRELIM ISSUE
JPR
PRELIM ISSUE
NDP
_B-9/10/14
O P/1 1 14 CONST ISSUE
NDP
SHEET TITLE:
WAVEGUIDE DETAILS
PROJECT y�:
SHE6L—
ARO 1218—A WM CJWM
O
NOTES
1. SLAB TO BE LEVEL ±1/4".
2. SLAB FOUNDATION DESIGNED ASSUMING ALLOWABLE SOIL BEARING PRESSURE OF 2000 PSF.
3. SLAB FOUNDATION DESIGNED ASSUMING MAXIMUM SOIL PLASTICITY INDEX OF 27 PER NCBC.
4. CONCRETE STRENGTH FOR FOUNDATION DESIGN SHALL BE A MINIMUM OF 3000 PSI AT 28 DAYS.
5. FOOTINGS TO EXTEND BELOW UNDISTURBED SOIL PER SITE SPECIFIC DESIGN.
6. REFER TO THE GENERAL NOTES FOR ADDITIONAL NOTES. N I'
12'-0"
TYPICAL EQUIPMENT FOUNDATION PLAN
,
2/S1
3/4" CHAMFER,
TYP. AT ALL EDGES J4 AT 12" O.C.
EACH WAY
FINISHED GRADE 6 MIL POLYETHYLENE
(CRUSHED STONE) VAPOR BARRIER
IV
io
6
�IN
"
SUB-BASE
\/
r) CONCRETE PAD DETAIL
SCALE: 4,
0'
3 1/2" SCH. 40 PIPE
PL 3/4"x5"x0'-10"
1/2"4 ANCHOR BOLTS --
EMBED 2 1/2" MIN. INTO
CONCRETE PAD WITH HILT[
HIT HY-150 MAX ADHESIVE
CONCRETE PAD --\
3 WAVEGUIDE BRIDGE POST DETAIL
SCALE:
T • •Mobileo
12980 FOSTER. SUITE 200
OVERLAND PARK, KS 66213
PRODUCED BY:
TOWER ENCINEER04 NS
8445 FREEPORT PARKWAY,
SURE 375
IRVING, TX 75063
PHONE: (972) 635-8238
COA / 2705 EXP. 12/31/2015
BY:
BR NCH
COMMUN/CAT/ONS, LLC
BRANCH COMMUNICATIONS
1516 S BOSTON AVE STE 215
TULSA, OKLAHOMA 74119
(916) 949-4551
SITE NAME:
WEST LITTLE ROCK
BTS NUMBER:
AR01218 A
SITE ADDRESS:
2525 JOHN BARROW RD
LITRE ROCK AR 72204
JAN o. 7784►��
PE / 7784 EXP. 12/3t/2014
40 DATE I DESCRIPTION
BY
A 8 I3 14 PRELIM ISSUE
JPR
B 9 10 14 PRELIM ISSUE
I4DP
0 9/11/14 CONST ISSUE
NDP
2/S1
T
4 AT 12" O.C., EACH WAY -I—�
0
1 —
6" CONCRETE SLAB
ON GRADE, RE: 2/S1
o
SHEET #:
S 1
T
1
O
8Y:
JWM
JI
I — 1
JI
I
12'-0"
TYPICAL EQUIPMENT FOUNDATION PLAN
,
2/S1
3/4" CHAMFER,
TYP. AT ALL EDGES J4 AT 12" O.C.
EACH WAY
FINISHED GRADE 6 MIL POLYETHYLENE
(CRUSHED STONE) VAPOR BARRIER
IV
io
6
�IN
"
SUB-BASE
\/
r) CONCRETE PAD DETAIL
SCALE: 4,
0'
3 1/2" SCH. 40 PIPE
PL 3/4"x5"x0'-10"
1/2"4 ANCHOR BOLTS --
EMBED 2 1/2" MIN. INTO
CONCRETE PAD WITH HILT[
HIT HY-150 MAX ADHESIVE
CONCRETE PAD --\
3 WAVEGUIDE BRIDGE POST DETAIL
SCALE:
T • •Mobileo
12980 FOSTER. SUITE 200
OVERLAND PARK, KS 66213
PRODUCED BY:
TOWER ENCINEER04 NS
8445 FREEPORT PARKWAY,
SURE 375
IRVING, TX 75063
PHONE: (972) 635-8238
COA / 2705 EXP. 12/31/2015
BY:
BR NCH
COMMUN/CAT/ONS, LLC
BRANCH COMMUNICATIONS
1516 S BOSTON AVE STE 215
TULSA, OKLAHOMA 74119
(916) 949-4551
SITE NAME:
WEST LITTLE ROCK
BTS NUMBER:
AR01218 A
SITE ADDRESS:
2525 JOHN BARROW RD
LITRE ROCK AR 72204
JAN o. 7784►��
PE / 7784 EXP. 12/3t/2014
40 DATE I DESCRIPTION
BY
A 8 I3 14 PRELIM ISSUE
JPR
B 9 10 14 PRELIM ISSUE
I4DP
0 9/11/14 CONST ISSUE
NDP
SHEET TITLE:
CONCRETE PAD
DETAILS
SHEET #:
S 1
PROJECT
AR01218J1
O
8Y:
JWM
KD:
JWM
x
PROPOSED (1) 3" PVC CONDUIT FOR
POWER FROM POWER POLE TO T -MOBILE
POWER METER ON UTILITY RACK (IN
§ COMMON TRENCH WITH TELCO). VERIFY
CONDUIT SIZE WITH POWER COMPANY.
PROPOSED 2" PVC CONDOR FOR FIBER/TELCO�4
FROM SOURCE TO T -MOBILE UTILITY RACK. $
VERIFY CONDUIT SIZE WITH TELCO COMPANY. 1
EXISTING
.-O.
WOOD GATE
r PROPOSED T -MOBILE
J 10'-0"x12'-0" CONCRETE
EQUIPMENT PAD AND
I EXISTING LEASE AREA
EXISTING ICE
BRIDGE
AT&T
J
o
SHELTER
�
Z
SHEET TITLE:
UTILITY PLAN $ CONDUIT
LAYOUT DIAGRAM
:SHEET #:
PROJECT #:
REV:
_ J
EXISTING ICE
BRIDGE
I I EXISTING
H -FRAME
T I EXISTING
AT&T
x L SHELTER
r t�
� L
1
r
X x x—
II PROPOSED T -MOBILE x
SSC CABINET
II PROPOSED T -MOBILE
23'-0" ICE BRIDGE
- EXISTING -
EMPTY ; EXISTING 8'-0"
CONCRETE
PAD i rd Ix WOOD FENCE
y0
EXISTING TLE ng I
BRIDGE
EXISTING 120'
MONOPOLE
7 g ilZo
EXISTING
w w H -FRAME
I O
X x x X
1 UTILITY ROUTING PLAN
SCALE:
17 10' 20' 30' 4W
PROPOSED RAINTIGHT
EMT POWER/TELCO
CONDUITS ANCHORED TO
SIDE OF CONCRETE PAD
PROPOSED RAINTIGHT
EMT POWER/TELCO
CONDUITS ANCHORED TO
SIDE OF CONCRETE PAD
PROPOSED T -MOBILE jI
PPC CABINET, RE: E3 I I
11
PROPOSED SSC CABINET I I
I
i PROPOSED 2" RAINTIGHT I
CONDUIT WITH PULL STRING I I
FROM PPC CABINET TO SSC
CABINET, RE: 4/E2 I I
II
-s �_ - _ -- - --�
07 ENLARGED UTILITY ROUTING PLAN
L SCALE: N.T.S.
SSC
Conduit Layout
New NODE 8 L1 RRU s
Cant Go On The Tower
Teko CorrduR
— . RC P&*f Conches
nr oNye. w.v,.ryfAne,
0 SSC CONDUIT LAYOUT
SCALE: N.T.S.
T . -Mobile.
12980 FOSTER, SUITE 2DO
OVERLAND PARK, KS 66213
0
ES
TOWER ENCINUTIONS
8445 FREF.PORT PARKWAY,
SUFFE 375
IRVING, TX 75063
PHONE: (972) 635-8238
COA / 2705 EXP. 12/31/2015
BY:
BR HIGH
COMMUN/CAT/ONS,LLC
BRANCH COMMUNICATIONS
1516 S BOSTON AVE STE 215
TULSA OKLAHOMA 74119
(918) 949-4551
SITE NAME:
WEST LITTLE ROCK
BTS NUMBER:
AR01218 A
2525 JOHN BARROW RD
LITTLE ROCK oWa
� pNo. 7784,+ f
d r
ar +�E
PE / 7784 EXP. 12/31/2014
JO DATE I DESCRIPTION BY
A 8 13 14 PRELIM ISSUE JPR
9/10/14 PRELIM ISSUE NDP
=9/10/1
11 14 CONST ISSUE NDP
NB
SHEET TITLE:
UTILITY PLAN $ CONDUIT
LAYOUT DIAGRAM
:SHEET #:
PROJECT #:
REV:
13Y: CKD:
JWM JWM
nill
2" RIGID CONDOR/PVC —
BELOW GRADE TO POWER
SOURCE
)POSED GPS ANTENNA,
LD VERIFY ACTUAL LOCATION
VEGUIDE COVER
N T—MOBILE LED FLOOD LIGHT
MANUAL TIMER SWITCH
TALLEO 8'-0' ABOVE PAD
MOBILE SUPPLIED RECEPTACLE
RIGID CONDUIT ABOVE
4DE/PVC BELOW GRADE
t (2) 02 THHN GRD
LDS
RIGID CONDUIT ABOVE GRADE/PVC
.OW GRADE FOR (2) 12 THHN
) LEADS
RIGID CONDUIT ABOVE
4DE/PVC BELOW GRADE FOR
TO TELCO/POWER DEMARC
~� 1" RIGID CONDUIT ABOVE GRADE/PVC
BY
PROPOED FIELD
PROPOSED METER
r
3" GALVANIZED RIGID PIPE
VERIFYSACTUALCLOCAT100N
T—MOBILE SUPPLIED RECEPTACLE
2 RIGID POWER CONDUIT/PVC
1-5/8" GALVANIZED PROPOSED GPS ANTENNA,
FIELD VERIFY ACTUAL LOCATION
BELOW GRADE TO POWER SOURCE
UNI—STRUT
—F
NEW T—MOBILE LED FLOOD LIGHT
SHEET #:
E 3
PROPOSED GPS ANTENNA,
WITH MANUAL T)MER SWITCH
FIELD VERIFY ACTUAL LOCATION
1' RIGID CONDUIT ABOVE
INSTALLED 8'-0" ABOVE PAD
RR BELOW DE
o
FOR (2)#2 THHN GRD
NEW T—MOBILE LED FLOOD
PROPOSED DISCONNECT,
LEADS
—
T
LOCATION
r PROPOSED ICE BRIDGE
2" RIGID CONDOR/PVC —
BELOW GRADE TO POWER
SOURCE
)POSED GPS ANTENNA,
LD VERIFY ACTUAL LOCATION
VEGUIDE COVER
N T—MOBILE LED FLOOD LIGHT
MANUAL TIMER SWITCH
TALLEO 8'-0' ABOVE PAD
MOBILE SUPPLIED RECEPTACLE
RIGID CONDUIT ABOVE
4DE/PVC BELOW GRADE
t (2) 02 THHN GRD
LDS
RIGID CONDUIT ABOVE GRADE/PVC
.OW GRADE FOR (2) 12 THHN
) LEADS
RIGID CONDUIT ABOVE
4DE/PVC BELOW GRADE FOR
TO TELCO/POWER DEMARC
~� 1" RIGID CONDUIT ABOVE GRADE/PVC
BY
BELOW GRADE FOR (2) N2 THHN
JPR
GRD LEADS
NDP
T—MOBILE SUPPLIED RECEPTACLE
NDP
2" RAINTIGHT EMT POWER/TELCO
CONDUIT ANCHORED TO SIDE OF
CONCRETE PAD TO SSC CABINET
SHEET TITLE;
PPC H -FRAME DETAILS
SHEET #:
E 3
PROPOSED GPS ANTENNA,
REV:
4
FIELD VERIFY ACTUAL LOCATION
ir
WAVEGUIDE COVER
71
1-5/8- GALVANIZED
UNI—STRUT
NEW T—MOBILE LED FLOOD
PROPOSED DISCONNECT,
LIGHT W/ MANUAL TIMER SWITCH
FIELD VERIFY ACTUAL
INSTALLED 8'-0" ABOVE PAD
LOCATION
PPC CABINET
PROPOSED METER i
(2) 2" RIGID CONDUIT ABOVE —
GRADE/PVC BELOW GRADE FOR
PPC TO TELCO/POWER DEMARC
CONCRETE PAD
f ��i1=�1�=1lE=1fI,=1iI==f1l�lll=l!l�i4€-ill;;-11I;;`�2" RAiNTic;Kr I •"���. ..,--��
FRONT VIEW CONDUITANCHO ED TOTELCOSIDEWOF ER SIDE VIEW
PPC H -FRAME DETAILS CONCRETE PAD TO SSC CABINET
SCALE: N.T.S.
T • •Mobile-
12980 FOSTER, SUITE 200
OVERLAND PARK, KS 66213
Ohm 0
TOWER ENGIN NS
8445 FREEPORT PARKWAY,
SUITE 375
IRVING. TX 75063
PHONE: (972) 635-8238
COA j 2705 EXP. 12/31/2015
BY:
BR NCH
COMMUN/CA7%ONS,LLC
BRANCH COMMUNKJRK)NS
1516 S BOSTON AVE STE 215
TUIS4. OKW40MA 74119
(918) 949-4551
SITE NAME:
WEST LITTLE ROCK
BTS NUMBER:
AR01218_A
SITE ADDRESS:
2525 JOHN BARROW RD
LITTLE ROCK AR 72204
PROJECT N W-"'.
* LIC x S
PRO NAL
ENGINE R
J No. 7784 r��7►�
l
PE j 7784 EXP. 12/31/2014
NO DATE DESCRIPTION
BY
7'781V 14 PRELIM ISSUE
JPR
B ? l0114 PRELIM ISSUE
NDP
0 9/11/14 CONST TSSUE
NDP
SHEET TITLE;
PPC H -FRAME DETAILS
SHEET #:
E 3
13ROJECT :
AR01218—A
REV:
4
I WM CJWM
RE: 1/G2 AND 4/G3
FOR ANTENNA
GROUNDING DETAIL
EXISTING
AT&T
SHELTER
RE: 4/G2 FOR TYPICAL
CADWELD DETAILS
PROPOSED CONCRETE PAD GROUND -- (FROM EQU
RING, RE: 3/G2 AND 1/G3 ® GROUND TEST WELL AT GROUND ROD
• •—• — CHAIN LINK FENCE
#2 AWG BARE SOLID TINNED 1♦ 5/8-x8'-0- COPPER CLAD GROUND ROD
COPPER CABLE TO GROUNDING AT 15'-0' MAX. SPACING, PER CM
SYSTEM (TYP.), RE: 2/G2
______�_�_�_�_� - PROPOSED GROUND
\ TEST WELL. RE. 6/13
J
i
1
:
AR01218..-A
O
JWM
CKD:
JWM
GROUNDING LEGEND:
SYMBOL DESCRIPTION
EXOTHERMIC WELD (CADWELD)
02 AWG BCW
■ MECHANICAL CONNECTION
—"— #2 STRANDED INSULATED
IPMENi TO MGB)
2
(30
I
HW
1
O 5/8' COPPER CLAD GROUND ROD
O AT EACH CORNER, RE: 5/G2
%%%+
- $2 AWG BARE SOLID ' t ICE BRIDGE FF
TINNED COPPER CABLE I
TO GROUNDING SYSTEM
FOR ICE BRIDGE POSTS
(TYP.), RE: 2/G2+
_ f
+ f + + f i +y + + +' ► +
+ + + + + + + + + + + + f + {
/
F++++7++
++ +++++++++ ++ + +++++++++++++++ ++++'+d.+'+++ + ++ + + +++ +++++}+}++++++i++++++++++++++ } ++ + + ��� �_ — �� tel•
PROPOSED TOWER
GROUND BAR, RE: 3/G3 /
+++ + + + + + + + + + + + + +
! � EXISTING ICE
BRIDGE
O O
O
+ + +
+ + + + + PAD + + + + + + + + + + +
z��
woa
• Q O Ct EXISTING 120'
MONOPOLE -
TRUE NORTH
EXISTING
TOWER GROUND RING (0.63' E)
MAG
COMPOUND GROUNDING PLAN
........... ..........
.++. ... .......
SCALE:
5' 10'
EXISTING + + + + + + + + + + + +
+ + + - -CONCRETE + + + + + + + r + +
12980 FOSTER, SUITE 200
OVERLAND PARK, KS 66213
TOWER ENGINEERING SMUTIOM
8445 FREEPDRT PARKWAY,
SUITE 375
RIVING, TX 75083
PHONE (972) 633-8238
COA j 2705 EXP.
12/31/2015
BR NDN
COMMON/CAT/ONS,LLC
BRANCH COMMUNICATIONS
1518 S BOSTON AVE STE 215
TULSA, OKLA}10AIA 74118
(818) 949
-4551
WEST LITTLE ROCK
HTS NUMBER:
AR01218_A
SITE ADDRESS:
2525 JOHN BARROW RD
LITTLE ROCK AR 72204
PROJECT NUMBER:
ARO 2#., 4
AR s r
I
LI A00 tL
L
PRO
ENGi ER
` * * R k
PE / 7784 EXP.
1$/31/2014
VO DATE DESCRIPTION BY
A 13 141PRELIM ISSUE JPR
8 9/10/14 IPREUM ISSUE NDP
0 9/11/14 CONST ISSUE NDP
s"&MPOUND
GROUNDING PLAN
SHEET PROJECT BYz #
1
:
AR01218..-A
O
JWM
CKD:
JWM
ANTENNA I ANTENNA 2 ANTENNA 3
ANTENNA MOUNT
(TYP.) `—
ANTENNA (TYP.)
I —RRU
RRU —
r TOWER TOP COVP BOX
CABLE GROUNDING I 1 I I COLLECTOR BUS BAR
KR, RE: 2/G3 (TYP.) j (GROUNDED TO TOP
OF TOWER).
HYBRID CABLE (TYP.) L _ LL COLLECTOR BUS BAR
r — (GRO D TTO MOWER I OR 2 AWG TSBC GROUND WIRE
TOWERS OVER 200').
COVP BOX AT
WAVEGUIDE BRIDGE METAL CABINETS SUCH 3/4- FLEX CONDUIT —
AS POWER, TELCO, SLEEVE
— — — — — DISTRIBUTION PANEL,
BUSS BAR MOUNTED WAVEGUIDE BRIDGE
WITH INSULATORS D r SUPPORTS, EQUIPMENT FINISHED GRADE
BASE OF TOWER I SUPPORT, PLATFORM,
I ETC.
MODULAR —INTERNAL EQUIPMENT s
-- CELL GROUND BUS BAR
I.. .... CABINET
I
WAVEGUIDE BRIDGE I I """ 1 SUPPLEMENTARY
GROUND BUS BAR I j INET FRAME I GROUND WIRE
MOUNTED AT I
WAVEGUIDE BRIDGE
MAIN GROUND RING
r caowELD (TYP.)
A TOWER GROUNDING RISER DETAIL
SCALE: N.T.S.
TYPE PT TYPE HS TYPE YA-2 TYPE VS
TYPE SS TYPE VBC TYPE YGHC
A TYPICAL CADWELD DETAILS
`'F SCALE: N.T.S.
TO MAIN GROUND RING
2 STUB UP DETAIL
SCALE: N.T.S.
COPPER GROUND ROD
(5/8"x8'-0- LONG)
5 COPPER -CLAD STEEL GROUNDING ROD
SCALE: N.T.S.
0
lI
V
f3 GROUND RING DETAIL
SCALE: N.T.S.
0% GROUND TEST WELL DETAIL
U SCALE: N.T.S.
FINISHED GRADE
AGGREGATE SURFACE
#2 AWG SOLID BARE
TINNED COPPER
EXTERIOR GROUND
RING
EXOTHERMIC WELD
TO GROUND ROD
GROUND ROD
(TYP.), RE: 5/G2
6'x24" DEEP INSPECTION
SLEEVE. PVC OR SOIL PIPE
WITH CAP OR EQUIVALENT.
CADWELI) CO""VPTMM
(TYPE—GT)
1" WIDE SLOT FOR
GROUND WIRE EXTEND
2" ABOVE GROUND WIRE
#2 AWG SOLID TINNED
COPPER WIRE (EXTERIOR
GROUND RING)
3/4" CRUSHED STONE OR
EQUAL FILL TEST WELL TO
WITHIN 2" OF TOP OF
GROUND LOOP WIRE
5/8700' LONG COPPER
CLAD GROUND ROD
,-P • .Mobile•
12980 FOSTER, SUITE 200
OVERLAND PARK, KS 66213
14
EVI
lio
TOWER ENG1N� NS
8445 FREEPORT PARKWAY.
SURE 375
IRVING, TX 75063
PHONE: (972) 635-8238
COA / 2705 EXP. 12/31/2015
BY:
BR NCH
COMMUN/CA77ON3,LLC
BRANCH COMMUNICADONS
1516 S BOSTON AVE SIE 215
TULSA, OKLMOMA 74119
(918) 949-4551
WEST LITTLE ROCK
AR01218_A
2525 JOHN BARROW RD
LITTLE ROCK AR 72204
a. 7784 �, ���
PE E 7784 EXP. 12/31/2014
NO DATE DESCRIPTION
BY
7_8713214 PRELIM ISSUE
JPR
8 9/10/14 PRELIM ISSUE
NOP
0 9 11 14 CONST ISSUE
NDP
SHEET TITLE:
GROUNDING DETAILS
SHEET 1:
G2
PRDJECT
ARO121B—A
:
0
J:
JWM
CKD:
JWM
Is
PROPOSED —
SSC CABINET
1 5/8' GALVANIZED UNI—STRUT
3' GALVANIZED PIPE
FURNISH AND INSTALL #2 —
THHN CU GROUND WIRE
FROM GROUND LOOP TO
TELCO GROUND BAR IN PPC
FURNISH AND INSTALL #2 THHN CU —
GROUND WIRE WEATHER SEALED IN
RIGID CONDUIT FROM PPC GROUNDING
ELECTRODE CONDUCTOR TERMINAL TO
GROUND LOOP
#2 BARE SOLID TINNED #2 BARE SOLID
CU GROUND WIRE I TINNED CU
GROUND WIRE VVV
FURNISH AND INSTALL FURNISH AND INSTALL
02 BARE SOLID TINNED 2/0 INSULATED PIGTAIL
CU GROUND WIRE (1) PER CABINET
EQUIPMENT GROUNDING RISER DIAGRAM
SCALE: N.T.S.
TO ANTENNA
CONNECTOR TO JUMPER
OR ANTENNA
COAX CABLE
I
4'
i
I
Q COAX CABLE
0 GROUNDING CLAMP KIT
INSTALLATION OF BUTYL do
TAPE PER MANUF. SPEC'S
PROVIDED IN GROUND KITS
#6 AWG GROUNDING
/ CONDUCTOR
f/ TO GROUND BUS BAR
TO CABINET
CONNECTION OF CABLE
GROUND KIT TO ANTENNA CABLE
4— SCALE: N.T.S.
TERMINATION GROUND BAR
FURNISH AND INSTALL 2/0 INSULATED
GROUND WIRE FROM GROUND LOOP TO
MASTER GROUND BARS
r ` ` BOND WAVEGUIDE BRIDGE SUPPORT POSTS TO
GROUND LOOP WITH 02 BARE SOLID TINNED
}� CU GROUND WIRE CADWELD CONNECTION
T k BOND TO EXISTING CONDUCTOR WITH 02
BARE SOLD TINNED CU GROUND WIRE
NOTE:
BUSS BAR TO BE SPRAYED
WITH COLD GAL ONCE ALL
CONNECTIONS ARE COMPLETED.
#6 AWG FROM ANTENNA
MOUNTS AND EQUIPMENT
GROUNDING (RE: 1/G2
FOR OTY)
LUG,
L CONTRACTOR TO SPRAY GROUND
BAR WITH COLD GALVANIZE ONCE
ALL CONNECTIONS ARE COMPLETED
3 GROUND BAR DETAIL
SCALE: N.T.S.
PROPOSED GROUND BAR
GROUNDED TO TOWER
C-1
(2) #6 AWG INSULATED
STRANDED COPPER FOR HOME
RUN TO GROUND BUSS BAR
A ANTENNA GROUNDING PLAN
"t SCALE: N.T.S.
12980 FOSTER, SUITE 200
OVERLAND PARK, KS 66213
TOWER MINNMING K3N5
8445 FREOVRT PARKWAY,
SUrIl 375
IRVING, TX 75053
PHONE: (972) 635-8238
COA / 2705 EXP. 12/31/2015
BR NCH
COMAE /A//CATONS.LLC
BRANCH COMMUNICATIONS
1516 S BOSTON AVE STE 215
TULSA, OKLAHOMA 74119
(919) 948-4551
WEST LITTLE ROCK
BTS NUMBER:
AR01218_A
S17E ADDRESS:
2525 JOHN BARROW RD
LITTLE ROCK AR 72204
PROFESSION PtL
B-3 ENGINEER
Le'
o. 7784 Tit
_IIF REr�►�
tf B-2
#6 AWG INSULATED
STRANDED COPPER
FOR EQUIPMENT
j GROUNDING, TYP.
FUTURE
TRUE NORTH
(0.63' E)
MAG
PE 1 7754 EXP. 12/31/2014
JO DATE I DESCRIPTION
BY
A B 13 14 PRELIM ISSUE
JPR
B 9 10 14 PRELIM ISSUE
NDP
0 9 11 14 CONST ISSUE
NDP
SHEET TITLE:
GROUNDING DETAILS
SHEET #:
G 3
PROJECT #:
AR012111—A
O
JWM
CJWM