HomeMy WebLinkAboutZ-4432-B Map 3GENERAL NOTES
1. FOR THE PURPOSE OF CONSTRUCTION DRAWING, THE FOLLOWING DEFINITIONS SHALL APPLY:
CONTRACTOR — BECHTEL
SUBCONTRACTOR — GENERAL CONTRACTOR (CONSTRUCTION)
OWNER — AT&T WIRELESS SERVICES.
2. PRIOR TO THE SUBMISSION OF BIDS. THE BIDDING SUBCONTRACTOR SHALL VISIT THE CELL SITE TO
FAMILIARIZE WITH THE EXISTING CONDITIONS AND TO CONFIRM THAT THE WORK CAN BE ACCOMPLISHED AS
SHOWN ON THE CONSTRUCTION DRAWINGS. ANY DISCREPANCY FOUND SHALL, BE BROUGHT TO THE
ATTENTION OF CONTRACTOR.
3. ALL MATERIALS FURNISHED AND INSTALLED SHALL BE IN STRICT ACCORDANCE WITH ALL APPLICABLE
CODES, REGULATIONS, AND ORDINANCES. SUBCONTRACTOR SHALL ISSUE ALL APPROPRIATE NOTICES AND
COMPLY WITH ALL LAWS. ORDINANCES. RULES, REGULATIONS, AND LAWFUL ORDERS OF ANY PUBLIC
AUTHORITY REGARDING THE PERFORMANCE OF THE WORK.
ALL WORK CARRIED OUT SHALL COMPLY WITH ALL APPLICABLE MUNICIPAL AND UTIUTY COMPANY
SPECIFICATIONS AND LOCAL JURISDICTIONAL CODES, ORDINANCES AND APPLICABLE REGULATIONS.
4. DRAWINGS PROVIDED HERE ARE NOT TO BE SCALED AND ARE INTENDED TO SHOW OUTLINE ONLY.
5. UNLESS NOTED OTHERWISE, THE WORK SHALL INCLUDE FURNISHING MATERIALS, EQUIPMENT,
APPURTENANCES, AND LABOR NECESSARY TO COMPLETE ALL INSTALLATIONS AS INDICATED ON THE
DRAWINGS.
6. 'KITTING USY SUPPLIED WITH THE BID PACKAGE IDENTIFIES ITEMS THAT WILL BE SUPPLIED BY
CONTRACTOR. ITEMS NOT INCLUDED IN THE BILL OF MATERIALS AND KITTING LIST SHALL BE SUPPLIED
ELY THE SUBCONTRACTOR.
7. THE SUBCONTRACTOR SHALL INSTALL ALL EQUIPMENT AND MATERIALS IN ACCORDANCE WITH
MANUFACTURER'S RECOMMENDATIONS UNLESS SPECIFICALLY STATED OTHERWISE
8. IF THE SPECIFIED EQUIPMENT CANNOT BE INSTALLED AS SHOWN ON THESE DRAWINGS, THE
SUBCONTRACTOR .HALL PROPOSE AN ALTERNATIVE INSTALLATION SPACE FOR APPROVAL BY THE
CONTRACTOR.
9. SUBCONTRACTOR SHALL DETERMINE ACTUAL ROUTING OF CONDUIT, POWER AND T1 CABLES, GROUNDING
CABLES AS SHOWN ON THE POWER. GROUNDING AND TELCO PLAN DRAWING. SUBCONTRACTOR SHALL
UITLIZE EXISTING TRAYS AND/OR SHALL ADD NEW TRAYS AS NECESSARY. SUBCONTRACTOR SHAf.L
CONFIRM THE ACTUAL ROUTING WITH THE CONTRACTOR.
10. THE SUBCONTRACTOR SHALL PROTECT EXISTING IMPROVEMENTS, PAVEMENTS, CURBS, LANDSCAPING AND
STRUCTURES. ANY DAMAGED PART SHALL BE REPAIRED AT SUBCONTRACTOR'S C(PE NSE TO THE
SATISFACTION OF OWNER.
11, SUBCONTRACTOR SHALL LEGALLY AND PROPERLY DISPOSE OF ALL SCRAP MATERIALS SUCH AS COAXIAL
CABLES AND OTHER ITEMS REMOVED FROM THE EXISTING FACILITY. ANTENNAS REMOVED SHALL BE
RETURNED TO THE OWNER'S DESIGNATED LOCATION.
12. SUBCONTRACTOR SHALL LEAVE PREMISES IN CLEAN CONDITION.
13. ALL CONCRETE REPAIR WORK SHALL BE DONE IN ACCORDANCE WITH AMERICAN CONCRETE INSTITUTE
(ACI) 301.
14. ANY NEW CONCRETE NEEDED FOR THE CONSTRUCTION SHALL HAVE 4000 PSI STRENGTH AT 28 DAYS.
ALL CONCRETING WORK SHALL BE DONE IN ACCORDANCE WITH ACI 318 CODE REQUIREMENTS.
15. ALL STRUCTURAL STEEL WORK SHALL BE DONE IN ACCORDANCE WITH RISC SPECIFICATIONS.
16. CONSTRUCTION SHALL COMPLY WITH SPECIFICATION 24623-033-3PS—AOOZ-00002. 'GENERAL
CONSTRUCTION SERVICES FOR CONSTRUCTION OF AWS 3G SITES.'
17. SUBCONTRACTOR SHALL VERIFY ALL EXISTING DIMENSIONS AND CONDITIONS PRIOR TO COMMENCING ANY
WORK. ALL DIMENSIONS OF EXISTING CONSTRUCTION SHOWN ON THE DRAWINGS MUST BE VERIFIED.
SUBCONTRACTOR SHALL NOTIFY THE CONTRACTOR OF ANY DISCREPANCIES PRIOR TO ORDERING MATERIAL
OR PROCEEDING WITH CONSTRUCTION.
16. THE EMSTING CELL SITE IS IN FULL COMMERCIAL OPERATION. ANY CONSTRUCTION WORK BY
SUBCONTRACTOR SHALL NOT DISRUPT THE EXISTING NORMAL OPERATION. ANY WORK ON COSTING
EQUIPMENT MUST BE COORDINATED WITH CONTRACTOR. ALSO. WORK SHOULD BE SCHEDULED FOR AN
APPROPRIATE MAINTENANCE WINDOW USUALLY IN LOW TRAFFIC PERIODS AFTER MIDNIGHT.
19. SINCE THE CELT. SITE IS ACTIVE. ALL SAFETY PRECAUTIONS MUST BE TAKEN WHEN WORKING AROUND
HIGH LEVELS OF ELECTROMAGNETIC RADIATION, EQUIPMENT SHOULD BE SHUTDOWN PRIOR TO
PERFORMING MAY WORK THAT COULD EXPOSE THE WORKERS TO DANGER. PERSON& RF EXPOSURE
MDNTTORS ARE ADVISED TO BE WORN TO ALERT OF ANY DANGEROUS EXPOSURE LEVELS.
APPRC"ED �:D��W";:' -; i v
r / �A t
400
^F3TI'iGil': "ciffI Y`G�-Fl,U10ilr3T1 �'t CFPT31TTIix.r t:CIOR vAdv DEVI FR',=s;Ji APPROVED
SITE PLAN VOIDS THIS PERIAIT.
j� BECHTEL KAVANAUGH
(� TELECOMMUNICATIONS SITE NO. LTRK1-065
L] 4700 S. BOWMAN ROAD, SUITE 700 3000 OZARK POINT
!�f LITTLE ROCK, AR. 72210 LITTLE ROCK, AR 72205
g-r'7w__w r .... -r.
SCOPE OF WORK: UNMANNED TELECOMMUNICATIONS FACILITY MODIFICATIONS
SITE ADDRESS:
3000 OZARK POINT
LITTLE ROCK, AR 72205
LATITUDE:
34 45 26.23
LONGITUDE
—92 18 32.77
JURISDICTION:
CITY OF' LITTLE ROCK
CURRENT USE
TELECOMMUNICATIONS FACILITY
PROPOSED USE
TELECOMMUNICATIONS FACILITY
TYPE STRUCTURE
GUYED TOWER
ANTENNA CENTER LINE:
144' _
DRAWING INDEX REV
LTR -065-01 TITLE SHEET 1
LTR4)65-02 POWER GROUNDING AND TELCO PLAN 1
LTR465-03 AC POWER, T1 CABLE AND GROUNDING SCHEMATIC 1
LTR4065-04 DETAILS 1
LTR4)65-05 DETAILS 0
LTR -M-06 DETAILS 0
LTR -065-07 ANTENNA ELEVATION, DETAILS & ORIENTATION 0
LTR -065-08 ANTENNA DETAILS AND BILL OF MATERIAL 0
VICINITY MAP
DIRECTIONS: TAKE 1-630 FAST TO THE FAIR PARK EXIT, GO NORTH AND TURN RIGHT ON MARKHAM. TURN
ON COLONIAL AND RIGHT ON KAVANAUGH. TURN LEFT ON MARTIN, GO APPROXIMATELY 1 1/2
BLACKS, SITE WILL BE ON RIGHT AT WATERWORKS
6 1 5 1 4
AT&T
AT&T WIRELESS SERVICES, INC.
900 SOUTH SHACKLE -D• SURE 500
LITRE RO:K, M 72211
3
AT&T
GSM OVERLAY
PROJECT
AT&T WIRELESS
SITE NUMBER: LTRK1-065
SITE NAME: KAVANAUGH
(POWER, GROUNDING, TELCO & MISC. CIVIL)
APPLICABLE BUILDING CODES AND STANDARDS
SUBCONTRACTOR'S WORK SHALL COMPLY WITH ALL APPLICABLE NATIONAL. STATE, AND LOCAL
CODES AS ADOPTED BY THE LOCAL AUTHORITY HAVING JURISDICTION (AHJ) FOR THE LOCATION.
THE EDITION OF THE AHJ ADOPTED CODES AND STANDARDS IN EFFECT ON THE DATE OF
CONTRACT AWARD SHALL GOVERN THE DESIGN.
BUILDING CODE
[UNIFORM BUILDING CODE (UBC), LATEST EDITION]
ELECTRICAL CODE:
[NATIONAL FIRE PROTECTION ASSOCIATION (NFPA) 70 — LATEST EDITION, NATIONAL ELECTRICAL
CODE]
LIGHTNING PROTECTION CODE:
[NFPA 780 — LATEST EDITION, UGHTNING PROTECTION CODE]
SUBCONTRACTOR'S WORK SHALL COMPLY WITH THE LATEST EDITION OF THE FOLLOWING
STANDARDS.
AMERICAN CONCRETE INSTITUTE (ACI) 318, BUILDING CODE REQUIREMENTS FOR STRUCTURAL
CONCRETE
AMERCM INSTITUTE OF STEEL CONSTRUCTION (RISC), MANUAL OF STEEL CONSTRUCTION, ASD,
NINTH EDITION
TELECOMMUNICATIONS INDUSTRY ASSOCIATION CTIA) 222—F. STRUCTURAL STANDARD FOR
STRUCTURAL ANTENNA TOWER AND ANTENNA SUPPORTING STRUCTURES
INSTITUTE FOR ELECTRICAL AND ELECTRONICS ENGINEERS (IFT-E) 81, GUIDE FOR MEASURING EARTH
RESISTIVITY, GROUND IMPEDANCE, AND EARTH SURFACE POTENTIALS OF A GROUND SYSTEM
IEEE 1100 (1999) RECOMMENDED PRACTICE FOR POWERING AND GROUNDING OF ELECTRONIC
EQUIPMENT
IEEE C62.41, RECOMMENDED PRACTICES ON SURGE VOLTAGES IN LOW VOLTAGE AC POWER
CIRCUITS (FOR LOCATION CATEGORY 'C3' AND -HIGH SYSTEM EXPOSURE-)
TLA 607 COMMERCIAL BUILDING GROUNDING AND BONDING REQUIREMENTS FOR
TELECOMMUNICATIONS
TELCORDLA GR -63 NETWORK EQUIPMENT—BUILDING SYSTDd (NEBS): PHYSICAL PROTECTION
TELCORDLA GR -347 CENTRAL OFFICE POWER WIRING
TELCORDLA GR -1275 GENERAL INSTALLATION REQUIREMENTS
TELCORDLA GR -1503 COAXIAL CABLE CONNECTIONS
FOR ANY CONFLICTS BETWEEN SECTIONS OF LISTED CODES AND STANDARDS REGARDING MATERIAL,
METHODS OF CONSTRUCTION, OR OTHER REQUIREMENTS, THE MOST RESTRICTIVE REQUIREMENT
SHALL GOVERN. WHERE THERE IS CONFLICT BETWEEN A GENERAL REQUIREMENT AND A SPECIFIC
REQUIREMENT. THE SPECIFIC REQUIREMENT SHALL. GOVERN,
AT&T WIRELESS
TITLE SHEET
NOKIA OUTDOOR
SITE DRAWING
AKA1 24623-954 LTR -065-01
2
ff
C
V
A
1 0f/17/Ob F&VOID POrlk'h anaKB m RFsAFS
D 1 msum FCR CONSTRVCI1011 ARA RFS
RFS
MO. DATE REVISIONS Iif CHK
APP"D
Sr'y K` AS SHOWN DESKA1m RFS =Mft
AT&T WIRELESS
TITLE SHEET
NOKIA OUTDOOR
SITE DRAWING
AKA1 24623-954 LTR -065-01
2
ff
C
V
A
d
:02
m
L
ZO-990-ILLI *96-STW
SNIMVVO US
HOW= VI)1ON
NVId 0313L ONV ONIONnOHO Mod
SS3l3HIM IVIV
Z
ti 1 S 1 9
VA :Nwm sm zamriwq Kwa Sv�3110`8
<<ZZL W •NON nun
ooa mins •adonlAWHS —OS 005
ONI'S33MSSS3l3HIM181V
�
lI?l%f ��
9OZZL HV 'MOOH Min
lNIOd MUM 000£
S9o-DIliLl 'ON 311S
HonvmvAlnl
OLZZL 'HV ')1008 3111n
OOL 311nS 'OV08 NY'S OOL4 ;
SNOI1bJINfIWwoWOJ3l31
13IM039
i A9 SNOISIA3N �
pw Noaorrosw)o mm moss zo/oz/z10
� sires NNW MMPM CQ/«/10 +
a01OYN wosns 'dlno3 3HnLnd
AS a3TWISNl V (INSINUM 313
Ol AVM33Va aw saolonONOO dlnb3 a3SOdOHd
AVN! TIM 'ISIM 'dlnm '1SIX3
aN303l
SIN
Mdld 1f10"1311S
X X X X X X X�X X X X X
ammo! 31110
a3Ano
VNla'Nne
ONLLSI)C3
tQ 9Q
90S 11YI30 33S
SSne QNnow M3N
AOM31N3 ONIIIVO
380.38 3aVH0 MO -138 .0-,Z
(1IV13a OLLW43HOS
dYO aw TD SnKm .ZL/M
11naNO3 am Oi aHOS .Z
13NIeVO 83dSNVal Mod INOOM M3N
ONV 3SVe 8313MV TIVISNI
'13NVd-ens M£ 'oL 'OVA OZL/Oi.Z '01M1 MY 09 M3N
6L I
'NOLLY001 Sle M3N 3Hl 01 STISVO 180ddnS Ol a3Hlntm sV LnON00
31ON®
aNY 'AVal 31M ')13V8 H3aaVl 31M TTYISNI aNV HSINNnd TMiS a01OValN00ens
13NIeV3 NOISNVdX3 YM1al IN33nl ONLLSIX3
XM ONILSIX3 NOW
:)1OVN N30aVl 3113VJ '£
a3MOd 803
Z L L 30 j0 *NIM V 031)1
13NISVO a3MOd VRCLL ONLLSIX3
I1naN0O SON -40 . L £
131)1036 Rum S38n0300Hd aNY mom 71Y 31YNIaa000 alnoHS Holov-dwooenS
n
m
i-T� -T�
H-
n
MI.
y
f X X
Lo -990 -an 0Ma
33S SYNN31W M3N HOA
1MVIdlnm aw ovd
IMI ldInm 313HONO3 ONLLS0 3
90
t Q IrVi3Q Mad
'MISS 33L M3N
•ANYSS303N SY 1MaMYH 1Y01a10313 ANY do 3SOdSla aw 3AOMC3a of N010 mooens '9
(1IV13a OLLW43HOS
804 £ 133HS 33S) •J3NISV3 83_4SNVal 83M0d INODWH V T1VISNI Tm4s voim1N00enS
13NIeVO 83dSNVal Mod INOOM M3N
'13NVd-ens M£ 'oL 'OVA OZL/Oi.Z '01M1 MY 09 M3N
'NOLLY001 Sle M3N 3Hl 01 STISVO 180ddnS Ol a3Hlntm sV LnON00
aNY 'AVal 31M ')13V8 H3aaVl 31M TTYISNI aNV HSINNnd TMiS a01OValN00ens
13NIeV3 NOISNVdX3 YM1al IN33nl ONLLSIX3
:)1OVN N30aVl 3113VJ '£
13NIeY0 OIaVH VWQl 1N3Onl ONIISIX3
HOIVNIOHOOO NOLLOnN1SNO3
13NISVO a3MOd VRCLL ONLLSIX3
131)1036 Rum S38n0300Hd aNY mom 71Y 31YNIaa000 alnoHS Holov-dwooenS
:HHOM d0 NOLMIQa000 T
we aNno8o 1V1N3W31ddns
')180M d0 S3d0Os TIY A mA Taw Trms HOIOIR mooens
OUM33H Sn0H11
9
*MVMIM3A a13Li 'l
I aMIdinm ssnN M3N
S310N NouonalSNOO
1N3Vldlno3 SIS VIXON MUM
INMMW3 S18 VI)1ON M3N
NoLLVowma MIww
.4am
X X X X X X
l3NVd Xsa
)f001e 9 9
(S1Ad) 3NOHd
(s) nso
(s) nIN
:ave NHnl38 lWd MMOd
:(eOMI) HYe aNnoHa M31SVM1
CA
:ave Moms o0131
Mwe 00131
(sMo) Saw 3AvM mmo
(9Nn00) 13NVd 30NYUM 3-18W
X
dwnd dmns
F(3a1no3nYM/xvoo)
30
a31�lo1wnH 3Q
(woos) auiaimm 30
X
H3LilalwnH
®£
SIOWN00 3VAH/1VlS0MIH3H1
I
I1Nn OVAH
X
1311!10 wo
Xos loumoo ONl1H0n NOLLOnmm M3M01
I
ONLLHOn ALwno3s lrRimm
(S) a31S00e 03l OV
X
a01Va3N30 Asawis
=V1d303H HOM N30 3-WiH d
3ON3d
OLLYHOI V/HOl1MS U31SNVdL
0N1151X3
X
1v11NYMl/H01MM4 kBASMY81
Z
Q
HOSMEWS 39ans OV
I
'13NVd MUM NrM OV
6l
cZi
U N30 Vol OV -MMM03
X
E1314HOJSNML OV
103NNOOSIC 30MOS OV 1YIOa3M MOO
84
I
T3NYd 3ONY81N3 3=13S !1/31810313
X
NMVI OV IVI048MIP403
Z 831M3AN1
I
L H31M3ANI
8318MAN03 Oa O1 3a
LE
X
a8v08 Emu OaAft
l
aHV08 a3MOd OQAiZ
6
I
lO3NNOOSIO AM31LV8
9
SO i[} i❑ 7130 130/S3MUV8 L
\�LW0,t695V
Sllvl3a 33S ONIaNnOHO I NOLLVIS HSVM NI)1S QNY 3A3 AON30a3Mf3 9
IN3)4dinb3 aNY aVd MridinM Il)1 aro !saki OS
313HONO3 .0-,£L X .0-,£ M3N siHOn AON3maru V
X OOZ Mld/NOISS38dnS 38W �£
NOIYH/NOISS38dnS 3HLi
X X X X X X X X X X H3HSInONLLX3 3HId Q
THE OFF POSITION
GENERATOR
RECEPTACLE
LEGEND
EXIST. EQUIP.
PROPOSED EQUIP.
FUTURE EQUIP.
++ �� GROUNDING
CONDUCTORS AND RACEWAY TO
BE FURNISHED & INSTALLED BY
SUBCONTRACTOR
DISCONNECT
K -9T
PWR
TVSS
MATERIALS
MFG.
MODEL
QUANTITY
PROVIDED BY
POS TRANSFER
MARCONI
F1004389
1
CONTRACTOR
CABINET
Hn. a�,E r:EVISIONs BY sift APP"a
rnfneETe vRASKrrc rluaeER
AS SHOWN p� DRAft feu
24623-954 LTR -065-03 1
40A, 2P, 120/240V
CUTLER
MATCH NEW
3
SUBCONTRACTOR
BREAKER
HAMMER
PANELBOARD
15A, 2P, 120/240V
CURER
MATCH NEW
1
SUBCONTRACTOR
BREAKER
HAMMER
PANELBOARD
RIGID CONDUIT,
3/4' & 1' C.,
POWER & GROUND
TO SUIT
#Q. JIO & #12 AWG
TO SUR
SUBCONTRACTOR
CONDUCTORS
STRANDED COPPER
BUILDING WIRE
#2 & #6 AWG
SUPPLEMENTAL
EQUIPMENT
TO SUIT
STRANDED
INSULATEDGGREEN
TO SUIT
SUBCONTRACTOR
COPPER
OPPER
CONDUCTOR
LT FLEX
TO SUIT
3/4'
TO SUIT
SUBCONTRACTOR
T1 CABLE
CONNECTORS
----
DATACOM
CDD411450
AS REQ'D.
SUBCONTRACTOR
RIGID CONDUIT
2' C WITH 2'
TELCO
TO SUIT
TO 3/4' REDUCER
TO SUIT
SUBCONTRACTOR
CONDUCTORS
TRAY
----
----
AS REQ.
SUBCONTRACTOR
BILL OF MATERIALS 3Q8
UNE
MAIN
NEW 240/120 VAC.10. 3W
POWER TRANSFER CABINET
3-1/C #8 AWG THHN,
3/4' C. (3 TYP)
(NOTE 2)
NOKIA
ULTRASITE
SUPPORT
CABINET
(NUSS)
NOKIA
ULTRASITE
CABINET
(GSM)
1' TEE W/2-1' TO
3/4' REDUCERS
NOTES:
1. ROUTE #2 AWG SUPPLEMENTAL EQUIPMENT GROUND CONDUCTOR 4.
FROM GROUND RING TO REACH TOP OF NOKIA CABINET. CUT,
COIL, AND TAPE TEN—FOOT PIGTAIL AND SUPPLY A 2 HOLE (5/16'
DIA) COMPRESSION LUG FOR CONNECT€ON BY NOKIA. SEE DETAIL
569D. FOR ADDITIONAL INFORMATION. WHERE APPLICABLE, ROUTE
EXISTING #2 SCUD GROUND TO BACK CORNER OF PROPOSED BTS
LOCATION FOR CONNECTION (CADWELD) WITH NEW 12 AWG GREEN
INSULATED GROUND WIRE.
2. ROUTE BRANCH CIRCUIT TO REACH TOP OF NOKIA CABINET.
SUPPORT ON CONCRETE PAD OR STEEL STRUCTURE W/UNISTRUT
EVERY 4'. TRANSITION RACEWAY FROM RGS TO UQUID—TIGHT FLEX
METAL CONDUIT (LFMC) AT END OF EXISTING TDMA EQUIPMENT.
CUT, COIL, TAPE AND COVER WITH PLASTIC BAG A 14—FOOT
PIGTAIL (WITH 10 FEET OF LFMC AND STRAIGHT LFMC CONNECTOR
W/TWIST NUTS) FROM END OF CONDUIT FOR CONNECTION BY
NOKIA. SEE DETAIL 567. FOR ADDITIONAL INFORMATION. INSTALL
ADDITIONAL PULLSTRING IN CONDUIT FOR FUTURE CABLE. INSTALL
#6 INSULATED GREEN STRAP ON ALL JOINTS OF RIGID CONDUIT
AND TERMINATE: ON BRASS COMPRESSION COLLAR MOUNT.
3. FURNISH AND INSTALL T1 TRANSPORT CABLE W/GROUND PIGTAIL
AT BTS CABINET ONLY. T1 TVSS INSTALLED BY OTHERS PER
DETAILS 1019. GROUND T1 TVSS TO MGB OR GROUNDED
EQUIPMENT FRAME
STRANDED
THWN
INSULATED
6-1/C #8 AWG THHN, 1' C
(NOTE 2)
3--1/C #8 AWG THHN, 1' C
(NOTE 2)
2-1/C #12 AWG THHN AND
1-1/C #12 AWG THHN
GREEN INSULATED GND:
3/4' C. (NOTE 6)
3/4' C
(NOTE 4)
NOKIA
SUPREME
CABINET
UMTS
(FUT.)
I
I
I
T1 CABLE: 2' C
(NOTE 3 & 4)
TELCO _
PANEL
TYBS TELCO
NIU
(NOTE 3) ■ EXISTING
TELCO
CABLE
I
C
#6 AWG STRANDED J EXISTING 06
COPPER THHN AWG SOLID
(OR THWN OUTDOORS)
GREEN INSULATED
INSTALL CONDUIT BETWEEN BTS AND NIU PANEL FOR T1 CABLE
ROUTE CONDUIT TO REACH TOP OF NOKIA CABINET, SUPPORT ON
CONCRETE PAD OR STEEL STRUCTURE W/UNISTRUT EVERY 4'.
TRANSITION RACEWAY FROM RGS TO UQUID—TIGHT FLEX METAL CONDUIT
(LFMC) AT END OF EXISTING TDMA EQUIPMENT. ATTACH 10 FEET OF
LFMC AND STRAIGHT LFMC CONNECTOR FROM END OF CONDUIT AND
CAP W/TWIST NUTS AND COVER WITH PLASTIC BAG FOR CONNECTION SY
NOKIA INSTALL PULLSTRING IN CONDUIT. INSTALL 16 INSULATED GREEN
STRAP ON ALL JOINTS OF RIGID CONDUIT AND TERMINATE ON BRASS
COMPRESSION COLLAR MOUNT.
5. FURNISH AND INSTALL THREE 40A 2—POLE CIRCUIT BREAKERS FOR A
NUSS WITH ONE OR TWO RECTIFIER SHELVES.
6. FURNISH AND INSTALL ONE 15A, 2—POLE BREAKER WITH CONDUIT
AND WIRING FOR EACH BTS THAT CABINET HAS THE OPTIONAL
'HEW HEATER. ROUTE CONDUIT TO REACH TOP OF NOKIA CABINET,
SUPPORT AS REQUIRED, TRANSITION FROM PVC/IMC TO LFMC WITHIN
6 FEET OF CABINET TOP AND INSTALL STRAIGHT LFMC CONNECTOR FOR
TERMINATION BY NOKIA
7. ROUTE EACH BRANCH CIRCUIT THROUGH JUNCTION BOX DIRECTLY TO
THE NUSS UNIT WITHOUT ANY SPLICING INSIDE JUNCTION BOX.
AC POWER (240/120 VAC}, T1 CABLE AND GROUNDING
INTERFACE TO NOKIA OUTDOOR BTS WAUSS
DETAIL584
NTS
BECHTEL
TELECOMMUNICATIONS
4700 S. BOWMAN ROAD, SUITE 700
LITRE ROCK, AR. 72210
KAVANAUGH
SITE NO. LTRK1-065
3000 OZARK POINT
LITTLE ROCK, AR 72205
—� AT&TT&T
" '
AT&T WIRELESS SERVICES, INC.
'� SOUTH �FnlE ROCKEAR 722; TIE 600 ISMS--
WIRELESS
AC POWER 1240/120 VAC), T1 CABLE.
DOONG R INTERFACE
� NOKLA OUTDOOR BTS �
s nr�rr�as rtEvrsm PowQe senors feu rers RFs
o 121W R ESLIED Fore CONSn uCrroee wu refs fo-s
Hn. a�,E r:EVISIONs BY sift APP"a
rnfneETe vRASKrrc rluaeER
AS SHOWN p� DRAft feu
24623-954 LTR -065-03 1
F 5
4 A I 3 1 2
C
A
DETAIL SOBA
LEGEND
1- COPPER GROUND BAR, Y4X 4'X 20', NEWTON INSTRUMENT CO.
CAT. N0. B-6142 OR EQUAL HOLE CENTERS TO MATCH NEMA
DOUBLE LUG CONFIGURATION.
2- INSULATORS, NEWTON INSTRUMENT CAT. NO. 3061-4
3- 5/8' LOCKWASHERS, NEWTON INSTRUMENT CO.
CAT. NO. 3015-8
4- WALL MOUNTING BRACKET, NEWTON INSTRUMENT CO.
CAT NO. A-6056
5- 5/B-11 X 1' HHCS BOLTS, NEWTON INSTRUMENT CO.
CAT NO. 3012-1
DETAIL q_as
1. ALL CONCRETE WORK SHALL BE IN ACCORDANCE WITH THE ACI 301,
ACI 318, ACI 336, ASTM A184, ASTM A185 AND THE DESIGN AND
CONSTRUCTION SPECIFICATION FOR CAST -IN-PLACE CONCRETE.
2. ALL CONCRETE SHALL HAVE A MINIMUM COMPRESSIVE STRENGTH OF
4000 PSI AT 28 DAYS, UNLESS NOTED OTHERWISE.
3. REINFORCING STEEL SHALL CONFORM TO ASTM A 615, GRADE 60,
DEFORMED UNLESS NOTED OTHERWISE WELDED WIRE FABRIC SHALL
CONFORM TO ASTM A 185 WELDED STEEL WIRE FABRIC UNLESS NOTED
OTHERWISE SPLICES SHALL BE CLASS 'B' AND ALL HOOKS SHALL BE
STANDARD, UNO.
4. THE FOLLOWING MINIMUM CONCRETE COVER SHALL BE PROVIDED FOR
REINFORCING STEEL UNLESS SHOWN OTHERWISE ON DRAWINGS:
CONCRETE CAST AGAINST EARTH ........ 3 IN.
CONCRETE EXPOSED TO EARTH OR WEATHER:
8 AND LARGER..........................2 IN.
AND SMALLER WWF........1 1/2 IN.
CONCRETE NOT EXPOSED TO EARTH OR WEATHER OR NOT
CAST AGAINST THE GROUND:
SLAB AND WALL ........................3/4 IN.
SEAMS AND COLUMNS..............1 1/2 IN.
5. A CHAMFER 3/4' SHALL BE PROVIDED AT ALL EXPOSED EDGES OF
CONCRETE, UNO, IN ACCORDANCE WITH ACI 301 SECTION 4.2.4.
6. INSTALLATION OF CONCRETE EXPANSION/WEDGE ANCHOR, SHALL BE PER
MANUFACTURER'S WRITTEN RECOMMENDED PROCEDURE. THE ANCHOR
BOLT, DOWEL OR ROD SHALL CONFORM TO MANUFACTURER'S
RECOMMENDATION FOR EMBEDMENT DEPTH OR AS SHOWN ON THE
DRAWINGS. NO REBAR SHALL BE CUT WITHOUT PRIOR ENGINEERING
APPROVAL WHEN DRILLING HOLES IN CONCRETE. EXPANSION BOLTS
SHALL BE PROVIDED BY RAMSET/REDHEAD OR APPROVED EQUAL
CONCRETE AND REINFORCING STEEL NOTES 30
NOTES:
1. FOR NUMBER OF GROUNDING RODS REQUIRED, REFER TO THE FACILITY GROUNDING AND
SURGE PROTECTION STANDARD (DOCUMENT NO. 24623-033-3DG-AOOZ-00001).
2. TWO SEPARATE GROUND LEADS SHALL BE INSTALLED NEAR POWER PANEL END OF EQUIPMENT.
THE GROUND LEADS SFWl BE COILED AND READY FOR CONNECTION TO THE INTERNAL
EQUIPMENT MASTER GROUND BAR (MCB) AND THE CABINET EXTERIOR. EACH (MOUND LEAD
SHALL BE CADWELDED TO UNDERGROUND RING. ONE GROUND LEAD SHALL BE ABLE TO
EXTEND A MINIMUM OF 10'-0' ABOVE GRADE FOR TERMINATION TO INTERNAL MGB.
TO EQUIPMENT
GROUND
CONCF
6' 1/2' PVC SCHEDULE 40
SLEEVE
TO BURIED -/ `02 AWG SOLID TINNED
GROUND RING
SLEEVE DETAIL
ORIENT SLEEVE TO ACHIEVE
SMOOTH BEND RADIUS FOR
GROUND WIRE
EQUIPMENT ON SLAB ON GRADE
FOR ORIENTATION SEE PLAN
DETAIL 69
NTS
-0' 116'
1'-0'
-1. /PULL Smmw
U
6' A90VE
PAD AM CAPPED FOR
POWER
7' RCS 1f/PIILL STRING
511199E0 IIP 6' ABOVE
PAD AM CAPPED FOR
TELCO
G3 a 0 BOLT
FRONT }}
V-6 5/16'
(TVP•)
FOUNDATON
SEE DETAIL 381
PLAN VIEW
NOTE
1. FOR CONCRETE
NOTES SEE DETAIL 302
2. GRAVEL SHALL BE
NATURAL OR CRUSHED
GRAVEL WITH 100
PERCENT PASSING
1 INCH SIEVE.
1/4' PER FT. EQUIP.
SLOPE (TYP.) LOCAT'O
2 5/8' 5 15/16'
(TYP-) (TYP.)
Irun,n PLINTH
1 2 3
2'-0 3/8'_,z,
m
(TYP.) g
o
ANCHOR BOLT
PA,TTER
POWER
TELCO
6' ABOVE GRADE
OR PAVEMENT
SAWCUT
I EXISTING
r 7coMPACTED
! / PAVEMENT
REPAIR TO MATCH
EXIST PAVEMQUIRED HT
AS REQUIREDFOR EMBEDDED 6'COMPACTED
CONDUIT STUB -UP CRUSHED STONE SOIL TO MIN.
LOCATION SEE OR GRAVEL 95% MODIFIED PROCTOR
PLAN VIEW MAX DENSITY PER ASTM
D1557 METHOD C
END VIEW
NOKIA OUTDOOR FQUIPMFNTS E NOKIA OUT R EQUIPMENT WEIGHT
(PCR CABINET] ULTRASTTE MAX. WEIGHT PER UNIT - 844.8 LBS (384 KG)
30.3' W x 29.5' D x 76.4' H ULTRASTTE MAX. SLAB LOADING - 136 LBS/SQ FT (671 KG/SQ M)
(770mm x 750mm x 1940mm) NUSS MAX WEIGHT PER UNIT - 1587 LBS (720 KG)
NUSS MAX SLAB LOADING - 255 LBS/SQ FT (1247 KG/SQ M)
NOKIA OUT OOR MINIMUM QLEARANCE5
CABINET REAR AND WALL O'(Omm)
CABINET RIGHT/LEFT SIDE O'(Omm)
ABOVE THE CABINET 30'(762mm)
IN FRONT OF THE CABINET 36 -/40 -(NOTE 1)/48 -(NOTE 2)
NOTE 1 - EXPOSED LIVE PARTS (I.E.. CABINET DOORS OPEN), GREATER THAN 150
VAC, ON ONE 510E AND GROUNDED PARTS ON THE OTHER SIDE.
NOTE 2 - EXPOSED LIVE PARTS (I.E., CABINET DOORS OPEN), GREATER THAN 150
VAC, ON BOTH SIDES OF THE WORKSPACE (NOT GUARDED) WITH THE
OPERATOR IN BETWEEN.
QONCREIE EQUIPMENT PAD/--SLA-13 ON GRADE
DETAIL 60
NTs _
BECHTEL
TELECOMMUNICATIONS
�] 4700 S. BOWMAN ROAD, SUITE 700
�f LITTLE ROCK, AR. 72210
KAVANAUGH
SITE NO. LTRK1-065
3000 OZARK POINT
LITTLE ROCK, AR 72205
F AT&T
+ 01/n/0 FXVGED POW CRCUrrs RICA RFs RFs
v 13/2D/42 ISSUED FOk cnaN WA RFs RFS
AT&T WIRELESS SERVICES, INC. DATE REVISIONS 9r CHK APA
940 SOUTH S'�CKLEFORD. SURE 600
LmLE ROCK, at qui i SCALE: AS SHOM DESIGNED; RFs DRAWN: RKA
AT&T WIRELESS
NOTES NOKIA AND
SITE DRAWING
CONCRETE FOUNDATION
r
GROUND ROD
CApWLLp �
COMPR£5510
CONNECTIONT
ICONNECTOR
1
(TYP.)
I
(Typ.)
1
1
12 AWG SOLID,
TINNED. BCW
(BURIED GROUND
1 RING) (AS SHOWN
#2 AWG SOLID,
ON GROUNDING
TOMMED. BCW
LAYOUT DRAWING)
(TVP)
i
!
1
1
24' MIN.
1
GRAVEL. YARD
NOTES:
1. FOR NUMBER OF GROUNDING RODS REQUIRED, REFER TO THE FACILITY GROUNDING AND
SURGE PROTECTION STANDARD (DOCUMENT NO. 24623-033-3DG-AOOZ-00001).
2. TWO SEPARATE GROUND LEADS SHALL BE INSTALLED NEAR POWER PANEL END OF EQUIPMENT.
THE GROUND LEADS SFWl BE COILED AND READY FOR CONNECTION TO THE INTERNAL
EQUIPMENT MASTER GROUND BAR (MCB) AND THE CABINET EXTERIOR. EACH (MOUND LEAD
SHALL BE CADWELDED TO UNDERGROUND RING. ONE GROUND LEAD SHALL BE ABLE TO
EXTEND A MINIMUM OF 10'-0' ABOVE GRADE FOR TERMINATION TO INTERNAL MGB.
TO EQUIPMENT
GROUND
CONCF
6' 1/2' PVC SCHEDULE 40
SLEEVE
TO BURIED -/ `02 AWG SOLID TINNED
GROUND RING
SLEEVE DETAIL
ORIENT SLEEVE TO ACHIEVE
SMOOTH BEND RADIUS FOR
GROUND WIRE
EQUIPMENT ON SLAB ON GRADE
FOR ORIENTATION SEE PLAN
DETAIL 69
NTS
-0' 116'
1'-0'
-1. /PULL Smmw
U
6' A90VE
PAD AM CAPPED FOR
POWER
7' RCS 1f/PIILL STRING
511199E0 IIP 6' ABOVE
PAD AM CAPPED FOR
TELCO
G3 a 0 BOLT
FRONT }}
V-6 5/16'
(TVP•)
FOUNDATON
SEE DETAIL 381
PLAN VIEW
NOTE
1. FOR CONCRETE
NOTES SEE DETAIL 302
2. GRAVEL SHALL BE
NATURAL OR CRUSHED
GRAVEL WITH 100
PERCENT PASSING
1 INCH SIEVE.
1/4' PER FT. EQUIP.
SLOPE (TYP.) LOCAT'O
2 5/8' 5 15/16'
(TYP-) (TYP.)
Irun,n PLINTH
1 2 3
2'-0 3/8'_,z,
m
(TYP.) g
o
ANCHOR BOLT
PA,TTER
POWER
TELCO
6' ABOVE GRADE
OR PAVEMENT
SAWCUT
I EXISTING
r 7coMPACTED
! / PAVEMENT
REPAIR TO MATCH
EXIST PAVEMQUIRED HT
AS REQUIREDFOR EMBEDDED 6'COMPACTED
CONDUIT STUB -UP CRUSHED STONE SOIL TO MIN.
LOCATION SEE OR GRAVEL 95% MODIFIED PROCTOR
PLAN VIEW MAX DENSITY PER ASTM
D1557 METHOD C
END VIEW
NOKIA OUTDOOR FQUIPMFNTS E NOKIA OUT R EQUIPMENT WEIGHT
(PCR CABINET] ULTRASTTE MAX. WEIGHT PER UNIT - 844.8 LBS (384 KG)
30.3' W x 29.5' D x 76.4' H ULTRASTTE MAX. SLAB LOADING - 136 LBS/SQ FT (671 KG/SQ M)
(770mm x 750mm x 1940mm) NUSS MAX WEIGHT PER UNIT - 1587 LBS (720 KG)
NUSS MAX SLAB LOADING - 255 LBS/SQ FT (1247 KG/SQ M)
NOKIA OUT OOR MINIMUM QLEARANCE5
CABINET REAR AND WALL O'(Omm)
CABINET RIGHT/LEFT SIDE O'(Omm)
ABOVE THE CABINET 30'(762mm)
IN FRONT OF THE CABINET 36 -/40 -(NOTE 1)/48 -(NOTE 2)
NOTE 1 - EXPOSED LIVE PARTS (I.E.. CABINET DOORS OPEN), GREATER THAN 150
VAC, ON ONE 510E AND GROUNDED PARTS ON THE OTHER SIDE.
NOTE 2 - EXPOSED LIVE PARTS (I.E., CABINET DOORS OPEN), GREATER THAN 150
VAC, ON BOTH SIDES OF THE WORKSPACE (NOT GUARDED) WITH THE
OPERATOR IN BETWEEN.
QONCREIE EQUIPMENT PAD/--SLA-13 ON GRADE
DETAIL 60
NTs _
BECHTEL
TELECOMMUNICATIONS
�] 4700 S. BOWMAN ROAD, SUITE 700
�f LITTLE ROCK, AR. 72210
KAVANAUGH
SITE NO. LTRK1-065
3000 OZARK POINT
LITTLE ROCK, AR 72205
F AT&T
+ 01/n/0 FXVGED POW CRCUrrs RICA RFs RFs
v 13/2D/42 ISSUED FOk cnaN WA RFs RFS
AT&T WIRELESS SERVICES, INC. DATE REVISIONS 9r CHK APA
940 SOUTH S'�CKLEFORD. SURE 600
LmLE ROCK, at qui i SCALE: AS SHOM DESIGNED; RFs DRAWN: RKA
AT&T WIRELESS
NOTES NOKIA AND
SITE DRAWING
.+09 NUNM TM+Aww+c NE+ig"
24623-954 LTR -065-04 1
6 5 4 3 1 2 1
m
L
r.
A
TO UTILITY
TO SITE GROUND
FDTN TYPE
II
.� f
Lx(FT)
9'-B'
S/G
8'-0'
t(IN)
5/N
RETNF TOP
13 O6'
REINF BOT
3/4' IMC CONDUIT AND FITTING
MAIN DISCONNECT
SWITCH (OR C. 87
r+... . .-.,
ALTERNATE C.B.
LOCATION (NOTE 2)
VC /10 AWG THHN IORTHWNf
JEXISTING
MAINMANUF.
SUPPLIEDDISCONNECT
SWITCH/
WIRES
N2(&
PANELBOARD
240/120 VACIO 3W
(NOTES 5 k 6)
TO EXISTING LOADS
J
AND
NEW BTS
TVSS ENCLOSURE
(NOTES 1, 2, 3 & 4)
NOTES:
1. FURNISH AND INSTALL INNOVATIVE TECHNOLOGY MODEL PTX160-1SI01 OR OWNER
APPROVED EQUAL TVSS DEVICE. WHEN AC SERVICE DOES NOT HAVE A TVSS.
2. CONNECT TVSS TO THE MAIN D.SW OR PANELBOARD THROUGH A 30A BREAKER.
BREAKER TO HAVE SHORT CIRCUIT INTERRUPTING RATING EQUAL TO OR GREATER
THAN THE AVAILABLE FAULT CURRENTOF EXISTING SERVICE ENTRANCE OR EXISTING
BRANCH CIRCUIT BREAKER SHORT CIRCUIT INTERRUPTING RATING IF CONNECTION
IS MADE ON THE EXISTING PANELBOARD BUS BARS. WHENEVER THE CIRCUIT
BREAKER CANNOT BE INSTALLED IN THE EXISTING PANELBOARD, INSTALL BREAKER
AND TVSS IN A 24'Hx16`WxB'D(MIN) NEMA 3R OR NEMA 12 ENCLOSURE (NEMA 12
ENCLOSURE IS REQUIRED WHEN INSTALLED INSIDE A SHELTER. NEMA 3R IS REQUIRED
OUTDOORS.) A SEPARATE ENCLOSURE IS NOT REQUIRED WHEN THE BREAKER IS INSTALLED
IN THE EXISTING PANELBOARD.
3. MOUNT TVSS OR TVSS/BREAKER ENCLOSURE IMMEDIATELY ADJACENT TO SERVICE
ENTRANCE MANDISCONNECT/PANELBWD. WHENEVER POSSIBLE, LOCATE TVSS SUCH
THAT WIRING IS 12' OR LESS.
4. MANUFACTURER'S INSTRUCTIONS SHALL BE FOLLOWED FOR TVSS INSTALLATION AND
WIRING.
5. FOR 208/120V 3-PHASE, 4 -WIRE SERVICE, USE INNOVATIVE TECHNOLOGY MODEL
PTX160-3Y101 AND A 3 -POLE 30A CIRCUIT BREAKER.
6. CONFIRM AC SERVICE ENTRANCE HAS SOLID BOND BETWEEN NEUTRAL AND GROUND.
TVSS INSTALLATION E)(TERNAITO EXISTING PANELBOARp
DETAIL 523
NT5
BECHTEL
TELECOMMUNICATIONS
i 4700 S. BOWMAN ROAD, SUITE 700
LITTLE ROCK, AR. 72210
KAVANAUGH
SITE NO. LTRK1-065
3000 OZARK POINT
LITTLE ROCK, Ai 72205
Lx
nAowc-r
FOR LOCATION SEE
DETAIL 3609 '
REBAR (SEE FOUNDATION L)
SCHEDULE BELOW) a
FOUNDATION
SCHEDULE
FDTN TYPE
II
WIND SPEED (MPH) 80-100
Lx(FT)
9'-B'
Ly(FT)
8'-0'
t(IN)
10'
RETNF TOP
13 O6'
REINF BOT
13 O B'
NOTE:FOUNDATION TYPE TO
BE SELECTED BASED ON THE
SITE LOCATION DESIGN WIND
SPEED.
NOKIA OUTDOOR CONCRETE PAD SUPPORT
OErAIL 381
6 1 5 1 4
AT&T
AT&T WIRELESS SERVICES, INC.
900 SOUOI SHACKLEFORD. SUITE 600
LITTLE ROCK. M 72211
RF NOTES:
1. QUANTITIES SHOWN IN () ARE TOTAL QUANTITY.
2. ACTUAL LENGTHS SHALL BE DETERMINED PER SITE CONDITION BY
SUBCONTRACTOR.
3. THE DESIGN IS BASED ON RF DATA SHEER, SIGNED AND APPROVED.
4. RADIO SIGNAL. CABLE AND RACEWAY SHALL COMPLY WITH THE REQUIREMENTS OF
THE NATIONAL ELECTRICAL CODE (NEC, NFPA 70), CHAPTER B.
5. ALL SPECIFIED UATERIAL FOR EACH LOCATION (E.G., OUTDOORS, INDOORS --OCCUPIED. INDOORS -
UNOCCUPIED. PLENUMS, RISER SHAFTS, ETC.) SHALL BE APPROVED. LISTED. OR LABELED AS
REQUIRED BY THE NEC.
6. RADIO SIGNAL CABLE SHALL BE SUPPORTED Al MINIMUM OF EVERY THREE (3) FEET EXCEPT
INSIDE MONOPOLES OR UATTACE TOWERS WHERE CABLE AND CONNECTOR MANUFACTURERS
SUPPORT RECCMMENOATIONS SHAM. BE FOLLOWED. MANUFACTURER RECCMMENDED CABLE SUPPORT
ACCESSORIES SHALL BE USED.
7. THE OUTDOOR CABLE SUPPORT SYSTEM SHALL BE PROVIDED WITH AN ICE SHIELD TO SUPPORT
AND PROTECT ANTENNA CABLE RUNS. SEE DETAIL NUMBER 568 AND 574.
B. DRIP LOOPS SHALL BE REQUIRED ON ALL OUTSIDE CABLES. CABLES SHALL BE SLOPED AWAY
FROM THE BUILDING OR OUTDOOR BTS CABINETS TO PREVENT WATER FROM ENTERING
THROUGH THE COAXIAL CABLE PORT.
9. ALL FEEDER LINE AND JUMPER CONNECTORS FOR 3G GSM SHALL BE AWS APPROVED 7/16 DIN
CABLE CONNECTORS THAT MEET IP68 STANDARDS.
10. WHEN MODIFYING EXISTING 2G TDMA COAXIAL CABLES FOR 3G USE, REMOVE ALL EXISTING N TYPE
CONNECTORS WHERE FEASIBLE AND REPLACE WITH NEW 7/16 DIN CONNECTORS.
11. MINIMUM CABLE BENDING RADIUS SHALL. BE ADHERED TO IN ACCORDANCE WITH SECTION 6.0 OF
DESIGN CRRIERIA (DOCUMENT NO. 24623-033-3DR-GET-00001).
12. ALL 7/16 DIN CONNECTORS SHALL BE IP68 RATED. ALL OUTDOOR CONNECTORS AND ALL COAXIAL
CABLE SHIELDING GROUND POINTS SHALL BE WEATHERPROOFED IN ACCORDANCE WITH THE
FOLLOWING PROCEDURE
START WITH ANDREW WEATHERPROOFING KIT TYPE 221213. START TAPE APPROXIMATELY 5 INCHES
FROM THE CONNECTOR AND WRAP 2 INCHES TOWARD THE CONNECTOR, THEN REVERSE THE TAPE
SO THAT THE STICKY SIDE IS UP. TAPE OVER THE CONNECTOR OR SURGE ARRESTOR UNTIL THREE
(3) TO FOUR (4) INCHES BEYOND THE CONNECTOR AND REVERSE AGAIN WITH THE STICKY SIDE
DOWN FOR ANOTHER INCH OR TWO. ADD THE BUM RUBBER AND FINISH WITH A FINAL LAYER OF
ANDREWS TAPE
13. MHA'9/7MA'e SHALL NOT BE PAINTED.
14. ANTENNAS SHALL BE PAINTED, WHEN REQUIRED, TO MATCH EXISTING ANTENNAS IN ACCORDANCE
WITH ANTENNA MANUFACTURERS' SURFACE PREPARATION AND PAINTING REQUIREMEWS. ALLGON
ANTENNAS SHALL USE ALLGON SYSTEM AS; ALLGON DOCUMENT NUMBER 990323/LL, ARC
ANTENNAS SHALL USE SPRAYLAT CORPORATION PRODUCTS PER ARC DRAWING NUMBER IN702194,
REVISION R2.
15. CABLE SHIELDS. AND TOWER CONDUITS SHALL BE GROUNDED AT THE TOP OF THE TOWER, WITHIN
10 FEET OF THEIR CONNECTORS, AND AT THE BOTTOM OF THE TOWER ABOUT 6 INCHES BEFORE
THEY TURN TOWARD THE FACILITY. THEY SHALL BE GROUNDED AT THE MIDPOINT OF TOWERS THAT
ARE BETWEEN 150 FEET AND 300 FEET HIGH, AND AT INTERVALS OF 150 FEET OR LESS ON
TOWERS THAT ARE HIGHER THAN 300 FEET.
16. APPROVED GROUNDING KITS, WHICH INCLUDE GROUNDING STRAPS, SHALL BE USED TO GROUND
THE COAXIAL CABLE SHIELDS, AND CONDUITS. THE GROUND DNDUCTORS FOR THE KITS AT THE
TOP OF THE TOWER, AND IN THE MIDDLE SECTION OF THE TOWER, ARE BONDED DIREC'11Y TO
TOWER STEEL USING O(OTHERMIC, BOLTED, OR APPRDVED CLAMP CONNECTIONS.
17. ALL RADIO SIGNAL CABLE SHALL BE LABELED WITH COLOR -CODED ELECTRICAL TAPE (3M SCOTCH
35, 7 MILS THICK, 34 INCH WIDE, VINYL ELECTRICAL TAPE. OR CONTRACTOR APPROVED EQUAL)
AND BRASS OR STANLESS STEEL IDENTIFICATION TAGS AS SPECIFIED IN DETAIL NUMBER 600.
18. THE SUBCONTRACTOR SHALL FILL IN DETAIL 601 AND AFFIX IT TO A WEATHER -PROTECTED
LOCATION (E.G., THE SHELTER INTERIOR WALL) NEAR THE CABLE PORT.
19. RECOMMENDED SURGE ARRESTORS THAT CAN BE USED WITH THE BTS EQUIPMENT:
ANDREW: 7/16 DIN M/F WIDEBAND 1/4 WAVE, GAS TUBE WITH DC BYPASS
HUBER+SUHNER: 7/16 DIN M/F WIDEBAND 1/4 WAVE, GAS TUBE WITH DC
BYPASS
20. DUP'LEXERS AND/OR DIPLEXERS AND MOUNTING HARDWARE (J CLAMPS) WHERE EQUIRED SHALL BE
SUPPLIED BY CONTRACTOR AND INSTALLED BY THE SUBCONTRACTOR.
21. MHA/TMA'S TO BE INSTALLED AT TOWER TOP, SHALL BE SUPPLIED BY CONTRACTOR (WHERE
REQUIRED) AND INSTALLED BY THE SUBCONTRACTOR.
22. ANTENNA FEED UNE SYSTEM SWEEP TESTING SHALL BE PERFORMED AND REPORTED IN ACCORDANCE
WITH THE REQUIREMENTS OF AWS DOCUMENT NO. WNS-0294 (LATEST REVISION). CONTRACTOR WILL
NOT ACCEPT A RADIO SIGNAL GABLE INSTALLATION WITH UNSATISFACTORY SWEEP TEST RESULTS.
0 1'12/=/021 05M FOIL CONMUMM REeI RFS RFS
tnj GATE I TENSIONS 9r C�#[ APP'Ef
MJBE AS SN01N1E DMIMM. WS MMM WA
3 1 2
AT&T WIRELESS
GENERAL DETAILS
NOKIA OUTDOOR
SITE DRAWING
JOB NLYBER OTAw, NLOFBER
24623-954 LTR -065-05 0
Vol
C
B
A
STRANDED CU WIRE WITH GREEN,-
60OV, THHN/THWN INSULATION.
SIZE AS SPECIFIED ON SINGLE UNE
FLOOR
OR ON � II11 II I
TOWERa
DETAIL
�1.
v
TWO -HOLE LUG, TO BE USED WITH
#2 AWG SOLID TINNED BARE CU
WIRE OR STRANDED CU WIRE WITH
GREEN. 60OV, THHN/THWN
INSULATION TO ANTENNA STRUCTURE,
BUILDING, RING GROUND OR MGB
DETAIL S08k
NTS
4BTM
S
E, 4 PR STP CABLE
T1 -SURGE SUPPRESSOR
ATLANTIC SCIENTIFIC NO.
90700
(PROTECTED)DIN RAIL
(SEE NOTE 1)
rRING TONGUE
COMPRESS
TERMj (SEE NOTEEON 2)
RJ45CI
I /5 AWG STRANDED CU,—
(UNPROTECTED)
U T14HN GREEN INSULATED
MAX NO. OF
CABLES/CND
GROUND WIRE BONDED TO
CAT 5E. 4 pR,�
MGB OR GROUNDED
SIP CAFE
TO NIU
ENCLOSURE
NOTES:
1. MOUNT SURGE ARRESTOR ON EXISTING DIN RAIL IF AVAILABLE,
OTHERWISE PROVIDE ATLANTIC SCIENTIFIC MODEL NO. 21605, 5 -INCH
4 -UNIT DIN RAIL, OR EQUAL. AND SECURELY MOUNT TO TELCO
BOARD.
2. ATTACH GROUND WIRE TO THE DIN RAIL, SEPARATELY FROM THE RAIL
MOUNTING HARDWARE, USING STAINLESS STEEL. BOLT, LOCKING WASHER
AND NUT OR SELF -TAPPING MACHINE SCREW THAT FIRMLY GRIPS THE
DIN RAIL
TI SURGE SUPPRESSOR (DaS)
(INSTALLED BY OTHERS)
DETAIL 1019
NTS
BECHTEL
TELECOMMUNICATIONS
4700 S. BOWMAN ROAD, SUITE 700
LITTLE ROCK, AR. 72210
D
5
TO UTILITY OR
SERVICE
DISCONNECT
(NOTE 6)
SITE GROUND ?i TO BTS
F-
- — — —
S/G
I S —
MAIN BREAKER
(OR MLO)
I
I T�
I �
TO
I OTHER
LOADS
I 30A
I
i
L — — — NOTES 2 & 5L_
EXISTING PANELBOARD
240/120 VAC 10 , 3W
(NOTE 5)
I
1
1
I
MANUFsupp. I
WIRES I
I
TVSS
1(3 T) I
I
J
NOTES:
1. FURNISH AND INSTALL INNOVATIVE TECHNOLOGY MODEL PTX16G-1S101
OR OWNER APPROVED EQUAL TVSS DEVICE WHEN AC SERVICE DOES
NOT HAVE A TVSS.
2. CONNECT TVSS TO THE PANELBOARD THROUGH A 30A CIRCUIT BREAKER.
INSTALL NEW CIRCUIT BREAKER IF REOUIRED. BREAKER TO MATCH EXISTING
BRANCH CIRCUIT BREAKER SHORT CIRCUIT INTERRUPTING RATINGS.
3. INSTALL TVSS INSIDE THE PANELBOARD IF SPACE PERMITS, OTHERWISE MOUNT
IMMEDIATELY ADJACENT TO THE PANEU30ARD (RfFE1iENCE DETAIL 1023). WHEREVER
POSSIBLE, LOCATE TYSS SUCH THAT WIRING IS 12 INCHES OR LESS.
4. MANUFACTURER'S INSTRUCTIONS SHALL BE FOLLOWED FOR TVSS INSTALLATION
AND WIRING.
5. FOR 2DO/120V 3-PHASE. 4 -WIRE SERVICE, USE INNOVATTVE TECHNOLOGY
MODEL PIXISO -3Y101 AND A 3 -POLE 30A CIRCUIT BREAKER.
6. CONFIRM AC SERVICE ENTRANCE HIS SOLID BOND BETWEEN NEUTRAL AND GROUND.
KAVANAUGH
SITE NO. LTRK1-065
3000 OZARK POINT
LITTLE ROCK, AR 72205
TVSS INSTALLATION INTERNAL
TO EXISTING PANELBOAR[]
DETAIL 524
NTS
4
AT&T
AT&T WIRELESS SERVICES, INC.
900 SOUTH SHACKLEFGRO, SUITE 600
UTILE ROCK. M 71211
3
SUPPORT POST W/4 HOLE FLANGE PART #8224
(MI5 OR EQUAL) + BRACKET FOR 1$- OR 24 -
CHANNEL PART f 852154 OR 852165 (PIROO
INC OR EQUAL) CUT POST LENGTH TO SUR BY
REMOVING UNCAPPED END
18. OR 24- ICE BRIDGE -
CHANNEL x10' PART
#852164 OR 852165
(PIROD INC. OR EQUAL)
CUT ICE BRIDGE CHANNEL
LENGTH TO SUIT (SEE
NOTE)
OUTDOOR RADIO
EQUIPMENT CABI
FOUNDATION
ANTENNA C
GROUNDING
NEW ICE BRIDGE TO MATCH
EXISTING ICE BRIDGE
HANGER BRACKET TYPE
DOUBLE 7/18. OR T/27- BRIDGE
PART j802264 OR 802257
(FMOO INC OR EQUAL) MAXIMUM
GABLE SPAN - 3'-0- TYP
12 AWG BCW SOLID
TINNED TO GROUND
RING
EXISTING ICE BRIDGE
L FOR CABLE HANGER
W SEE TABLE BELOW
ANTENNA CABLES
ARRANGEMENT
BY CONTRACTOR.
NOMINAL
CABLE
TYPE
CABLE HANGER
MANUR MIN.
BEND RADIUS
MAX NO. OF
CABLES/CND
CABLE SIZE
NUMBER
TYPE NUMBER
1/2-
LDF4-50A
206706-1
5-
9
1/2-
FSJ4-5OB
206706-1
1.25-
9
7/8-
LDF5-50A
206706-2
10-
3
1 1/4-
LDFS-50
206706-3
15'
1
1 5/8-
LDF7-50A
206706-4
20-
1
NOTESX
1. WHEN USING PIROD COMPONENTS AS SHOWN IN STANDARD DETAILS, MAXIMUM ALLOWABLE SPAN BETWEEN SUPPORTS
ON A CONTINUOUS SINGLE SECTION OF BRIDGE CHANNEL SHALL BE 9 FEET FOR 10 FOOT BRIDGE CHANNEL
2. WHEN USING PIROD COMPONENTS FOR SPLICING BRIDGE CHANNEL SECTIONS, THE SPLICE SHOULD BE PROVIDED AT
THE SUPPORT, IF POSSIBLE, OR AT A MAXIMUM OF 2 FEET FROM THE SUPPORT.
3. WHEN USING PIROD COMPONENTS, SUPPORT SHOULD BE PROVIDED AS CLOSE AS POSSIBLE TO THE ENDS OF ICE
BRIDGES, WITH A MAXIMUM CANIILIVER DISTANCE OF 2 FEET FROM THE SUPPORT TO THE FREE END OF THE ICE
BRIDGE
4. CUT BRIDGE CHANNEL SECTIONS SHALL HAVE RAW EDGES TREATED WITH A MATERIAL TO RESTORE THESE EVES TO
THE ORIGINAL CHANNEL, OR EQUIVALENT, FINISH.
5. ICE BRIDGES MAY BE CONSTRUCTED WITH COMPONENTS FROM MANUFACTURERS OTHER THAN PIROD, PROVIDED THE
MANUFACTURER'S INSTALLATION GUIDELINES ARE FOLLOWED.
6. DEVIATIONS FROM STANDARDS FOR COMPONENT INSTALLATIONS ARE PERMITTED WITH THE RESPECTIVE MANUFACTURER'S
APPROVAL
7. DEVIATIONS FROM ICE BRIDGE FOUNDATIONS SHOWN ON SITE SPEGFIC DRAWINGS OR STANDARD DETAILS REQUIRE
ENGINEERING APPROVAL
ICE BRIDGE OUTDOOR EQUIPMENT
CABINETS
D ETAI L
NTS _
AT&T WIRELESS
GENERAL DETAILS
NOKIA OUTDOOR
SITE DRAWING
k24r,23-954
HUMBER IMG'1WIX6 KNOER
LTR -065-06 0
I
C
wl
A
ALLGON 6NIEN
ALLGON [IXC -1900-65-17.5-4—D (7542.00)
1650-199OMHz
DIMENSIONS:— 51'H X 12.8W X 3.15"D
WEIGHT:— 32 LBS.
AREA— 4.55 SQ.FT.
MOUNT:— 2"0-5'/
(2) 1 5/8' RF CABLES
il► ■■ •rr r
rr
ALLGON ANIMNAS
ALLGON XM -1900 -90 -16i -2—D (7262.02)
& XM -1900 -90 -16i -4—D (7262.03)
1850-199OMHz
DIMENSIONS:— 51.2'H X 5'W X 3.2'D
WEIGHT.— 10.8 LBS.
AREA:— 1.8 SQ.Fr.
MOUNT.— 1'0-5'0
(2) 1 5/8• RF CABLES
G
XM -1900-90-16i-4-0 r
BECHTEL
PIWW TELECOMMUNICATIONS
4700 S. BOWMAN ROAD, SUITE 700
LITRE ROCK, AR. 72210
KAVANAUGH
SITE NO. LTRKi-065
3000 OZARK POINT
LITRE ROCK, AR 72205
ARC WIRELESS ANTENNAS
ARC PCS—DS-16-09007-2D
1850-199OMHz
DIMENSIONS:- 48'H X 8.3W X 2.1*D
WEIGHT:- 10.2 LBS.
AREA:- 2.7 SQ.Fr.
MOUNT:- 2"4-5'0
(2) 1 5/8' RF CABLES
;: ;.���►lir_
r•rr ��
IIIIIIIIIIIIIIII=LlQI!WW%-7=f r•rr
REPLACE EXISTING ANTENNAS IN
SECTORS A & B WITH NEW ALLGON
JUXC-1900-65-17.5-4-D ANTENNAS,
Iw A_1 7 MECH. DOWN7ILT (TYP. FOR 2)
uj
C-1
D
e$
�Ec SFe
Ski
REPLACE
B-1
REPLACE EXISTING ANTENNA IN
SECTOR C WITH NEW ALLGON
JUXC-1900-65-17.5-4-D
ANTENNA, 5' MECH. DOWNTILT
(TYP. FOR 1)
6 1 5 1 4
ANTNA�QRIENTAIl4�i
GUYED TOWER
AT&T
AT&T WIRELESS SEFWICES,INC.
900 SOUTH SWICKLEFORD. SURE 600
LITTLE ROCK. AR 77211
3
TOP OF E a m T7M57
ELI:v Dov —o
ELEV.
faImolw:I
a". 117'-[
CL OF 6 FT.
ELEV. 100* -1
CL OF 4 FT.
ELEV. -0'
6 -NEW 1 5/8' -
COAX CABLES
COMMSCOPE NO.
CR50-1873-PE
V2VW I spa FN OMMM T M
DATE I MOONS
AS SHOWM omal . R"
EXISTING --
300' GUYED
TOWER
REPLACE EXISTING ANTENNAS
SEE ANTENNA ORIENTATION
FOR MODEL NUMBER
1 PER SECTOR -3 TOTAL
EXISTING
BLOCK
BUILDING
Lellf4*11111[6l al►
AT&T WIRELESS
ANTENNA ELEVATION, DETAILS
AWA
AND ORIENTATION
doe HuuarSi oRIRNNifY61AppAyyM 24623-954LTTR-065-07
2 I 1
D
IC
IN
A
TO
ANTENNA
ITEM
GROUND SAR (C GiGSE)
TOP OF MONOPOLE
PART NO.
SFE DDEETNL1` (SIMILAR)
STAN GROUND �
16 AWG 2 -HOLE LUG
I1
/2 AWG CU STRANDED WIRE WITH
/6 AWG STRA
GREEN. 6OOV. THWTN NNSULATION
WIRE FURNIS
GROUND LUG
]NA
MARK WITH G
#6 AWG STRANDED CU WIRE
ANTENNA GROUND BAR (CIGBE)
CONNECTOR
BOTTOM OF MONOPOLE
SEE NOTE 1.
SEE DETAIL SOBA (SIMILAR)
GROUND KRSTANDARD
NEAR/BELOW ANTENNA
WITH GREEN TAPE
/8 AWG 2 -HOLE LUG
COAX CABL
COMMSCOPE
(TYP. FOR A
LUG
/2 AWG SOLID TINNED BARE CU
7/8' COAX CABLE
WIRE OR STRAN= CU WIRE WITH
TO BTS
GREEN. 60AV, THWN INSULATION
VIA TRAY
COMMSCOPE
MONOPOLE PIER
j2 AWG BCW SOLID
TINNED GROUND RING #2 AWG BCW SOLA TINNED
CIDWELD TO MONOPOLE
CADWELD (TYP.) BASE PLATE
NOTE:
1. NUMBER OF GROUND BARS MAY VARY DEPENDING ON THE TYPE OF MONOPOLE.
ANTENNA LOCATION AND COLLECTION ORIENTATIDW PROVIDE AS REOUIRM
DETAILNRi
52fi
TO TRANSMIT
NA
TO LOW NOISE AMPLIFIER UNITS
(LNA) (WHEN REQUIRED) AND
RECEIVE ANTENNA NOT
DONOT INSTALL CABLE GROUND
KR AT A BEND AND ALWAYS DIRECT
_&r A r GROUND WIRE DOWN TO CIGBE.
RX1/RX21'I I'1RX1/RX2
CABLE TO ANTENNA
CONNECTOR
WEATHERPROOFING
KR (TYP.)
FROM LIMA
(WHEN REQUIRED)
#6 AWG 2 -HOLE LUG
t2 AWG 2 -HOLE LUG
#2 AWC CU STRANDED WIRE WITH G'.
600Y. THWN INSULATIDN BONDED TO
TOWER STEEL OR MONOPOLE
1.2280 DIA. MAX.
WEATHERPROOFING KIT
ITEM
(TYP.)
PART NO.
STANDARD GROUND KR
ANTENNA CABLE
(TYP.) (SEE NOTE)
I1
ANTENNA CABLE
�0
TO BTS
1 5/6' COAX CABLE
M7.)
CR50-1873-PE
#6 AWG STRANDED CU WIRE
FURNISHED W/KIT. MARK WITH
CONNECTOR
GREEN TAPE (TYP).
- CIGBE (GROUND BAR), SIMILAR
TO DETAIL 509 MOUNTED
+6 AWG STRANDED CU WIRE MARKED
NEAR/BELOW ANTENNA
#2 AWC CU STRANDED WIRE WITH G'.
600Y. THWN INSULATIDN BONDED TO
TOWER STEEL OR MONOPOLE
1.2280 DIA. MAX.
i�►k i . Mou l� •
TO ANTENNA CA13LE
DO NOT INSTALL CABLE GROUND KIT AT A BEND AND ALWAYS
DIRECT GROUND WIRE DOWN TO GROUND BAR.
GROUNDINQ, KIT SHAT BE TYPE AND PART NUMBER AS
SUPPLIED OR RECOMMENDED BY CABLE MANUFAMRER.
WEATHER gROOFING SHALL BE (TYPE AND PART NUMBER AS
SUPPLIED 6R RECOMMENDED BY CABLE MANUFACTURER.)
DETAIL 13A
NTS _
(2.-0 N ALVIZED 3 1/2- VERIFY
DESIGN N
BOLT 1OTE
VERIFY EXISTING
EMBEDMENT (TYP) MINIMUM EDGE WALL FOR APPLIED
DISTANCE OF 6'. DO NOT CUT LOADS
REINFORCING BAR WHEN INSTALLING
ANCHORS
MFG: VALMONT/
MICROFLECT
FOR SOLID CONCRETE W& PRODUCT PART
/91592 OR EQUAL.
3 11/16-
(4) 1/2-0 HILTI HIT HY20 q�
HIT -A ROD (GALVANIZED) OR
EaUN. W/3 3/8' MINIMUM x
EMBEDMENT INSTALL (1)
ANCHOR PER BRICK/BLACK.
MINIMUM EDGE DISTANCE OF 2
BRICK/BLOCK OR 16' (WHICHEVER
Is LESS).
FOR HOLLOW SOLID
BLACK & BRICK WALLS 1'-2 I/
N
1. THIS DESIGN IS BASED ON UBC 1997, WIND SPEED 120 mph, EXPOSURE D, ELEVATION
400 FT.
2. THIS SUPPORT IS DESIGNED FOR (1) ANTENNA WITH MAXIMUM WIND SURFACE AREA OF
6.2 FT. THIS ANTENNA IS SHOWN ON DETAIL 961.
3. THE WEIGHT OF THE ANTENNA MOUNT IS 70 LBS (INCLUDES 5'-6' LENGTH OF PIPE).
CONNECTION QF GROUND WIRE TO GROUNDINQ BAR
(CIGBE) TOWER/MONOPOL.�
DETAIL 22A
BECHTEL KAVANAUGH
TELECOMMUNICATIONS SITE NO. LTRK1-065
4700 S. BOWMAN ROAD, SUITE 700 3000 OZARK POINT
LITTLE ROCK, AR. 72210 LITTLE ROCK, AR 72205
M
5
G TDMA E911 AOA SINGE PANEL ANTENNA
(DECIBEL 9784N8 -120E -M) (1850-1990 MLIZ)
MOUNTED AT WA L
DETAIL 835
NTS
4
AT&T
AT&T WIRELESS SERVICES, INC.
900 SOUTH SWKLEFORD, SUITE 600
LR11.E ROCK AR 72211
3
1900MHz-3G (GSM) BILL OF MATERIALS
(TYPICALLY}
ITEM
-12' TO 24'
PART NO.
' 120' MAX.
ANTENNA CABLE
I
I1
I
WEATHERPROOFING KR
�0
1
1 5/6' COAX CABLE
(SEE NOTE 3)
CR50-1873-PE
ANTENNA CABLE
COMMSCOPE
CONNECTOR
CABLE GROUND KR
2
+6 AWG STRANDED CU WIRE MARKED
(12)
WITH GREEN TAPE
CONTRACTOR
(GROUNDED TO GROUND BAR)
COMMSCOPE
(SEE NOTES 1 & 2)
i�►k i . Mou l� •
TO ANTENNA CA13LE
DO NOT INSTALL CABLE GROUND KIT AT A BEND AND ALWAYS
DIRECT GROUND WIRE DOWN TO GROUND BAR.
GROUNDINQ, KIT SHAT BE TYPE AND PART NUMBER AS
SUPPLIED OR RECOMMENDED BY CABLE MANUFAMRER.
WEATHER gROOFING SHALL BE (TYPE AND PART NUMBER AS
SUPPLIED 6R RECOMMENDED BY CABLE MANUFACTURER.)
DETAIL 13A
NTS _
(2.-0 N ALVIZED 3 1/2- VERIFY
DESIGN N
BOLT 1OTE
VERIFY EXISTING
EMBEDMENT (TYP) MINIMUM EDGE WALL FOR APPLIED
DISTANCE OF 6'. DO NOT CUT LOADS
REINFORCING BAR WHEN INSTALLING
ANCHORS
MFG: VALMONT/
MICROFLECT
FOR SOLID CONCRETE W& PRODUCT PART
/91592 OR EQUAL.
3 11/16-
(4) 1/2-0 HILTI HIT HY20 q�
HIT -A ROD (GALVANIZED) OR
EaUN. W/3 3/8' MINIMUM x
EMBEDMENT INSTALL (1)
ANCHOR PER BRICK/BLACK.
MINIMUM EDGE DISTANCE OF 2
BRICK/BLOCK OR 16' (WHICHEVER
Is LESS).
FOR HOLLOW SOLID
BLACK & BRICK WALLS 1'-2 I/
N
1. THIS DESIGN IS BASED ON UBC 1997, WIND SPEED 120 mph, EXPOSURE D, ELEVATION
400 FT.
2. THIS SUPPORT IS DESIGNED FOR (1) ANTENNA WITH MAXIMUM WIND SURFACE AREA OF
6.2 FT. THIS ANTENNA IS SHOWN ON DETAIL 961.
3. THE WEIGHT OF THE ANTENNA MOUNT IS 70 LBS (INCLUDES 5'-6' LENGTH OF PIPE).
CONNECTION QF GROUND WIRE TO GROUNDINQ BAR
(CIGBE) TOWER/MONOPOL.�
DETAIL 22A
BECHTEL KAVANAUGH
TELECOMMUNICATIONS SITE NO. LTRK1-065
4700 S. BOWMAN ROAD, SUITE 700 3000 OZARK POINT
LITTLE ROCK, AR. 72210 LITTLE ROCK, AR 72205
M
5
G TDMA E911 AOA SINGE PANEL ANTENNA
(DECIBEL 9784N8 -120E -M) (1850-1990 MLIZ)
MOUNTED AT WA L
DETAIL 835
NTS
4
AT&T
AT&T WIRELESS SERVICES, INC.
900 SOUTH SWKLEFORD, SUITE 600
LR11.E ROCK AR 72211
3
1900MHz-3G (GSM) BILL OF MATERIALS
ITEM
ITEM
TOTAL QUANTITY
PART NO.
SUPPLIED BY
NO.
DESCRIPTION
e� --
�0
1
1 5/6' COAX CABLE
1320'
CR50-1873-PE
CONTRACTOR
COMMSCOPE
2
1 5/8' CABLE CONNECTOR DIN -FEMALE
(12)
OR -1873A -DF
CONTRACTOR
COMMSCOPE
3
7/8' COAX CABLE
-
CRW-1070-PE
CONTRACTOR
COMMSCOPE
4
CABLE CONNECTOR DIN -FEMALE
-
OR-107GA-DF
CONTRACTOR
CO/8-
MMSCOPE
5
GSM ANTENNA
-
PCs -DS -16 -09007 -OD
CONTRACTOR
ARC WIRELESS
6
�
-
PCS -DS -16-09007-2D
CONTRACTOR
WIRELESS
7
GSM ANTENNA
(3)
UXC-1900-65-17.5-4-D
CONTRACTOR
A.LGON
(7542.00)
6
GSM ANTENNA
-
XM -1900-90-181-4-D
CONTRACTOR
A LGON
(7262.03)
GSM ANTENNA
-
XM -1900 -90 -16i -2-D
CONTRACTOR
9
ALGON
(7262.02)
10
1/2' COAX CABLE
200'
CR50-540-PE
CONTRACTOR
COMMSCOPE
11
SURGE ARRESTOR
(6)
3409.41.0024
CONTRACTOR
HUBER SUHNER
12
1/2' CABLE CONNECTOR DIN -MALE
(12)
540ADM
CONTRACTOR
COMMSCOPE
13
(18)
CR-54ODMDM-6
CONTRACTOR
COMMSCOPE/2-JUMER
14
MHA, NOKIA
(8)
TBD
CONTRACTOR
3G (GSIA) OUTDOOR BELL OF M T�RJAL
DETAIL 951
NTS -
AT&T WIRELESS
ANTENNA DETAILS AND
BILL OF MATERIAL
jag MLWRDRAWNG NUHAER
24623-954 1 LTR -065-08
IQ
C
A
A
e� --
�0
oo
AT&T WIRELESS
ANTENNA DETAILS AND
BILL OF MATERIAL
jag MLWRDRAWNG NUHAER
24623-954 1 LTR -065-08
IQ
C
A
A