HomeMy WebLinkAboutLA2022-02-Civil Engineering Review Letter
RE:
Planning Commission Review – Central Arkansas Water
LA 2022-02
1. Central Arkansas Water has a water line on the north side of Cantrell Rd. Provide a profile of
the water line route showing the proposed and existing ground elevations. Maintain a minimum
of 30-inches of cover over the existing water line. If there are facilities that need to be adjusted
and/or relocated, contact Central Arkansas Water. That work would be done at the expense of
the developer.
No grading changes will occur at the location of the water line.
Planning Commission Review – Tracy Spillman, plans development administrator
15104, 15510, &15122 Cantrell Rd LA2202-02
All boundaries and limits of disturbance will remain as the original approved grading permit
provided.
1. Site plan must comply with the City’s minimal landscape and buffer ordinance requirements
and the Highway 10 Scenic Corridor Overlay District.
Will comply.
2. A land use buffer six (6) percent of the average width / depth of the lot will be required when an
adjacent property has a dissimilar use of a more restrictive nature. The property to the north is
zoned R-2. As a component of all land use buffer requirements, opaque screening, whether a
fence or other device, a minimum of six (6) feet in height shall be required upon the property
line side of the buffer. A minimum of seventy (70) percent of the land use buffer shall be
undisturbed. Easements cannot count toward fulfilling this requirement. The plantings, existing
and purposed, shall be provided within the landscape ordinance of the city, section 15-81.
Will comply
3. The City Beautiful Commission recommends preserving as many existing trees as feasible on
this site. Credit toward fulfilling Landscape Ordinance requirements can be given when
preserving trees of six (6) inch caliper or larger.
Will comply
Planning Commission Review – Fire Marshal Derek Ingram and Captain Tony Rhodes
LA 2022-02 Cantrell West Development – Advance Grading Variance 15122 Highway 10
Maintain Access:
Fire Hydrants.
Maintain fire apparatus access roads at fire hydrant locations as per Appendix D of the 2012 Arkansas Fire
Prevention Code Vol. 1 Section D103.1 Access road width with a hydrant. Where a fire hydrant is located
on a fire apparatus access road, the minimum road width shall be 26 feet, exclusive of shoulders.
Will comply.
Grade
Maintain fire apparatus access roads as per Appendix D of the 2012 Arkansas Fire Prevention Code Vol. 1
Section D103.2 Grade. Fire apparatus access roads shall not exceed 10 percent in grade except as
approved by the fire chief. If the grade exceeds 10 percent, approval will be denied and the applicant must
submit request to be reviewed by Fire Chief for Approval.
Will comply.
Loading
Maintain fire apparatus access road design as per Appendix D of the 2012 Arkansas Fire Prevention Code
Vol. 1 Section D102.1 Access and loading. Facilities, buildings or portions of buildings hereafter
constructed shall be accessible to fire department apparatus by way of an approved fire apparatus access
road with an asphalt, concrete or other approved driving surface capable of supporting the imposed load of
fire apparatus weighing at least 75,000 pounds.
Will comply.
Commercial and Industrial Developments – 2 means of access. - Maintain fire apparatus access roads as
per Appendix D of the 2012 Arkansas Fire Prevention Code Vol. 1
Will comply.
Section D104.1 Buildings exceeding three stories or 30 feet in height. Building or facilities exceeding 30
feet or three stories in height shall have at least two means of fire apparatus access for each structure.
Will Comply.
Section D104.2 Building exceeding 62,000 square feet in area. Buildings or facilities having a gross
building area of more than 62,000 square feet shall be provide with two separate and approved fire
apparatus access roads.
Exception: Projects having a gross building area of up to 124,000 square feet that have a single
approved fire apparatus access road when all building are equipped throughout with approved
automatic sprinkler systems.
Will comply.
D104.3 Remoteness. Where two fire apparatus access roads are required, they shall be placed a distance
apart equal to not less than one half of the length of the maximum overall diagonal dimension of the lot or
area to be served, measured in a straight line between accesses.
Will comply.
30’ Tall Buildings - Maintain aerial fire apparatus access roads as per Appendix D of the 2012 Arkansas
Fire Prevention Code Vol. 1 Section D105.1 – D105.4
Will comply.
D105.1 Where Required. Where the vertical distance between the grade plane and the highest roof surface
exceed 30’, approved aerial fire apparatus access roads shall be provided. For the purposes of this section
the highest roof surfaces shall be determined by measurement to the eave of a pitched roof, the
intersection of a roof to the exterior wall, or the top of the parapet walls, whichever is greater.
Will comply.
D105.2 Width. Aerial fire apparatus access roads shall have a minimum unobstructed with of 26’, exclusive
of shoulders, in the immediate vicinity of the building or portion thereof.
Will comply
D105.3 Proximity to building. At least one of the required access routes meeting this condition shall be
located within a minimum of 15 feet and a maximum of 30 feet from the building, and shall be positioned
parallel to one entire side of the building. The side of the building on which the aerial fire apparatus access
road is positioned shall be approved by the fire code official.
Will comply.
D105.4 Obstructions. Overhead utility and power lines shall not be located over the aerial fire apparatus
access road or between the aerial fire apparatus road and the building. Other obstructions shall be
permitted to be places with the approval of the fire code off icial.
Will comply.
Dead Ends.
Maintain fire apparatus access roads at dead end locations as per Appendix D of the 2012 Arkansas Fire
Prevention Code Vol. 1 Section D103.4 Dead Ends. Dead -end fire apparatus access roads in excess of
150 feet shall be provided with width and turnaround provisions in accordance with Table D103.4.
Requirements for Dead-end fire apparatus access roads.
Will comply.
Gates
Maintain fire apparatus access road gates as per Appendix D of the 2012 Arkansas Fire Prevention Code
Vol. 1 Section D103.5 Fire apparatus access road gates. Gates securing the fire apparatus access roads
shall comply with all of the following criteria:
1. Minimum gate width shall be 20 feet.
2. Gates shall be of swinging or sliding type.
3. Construction of gates shall be of material that allow manual operation by one person.
4. Gate components shall be maintained in an operable condition at all times and replaces or repaired
when defective.
5. Electric gates shall be equipped with a means of opening the gate by fire department personnel for
emergency access. Emergency opening devices shall be approved by the fire code official.
6. Manual opening gates shall not be locked with a padlock or chain and padlock unless they are capable
of being opened by means of forcible entry tools or when a key box containing the keys to the lock is
installed at the gate location.
7. Locking device specifications shall be submitted for approval \by the fire code official
8. Electric gate operators, where provided, shall be listed in accordance with UL 325.
9. Gates, intended for automatic operation shall be designed, constructed and installed to comply with
requirements of ASTM F 2200.
Will comply.
Fire Hydrants
Locate Fire Hydrants as per Appendix C of the 2012 Arkansas Fire Prevention Code. Section C101 –
C105, in conjunction with Central Arkansas Water (Daniel Tull 501 -377-1245) and the Little Rock Fire
Marshals Office (Capt. Tony Rhodes 501-918-3757, or Fire Marshal Derek N Ingram 501-918-3756
Number and Distribution of Fire Hydrants as per Table C105.1.
Will comply.