HomeMy WebLinkAbout2019.01.07 - Inspection ReportInspection Report
Steve Harrelson
Property Address:
1321 Scott Street
Little Rock AR 72202
Authentic Inspection Services, Inc.
Wayne Pace HI-1265
www.authentic-inspection.com
501-664-7233
Table of Contents
Cover Page .......................................................................1
Table of Contents .............................................................2
Intro Page .........................................................................3
1 STRUCTURAL COMPONENTS .........................................4
2 EXTERIOR ....................................................................12
3 ROOFING .....................................................................18
4 PLUMBING SYSTEM ......................................................24
5 ELECTRICAL SYSTEMS .................................................29
6 HEATING ......................................................................38
7 CENTRAL AIR CONDITIONING ......................................41
8 INTERIORS ...................................................................44
9 INSULATION AND VENTILATION ...................................51
10 FIREPL ACES AND SOLID FUEL BURNING APPLIANCES53
11 BUILT-IN KITCHEN APPLIANCES ..................................55
Repair Summary ............................................................57
Maintenance Summary ..................................................64
Authentic Inspection Services, Inc.Harrelson
1321 Scott Street Page 2 of 72
Date:1/7/2019 Time:09:00 AM Report ID:B5478
Property:
1321 Scott Street
Little Rock AR 72202
Customer:
Steve Harrelson
Real Estate Professional:
Comment Key or Definitions
The following definitions of comment descriptions represent this inspection report. All comments by the
inspector should be considered before purchasing this home. Any recommendations by the inspector to
repair or replace suggests a second opinion or further inspection by a qualified contractor. All costs
associated with further inspection fees and repair or replacement of item, component or unit should be
considered before you purchase the property. Acceptance of this report or any part of this report indicates full
agreement with all terms and conditions of the Authentic Inspection Services, Inc. Agreement for Home
Inspection Services. The electronic home inspection report is the concluding or final version of this home
inspection report and should be viewed.
Inspected (IN)= I visually observed the item, component or unit and if no other comments were made then
it appeared to be functioning as intended allowing for normal wear and tear.
Not Inspected (NI)= I did not inspect this item, component or unit and made no representations of whether
or not it was functioning as intended and will state a reason for not inspecting.
Not Present (NP)= This item, component or unit is not in this home or building.
Repair or Replace (RR)= The item, component or unit is not functioning as intended or needs further
inspection by a qualified contractor. Items, components or units that can be repaired to satisfactory condition
may not need replacement.
OUTBUILDING(S) ON SITE WERE NOT EVALUATED AS PART OF THIS INSPECTION. THIS IS FOR
YOUR INFORMATION.
Age Of Structure:
1881 Construction
Main Entrance Faces:
West
Client Is Present:
Yes
Weather:
Cloudy
Temperature:
55 Degrees
Rain in last 3 days:
Yes
Occupancy:
Vacant with items remaining
Authentic Inspection Services, Inc.Harrelson
1321 Scott Street Page 3 of 72
1.STRUCTURAL COMPONENTS
The Home Inspector shall observe structural components including foundations, floors, walls, ceilings and r oof. The home inspector shall
describe the type of Foundation, floor structure, wall structure, columns or piers, ceiling structure, roof structure. The home inspector
shall: Probe structural components where deterioration is suspected; Enter under floor crawl spaces, basements, and attic spaces except
when access is obstructed, when entry could damage the property, or when dangerous or adverse situations are suspected; Report the
methods used to observe under floor crawl spaces and attics; and Report signs of abnormal or harmful water penetration into the
building or signs of abnormal or harmful condensation on building components. The home inspector is not required to: Enter any area or
perform any procedure that may damage the property or its components or be dangerous to or adversely effect the health of the home
inspector or other persons.
Styles & Materials
FOUNDATION:
ROCK AND MORTAR
FLOOR STRUCTURE:
2 X 8
2 X 12
WOOD JOISTS
WOOD BEAMS
POURED CONCRETE
SLAB
SUSPENDED CONCRETE SLAB
COLUMNS OR PIERS:
WOOD POST(S)
Extra Info : BRICK WALLS
WALL STRUCTURE:
2 X 4 WOOD
NOT VISIBLE IN AREAS
CEILING STRUCTURE:
2X12 WOOD
NOT VISIBLE IN AREAS
Extra Info : MOST ATTIC AREAS WERE
NOT ACCESSIBLE
ROOF STRUCTURE:
2 X 4 WOOD RAFTERS
NOT VISIBLE IN AREAS
Extra Info : MOST ATTIC AREAS WERE
NOT ACCESSIBLE
ROOF-TYPE:
LOW SLOPE
FLAT
MANSARD
METHOD USED TO OBSERVE ATTIC:
FROM ENTRY
Extra Info : MOST ATTIC AREAS WERE
NOT ACCESSIBLE
ATTIC INFO:
NO ACCESS
Extra Info : MOST ATTIC AREAS WERE
NOT ACCESSIBLE
METHOD USED TO OBSERVE
CRAWLSPACE:
WALKED
CRAWLED
AREAS WERE INNACCESSIBLE
CRAWLSPACE CONDITIONS AT TIME
OF INSPECTION:
DAMP
Extra Info : BASEMENT ALSO
Items
1.0 FOUNDATIONS (where visible)
Comments:Inspected
(1) There were minor visible signs of water intrusion present in the crawlspace at the time of the
inspection, from damp water and silt stains observed along the lower foundation walls in the basement.
There was also some signs of dry silt in areas. Moisture intrusion if not maintained can lead to other
problems including mold, and cause moisture build-up on the floor system that can lead to deterioration
and settlement over time. Maintain the gutters and any ground drains around the home. Recommend
further investigation or correction by a qualified licensed contractor or water infiltration specialist if
desired.
Authentic Inspection Services, Inc.Harrelson
1321 Scott Street Page 4 of 72
1.0 Item 1(Picture)1.0 Item 2(Picture)
(2) There are vertical stair-step crack(s) in the brick foundation walls in the crawlspace under the left
entry doors. This is typical for a home this age, but is due to some minor settlement in these ar eas.
However since opinions vary, we recommend having a qualified licensed contractor evaluate further if
desired.
1.0 Item 3(Picture)
(3) The brick walls in the crawlspace show signs of minor deterioration or sanding of the bricks in ar eas
due to age. Repairs will be needed at some point to prevent further deterioration of the walls. However,
since opinions vary, we recommend having a qualified licensed contractor evaluate further, and repair
or correct as needed.
Authentic Inspection Services, Inc.Harrelson
1321 Scott Street Page 5 of 72
1.0 Item 4(Picture)
1.0 Item 5(Picture)
(4) The small holes in the foundation wall at the rear of the home need to be sealed. Unwanted pests
could enter the crawlspace if not corrected. Recommend having a qualified contractor or person seal
where needed.
1.0 Item 6(Picture)
1.1 WALLS (Structural)
Comments:Inspected
(1) The plaster on the brick walls of the front entry shows signs of diagonal settlement cracking in areas.
This is due to some past settlement in this area of the home. However since opinions vary, we
recommend having a licensed structural engineer or contractor evaluate further for the cause if desired.
Authentic Inspection Services, Inc.Harrelson
1321 Scott Street Page 6 of 72
1.1 Item 1(Picture)
(2) The drywall and plaster on the walls shows signs of cracking over and under some windows and
doorways in the home, and on some walls in this home. This is due to some settlement or expansion or
contraction of the home over time. However since opinions vary, we recommend having a licensed
contractor evaluate further for cause if desired.
1.2 COLUMNS OR PIERS
Comments:Inspected
(1) Additional bracing and a beam have been added below the floor structure under the left side of the
kitchen. This is common under older homes and is done to provided additional support because the
original center pier system was insufficient, or to prevent deflection in the floor under certain rooms. We
are unsure of the long-term adequacy of the additional piers because they are made up of dry stacked
blocks that do not appear to have reinforced concrete footers under them. However since opinions vary,
we recommend having a qualified licensed structural engineer or contractor evaluate further.
1.2 Item 1(Picture)
(2) There is a wood dimensional vertical support installed under a beam in the basement below the rear
right entry into the kitchen. There is a dip and raised area in the floor over this area. This would not be
considered a proper pier according to today's standards. Recommend having a qualified contractor
evaluate further.
Authentic Inspection Services, Inc.Harrelson
1321 Scott Street Page 7 of 72
1.2 Item 2(Picture)1.2 Item 3(Picture)
1.3 FLOORS (Structural)
Comments:Inspected
(1) There are typical signs of fungal growth present on the floor system in the center of the basement in
areas. We did not inspect, test, or determine if the mold like substances are or are not a health hazard.
This is due to increased moisture levels under the home, or improper or insufficient vapor barriers.
Recommend contacting a mold inspector or expert for investigation or correction if needed.
1.3 Item 1(Picture)
(2) Signs of wood destroying organisms were discovered on the floor structure members in the front
center of the basement room. This damage appears to be old. Recommend having a licensed
exterminator inspect further and repair or correct as needed.
Authentic Inspection Services, Inc.Harrelson
1321 Scott Street Page 8 of 72
1.3 Item 2(Picture)
1.3 Item 3(Picture)
(3) The floor structure has some minor dips or sags in areas of this home. This is typical in older homes,
but is due to settlement of the original piers and support over time. However since opinions vary, we
recommend having a qualified licensed structural engineer evaluate further if desired and repair or
correct as needed.
1.4 CEILINGS (structural)
Comments:Inspected
1.5 ROOF STRUCTURE AND ATTIC
Comments:Inspected
(1) Rodent droppings were found in the rear right lower attic. Sometimes pests can cause damage to the
home or components, and in certain cases pest entry prevention can be expensive. Recommend having
a qualified pest control contractor evaluate further and remove or correct the problem as needed.
(2) There was no fire stop in place at the top of a wall cavity from the basement in the rear right lower
attic. A fire stop should aid in slowing the spread of fire if one should occur in the home. Recommend
having a qualified contractor install an appropriate fire stop to slow the spread of fire.
1.5 Item 1(Picture)
1.6 VIEW OF ATTIC AT TIME OF INSPECTION
Comments:Inspected
This picture of the rear right lower attic represents the view at time of inspection.
Authentic Inspection Services, Inc.Harrelson
1321 Scott Street Page 9 of 72
1.6 Item 1(Picture)
1.7 INACCESSIBLE ATTIC AREAS
Comments:Not Inspected
Due to the many angles and pitches of this roof line, most of the attic areas where not accessible. There
was access to a small amount of attic space to the right of the upstairs rear right bedroom that was
viewed from the access door due to limited space. This is for your information.
1.8 VIEW OF CRAWLSPACE AT TIME OF INSPECTION
Comments:Inspected
This picture of the crawlspace and basement areas represents the views at the time of the inspection.
Authentic Inspection Services, Inc.Harrelson
1321 Scott Street Page 10 of 72
1.8 Item 1(Picture)1.8 Item 2(Picture)
1.8 Item 3(Picture)
1.9 INACCESSIBLE CRAWLSPACE AREAS
Comments:Not Inspected
We were unable to fully access crawlspace areas under the left side of the home under the kitchen
(facing front) due to limited space between the floor structure and the ground. This is for your
information.
The structure of the home was inspected and reported on with the above information. While the inspector makes every effort to find all
areas of concern, some areas can go unnoticed. Please be aware that the inspector has your best interest in mind. Any repair items
mentioned in this report should be considered before purchase. It is recommended that qualified contractors be used in your further
inspection or repair issues as it relates to the comments in this inspection report.
Authentic Inspection Services, Inc.Harrelson
1321 Scott Street Page 11 of 72
2.EXTERIOR
The home inspector shall observe: Wall cladding, flashings, and trim; Entryway doors and a representative number of windows; Garage
door operators; Decks, balconies, stoops, steps, areaways, porches and applicable railings; Eaves, soffits, and fascias; and Vegetation,
grading, drainage, driveways, patios, walkways, and retaining walls with respect to their effect on the condition of the building. The
home inspector shall: Describe wall cladding materials; Operate all entryway doors and a representative number of windows; Operate
garage doors manually or by using permanently installed controls for any garage door operator; Report whether or not any garage door
operator will automatically reverse or stop when meeting reasonable resistance during closing; and Probe exterior wood components
where deterioration is suspected. The home inspector is not required to observe: Storm windows, storm doors, screening, shutters,
awnings, and similar seasonal accessories; Fences; Presence of safety glazing in doors and windows; Garage door operator remote
control transmitters; Geological conditions; Soil conditions; Recreational facilities (including spas, saunas, steam baths, swimming pools,
tennis courts, playground equipment, and other exercise, entertainment, or athletic facilities); Detached buildings or structures;
Presence or condition of buried fuel storage tanks; or erosion control and earth stabilization measures. Flashings for decks that are not
visible were not inspected. The home inspector is not required to: Move personal items, panels, furniture, equipment, plant life, soil,
snow, ice or debris that obstructs access or visibility. Inspector will not perform a technically exhaustive EIFS inspection as part of this
general home inspection. Any comments regarding EIFS type siding systems and items are for information only and are not part of this
inspection. The Client is urged to schedule a separate EIFS inspection with Inspector's company at a separate time, or contact a different
competent specialist if information, identification or testing of any EIFS type siding system if desired.
Styles & Materials
SIDING STYLE:
BRICK
SIDING MATERIAL:
PAINTED BRICK VENEER
EXTERIOR ENTRY DOORS:
WOOD
DRIVEWAY:
GRAVEL
PARKING LOT
AUTO OPENER MANUFACTURER:
N/A
GARAGE DOOR MATERIAL:
N/A
GARAGE DOOR TYPE:
N/A
Items
2.0 WALL CLADDING FLASHING AND TRIM
Comments:Inspected
(1) There are typical settlement crack(s) or separation in the brick siding over and under some of the
windows around the home. This is common for a home this age, but is due to some expansion and
contraction or settlement at least in the brick veneer. However since opinions vary, we recommend
having a qualified contractor evaluate further for cause and occurrence if desired, and repair or seal
cracking as needed.
2.0 Item 1(Picture)
(2) There are signs that the brick has been anchored to the wall with fasteners at the left side of the
home. Recommend having a qualified contractor evaluate further if desired.
Authentic Inspection Services, Inc.Harrelson
1321 Scott Street Page 12 of 72
(3) The paint on the lower exterior walls shows signs of flaking in areas. Old paint can contain lead which
can be harmful if consumed. Recommend having a qualified contractor prep and paint the front porch
where needed.
2.0 Item 2(Picture)
2.1 DOORS (Exterior)
Comments:Inspected
(1) The exterior entry doors, trim, and some jambs shows signs of flaking paint in areas. Deterioration
will occur over time if not corrected. Recommend having a qualified contractor prep and paint to extend
the life span of the wood materials.
2.1 Item 1(Picture)
(2) The locking hardware for the left side entry doors is damaged and missing parts. A replacement is
needed. Recommend having a qualified licensed contractor inspect further and repair or replace as
needed.
2.2 WINDOWS
Comments:Inspected
(1) There is a hole in the lower left corner of the window trim for the upper rear right window (facing
front) made by varmints. Unwanted pests or squirrels may be entering the attic or walls through the
hole. Recommend having a qualified contractor inspect further and repair or correct as needed.
Authentic Inspection Services, Inc.Harrelson
1321 Scott Street Page 13 of 72
2.2 Item 1(Picture)
(2) The paint is peeling or flaking away on some window exterior frames or trim at some windows
around the home. There are also signs of minor deterioration in areas around some windows.
Recommend having a qualified contractor or person prep and paint where needed to prevent
deterioration over time.
2.2 Item 2(Picture)2.2 Item 3(Picture)
(3) The gaps around the exterior sides of windows should be sealed, especially around some of the
upper windows. Moisture could enter behind the brick resulting in deterioration if not corrected.
Recommend having a qualified contractor or person seal the gaps where needed.
(4) The window screens are missing, or have not been installed on the home. Recommend having a
qualified contractor or person install screens where needed.
2.3 DECKS, BALCONIES, STOOPS, STEPS, AREAWAYS, PORCHES AND APPLICABLE RAILINGS
Comments:Inspected
(1) The concrete front steps at the front of the home have cracked and settled in the middle over time.
Recommend having a qualified contractor evaluate further, and repair or correct if needed.
Authentic Inspection Services, Inc.Harrelson
1321 Scott Street Page 14 of 72
2.3 Item 1(Picture)
(2) There is no hand rail for the steps at the front of the home. Recommend having a qualified contractor
install hand rails where there are 3 or more steps for safety reasons. A fall or injury could occur if not
corrected.
(3) There are gaps in the grout and between some tiles around the edges of the front porch. Moisture
intrusion and deterioration could occur over time if not corrected. Recommend having a qualified
contractor seal where needed to prevent possible moisture intrusion.
2.3 Item 2(Picture)2.3 Item 3(Picture)
2.3 Item 4(Picture)
Authentic Inspection Services, Inc.Harrelson
1321 Scott Street Page 15 of 72
(4) The edges of the wood porch floor at the rear of the home shows signs of deterioration in areas.
Further deterioration may occur if not repaired. Recommend having a qualified licensed contractor
inspect further and repair or replace as needed.
2.3 Item 5(Picture)
(5) The paint on the rear and left side porches show signs of flaking in areas. Old paint can contain lead
which can be harmful if consumed. Recommend having a qualified contractor prep and paint the front
porch where needed.
We did not inspect, test or determine if the paint on the interior or exterior of this home contains lead, or
if it is or is not a health hazard. Recommend you contact a specialist or expert for investigation or
correction if desired.
(6) The hand and guard rails for the rear deck are missing proper spacing between the vertical pickets
according to today's standards. Recommend having a qualified contractor install rails with a maximum
space between vertical pickets of four inches for the guardrails, and where there are 3 or more steps. A
fall or injury could occur if not corrected.
(7) The steps or porch at the left side of home show signs of separation around the edges. Recommend
having a qualified contractor inspect further and seal the gaps where needed to prevent moisture from
entering under the steps.
2.4 EAVES, SOFFITS AND FASCIAS (Where accessible from ground level)
Comments:Inspected
2.5 VEGETATION, GRADING, SURFACE DRAINAGE AND RETAINING WALLS (With respect to their
effect on the condition of the building)
Comments:Inspected
The minor negative slope or low area at the rear left sidewalk allows water to pool in this area.
Recommend having a qualified contractor regrade, or improve the drainage in this areas.
Authentic Inspection Services, Inc.Harrelson
1321 Scott Street Page 16 of 72
2.5 Item 1(Picture)
2.6 WALKWAYS, PATIOS, AND DRIVEWAYS LEADING TO DWELLING ENTRANCES
Comments:Inspected
There is typical settlement cracking in areas. Recommend having a qualified contractor or person seal
cracks to prevent further cracking over time.
2.7 GARAGE DOOR OPERATORS (Report whether or not doors will reverse when met with
resistance)
Comments:Not Present
The exterior of the home was inspected and reported on with the above information. While the inspector makes every effort to find all
areas of concern, some areas can go unnoticed. Please be aware that the inspector has your best interest in mind. Any repair items
mentioned in this report should be considered before purchase. It is recommended that qualified contractors be used in your further
inspection or repair issues as it relates to the comments in this inspection report.
Authentic Inspection Services, Inc.Harrelson
1321 Scott Street Page 17 of 72
3.ROOFING
The home inspector shall observe: Roof covering; Roof drainage systems; Flashings; Skylights, chimneys, and roof penetrations; and
Signs of' leaks or abnormal condensation on building components. The home inspector shall: Describe the type of roof covering
materials; and Report the methods used to observe the roofing. The home inspector is not required to: Walk on the roofing; Observe
interiors of flues or chimneys which are not readily accessible; or Observe attached accessories including but not limited to solar
systems, antennae, and lightning arrestors. We did not confirm whether or not there is a proper membrane, underlayment, or water
proofing (ie. felt paper or ice shield) under the roof coverings. We did not confirm whether or not there was proper membrane,
underlayment, or water proofing (felt paper or ice shield) under the roof coverings.
Styles & Materials
ROOF COVERING:
METAL
RUBBER MEMBRANE
SLATE
ROLL/SELVAGE
COPPER
VIEWED ROOF COVERING FROM:
LADDER
WALKED ROOF
BINOCULARS
SKY LIGHT (S):
NONE
CHIMNEY (exterior):
BRICK
Items
3.0 ROOF COVERINGS
Comments:Inspected, Not Inspected
(1) Views of the roof for your information.
Authentic Inspection Services, Inc.Harrelson
1321 Scott Street Page 18 of 72
3.0 Item 1(Picture)3.0 Item 2(Picture)
3.0 Item 3(Picture)
(2) The upper roof coverings and components were inspected from a ladder leaned against a brick
chimney, the ground, and from binoculars. We did not walk on the upper roof because we did not lay a
ladder on the slate tiles around the edges to prevent damage. We walked the lower rear left roof. There
may be portions of the roof that were not visible. This is for your information.
(3) The slate shingles shows signs of damage in multiple areas around the home. There is also corner
trim that is missing on the corners of the mansard roof lines in multiple areas. Damaged slate, and
missing trim should be repaired or replaced as soon as possible to prevent possible leaking and
deterioration over time. Recommend having a qualified licensed roofing contractor inspect further and
repair or replace as needed.
Authentic Inspection Services, Inc.Harrelson
1321 Scott Street Page 19 of 72
3.0 Item 4(Picture)3.0 Item 5(Picture)
3.0 Item 6(Picture)3.0 Item 7(Picture)
(4) Leaves and other debris on the roof covering should be removed to allow water to drain properly
from roof. Areas covered in debris were not visible.
(5) Tree limbs that are in contact with the roof, or hanging near roof should be trimmed. Recommend
having a qualified contractor or person trim limbs as needed.
(6) Recommend monitoring periodically for leaks where satellite dish mounts are secured to the rear
lower left roof. The sealer that is often applied at the fasteners can separate over time.
3.1 ROOFING DRAINAGE SYSTEMS
Comments:Inspected
(1) The gutter troughs have debris in them in most areas. Gutters that drain poorly or are clogged can
lead to many costly problems such as deterioration of fascia, soffit or roof edge. It can also cause
gutters to pull loose and lead to possible water intrusion. Recommend cleaning and maintaining the
gutters troughs and downspouts on a regular basis.
Authentic Inspection Services, Inc.Harrelson
1321 Scott Street Page 20 of 72
3.1 Item 1(Picture)
(2) The gutter downspout is missing the lower section at the front left corner of the home (facing front).
Erosion can occur if not corrected, possibly leading to water intrusion under the home. Recommend
having a qualified licensed contractor inspect further and repair or replace the downspout as needed.
3.1 Item 2(Picture)
(3) The gutter downspout needs to be extended out of the flower bed at the rear left corner of the home
(facing front). Erosion can occur if not corrected, possibly leading to water intrusion under the home.
Recommend having a qualified licensed contractor inspect further and repair or replace as needed.
Authentic Inspection Services, Inc.Harrelson
1321 Scott Street Page 21 of 72
3.1 Item 3(Picture)
3.2 FLASHINGS
Comments:Inspected, Not Inspected
(1) There is a tape material installed where the edges of the roof and walls meet around some dormers
and chimneys at the rear of the home. There are signs of active leaking in these areas (SEE 8.0(1)). This
is not adequate, and proper flashings should be installed to prevent further moisture intrusion and
deterioration in the future. Recommend having a licensed roofing contractor install proper flashings
where needed.
Authentic Inspection Services, Inc.Harrelson
1321 Scott Street Page 22 of 72
3.2 Item 1(Picture)3.2 Item 2(Picture)
3.2 Item 3(Picture)
(2) The upper roof coverings and components were inspected from a ladder leaned against a brick
chimney, the ground, and from binoculars. We did not walk on the upper roof because we did not lay a
ladder on the slate tiles around the edges to prevent damage. We walked the lower rear left roof. There
may be portions of the roof that were not visible. This is for your information.
3.3 SKYLIGHTS, CHIMNEYS AND ROOF PENETRATIONS
Comments:Inspected
The roof of the home was inspected and reported on with the above information. While the inspector makes every effort to find all areas
of concern, some areas can go unnoticed. Roof coverings and skylights can appear to be leak proof during inspection and weather
conditions. Our inspection makes an attempt to find a leak but sometimes cannot. Please be aware that the inspector has your best
interest in mind. Any repair items mentioned in this report should be considered before purchase. It is recommended that qualified
contractors be used in your further inspection or repair issues as it relates to the comments in this inspection report.
Authentic Inspection Services, Inc.Harrelson
1321 Scott Street Page 23 of 72
4.PLUMBING SYSTEM
The home inspector shall observe: Interior water supply and distribution system, including: piping materials, supports, and insulation;
fixtures and faucets; functional flow; leaks; and cross connections; Interior drain, waste, and vent system, including: traps; drain, waste,
and vent piping; piping supports and pipe insulation; leaks; and functional drainage; Hot water systems including: water heating
equipment; normal operating controls; and chimneys, flues, and vents; Fuel storage and distribution systems; Drainage pumps and
Sump pumps. The home inspector shall describe: Water supply and distribution piping materials; Drain, waste, and vent piping
materials; Water heating equipment; and Location of main water supply and fuel shutoff devices. The home inspector shall operate
plumbing fixtures. The home inspector is not required to: State the effectiveness of anti-siphon devices; Determine whether water supply
and waste disposal systems are public or private or the quantity or quality of the water supply; Light pilot lights; Operate automatic
safety controls; Operate any valve except water closet flush valves, fixture faucets, and hose faucets; Observe: Water conditioning
systems; Solar water heating systems; Fire and lawn sprinkler systems; On-site water supply quantity and quality; On-site or private
waste disposal systems; Foundation irrigation systems; Cloths washing machine connections; Interiors of flues or chimneys which are not
readily accessible; wells, well pumps, or water storage related equipment; Spas, except as to functional flow and functional drainage;
Swimming pools; Solar water heating equipment; or Observe the system for proper sizing, design, or use of proper materials. SHOWER
PANS MAY NOT SHOW SIGNS OF LEAKING AT THE TIME OF THE INSPECTION IF THE SHOWER HAS NOT BEEN OPERATED FOR SOME TIME
OR LENGTHY PERIODS OF TIME.
Styles & Materials
WATER SUPPLY
SOURCE:
PUBLIC
WATER SUPPLY:
COPPER
WHERE VISIBLE
PLUMBING DISTRIBUTION:
COPPER
PEX
WHERE VISIBLE
PLUMBING WASTE:
PVC
CAST IRON
COPPER
WHERE VISIBLE
VENT PIPING:
COPPER
WATER HEATER POWER
SOURCE:
ELECTRIC
WATER HEATER
CAPACITY:
40 GAL (1-2 PEOPLE)
WATER HEATER MANUFACTURER:
WHIRLPOOL
Serial Number : 0408105988 MFR DATE 2004 (Located in the
basement)
Items
4.0 WATER SUPPLY AND DISTRIBUTION SYSTEMS, FIXTURES AND FAUCETS
Comments:Inspected
(1) The spray nozzle at the kitchen sink leaks at the connection to the hose. Repairs are needed.
Recommend having a qualified licensed plumber inspect further and repair or correct as needed.
4.0 Item 1(Picture)
(2) The faucet at the kitchen sink partially clogged, or has lower volume or pressure. The cause of a
clogged or partially clogged supply line could range from the aerator needs cleaning or a more involved
Authentic Inspection Services, Inc.Harrelson
1321 Scott Street Page 24 of 72
correction may be needed. Recommend having a qualified licensed plumber inspect further and repair
or correct as needed.
(3) The bathtub spout for the upstairs bathroom tub is installed inside the rim of the bathtub which is
potentially below the water line. This can result in backflow or cross connection of dirty contaminated
water back into the water supply of the home. This is for your information. Recommend having a
qualified plumber inspect further if desired.
4.0 Item 2(Picture)
(4) The outside water faucet at the left side of the home (facing front) has been disconnected, and is no
longer functional. This is for your information. Recommend having a qualified licensed plumber inspect
further and repair or replace if desired.
4.1 INTERIOR DRAIN, WASTE AND VENT SYSTEMS
Comments:Inspected
(1) The plumbing drain line shows signs of minor active leaking at the connection to the bottom of the
downstairs hall bathroom sink. Repairs are needed. Recommend having a qualified licensed plumber
inspect further and repair or correct as needed.
4.1 Item 1(Picture)
(2) The toilet in the upstairs hall bathroom does not re-fill properly. Repairs may be needed. Recommend
having a qualified licensed plumber inspect further and repair or correct as needed.
(3) The bathroom sink stopper is missing in the upstairs hall bathroom. Recommend having a qualified
plumber or person replace the stopper as needed.
Authentic Inspection Services, Inc.Harrelson
1321 Scott Street Page 25 of 72
4.2 WATER HEATER SYSTEMS, CONTROLS, CHIMNEYS, FLUES AND EXHAUST VENTS
Comments:Inspected, Not Inspected
(1) The water heater is old and past typical life expectancy. We are unable to determine life remaining.
Our company did not inspect the water heater for proper operation because there was no electrical
power to the water heater at the time of the inspection. You should budget to have this water heater
replaced in the near future.
(2) The T&P (Temperature and Pressure) valve pipe for the water heater terminates in the right
basement room, and needs a 3/4 approved piping material to extend to the exterior of the home if
possible to prevent water intrusion in the crawlspace if the valve should open and stick. PVC piping is
also currently being used, which is not an approved material because it can melt due to super heated
water if the T&P valve opens. Melting of the PVC can result in restrictions in the piping that can prevent
proper release of pressure from the water heater and damage to the home. Recommend having a
qualified licensed plumber replace the T&P piping as needed.
4.2 Item 1(Picture)
(3) There was minor signs of water dripping from the water heater T&P (Temperature and Pressure)
valve pipe that exits in the basement. This indicates problems with the T&P valve, or thermal expansion
in the water system of the home. Further inspection is needed by a qualified plumber. Recommend
having a qualified licensed plumber inspect further and repair or replace as needed.
4.3 FUEL STORAGE AND DISTRIBUTION SYSTEMS (Interior fuel storage, piping, venting,
supports, leaks)
Comments:Inspected
A gas detector was used to confirm active gas leaks at a gas line elbow connection in the
basement near the furnace, and at the valve for the fireplace in the front right room which is
dangerous. Also, the mercaptan additive which adds odor to natural gas is a health concern
because it displaces the oxygen in the air. This is a life safety issue and should be addressed
as soon as possible. Recommend further inspection and repair by a licensed plumber.
Authentic Inspection Services, Inc.Harrelson
1321 Scott Street Page 26 of 72
4.3 Item 1(Picture)4.3 Item 2(Video) SEE VIDEO
4.3 Item 3(Picture)
4.4 DRAINAGE PUMPS, SUMP PUMPS AND RELATED PIPING
Comments:Not Present
4.5 MAIN WATER SHUT-OFF DEVICE (Describe location)
Comments:Inspected
The main water shut off is the valve located outside at the meter in the front yard near the street. There
is an additional shut-off located in right center basement room. This is for your information.
Authentic Inspection Services, Inc.Harrelson
1321 Scott Street Page 27 of 72
4.5 Item 1(Picture)4.5 Item 2(Picture)
4.6 MAIN FUEL SHUT-OFF DEVICE (Describe location)
Comments:Inspected
The main fuel shut-off is located on the exterior left side of the home (facing front) at the meter. This is
for your information.
4.6 Item 1(Picture)
The plumbing in the home was inspected and reported on with the above information. While the inspector makes every effort to find all
areas of concern, some areas can go unnoticed. Washing machine drain line for example cannot be checked for leaks or the ability to
handle the volume during drain cycle. Older homes with galvanized supply lines or cast iron drain lines can be obstructed and barely
working during an inspection but then fails under heavy use. If the water is turned off or not used for periods of time (like a vacant home
waiting for closing) rust or deposits within the pipes can further clog the piping system. Please be awar e that the inspector has your best
interest in mind. Any repair items mentioned in this report should be considered before purchase. It is recommended that qualified
contractors be used in your further inspection or repair issues as it relates to the comments in this inspection report.
Authentic Inspection Services, Inc.Harrelson
1321 Scott Street Page 28 of 72
5.ELECTRICAL SYSTEMS
The home inspector shall observe: Service drop; Service entrance conductors; Service equipment, grounding equipment, main over
current device, and main and distribution panels; Amperage and voltage ratings of the service; Branch circuit conductors, their over
current devices, The operation of a representative number of installed ceiling fans, lighting fixtures, switches and receptacles located
inside the house, garage, and on the dwelling's exterior walls; The polarity and grounding of all receptacles within six feet of interior
plumbing fixtures; The operation of ground fault circuit interrupters; The home inspector shall describe: Service amperage and voltage;
Service entry conductor materials; Branch wiring methods and Location of main and distribution panels. The home inspector shall report
any observed visible aluminum branch circuit wiring. The home inspector shall report on presence or absence of smoke detectors if
accessible; The home inspector is not required to: Insert any tool, probe, or testing device inside the panels; Test or operate any over
current device except ground fault circuit interrupters; Dismantle any electrical device or control other than to remove the covers of the
main and auxiliary distribution panels; Measure amperage, voltage, or impedance; or Observe: Remote control devices unless the device
is the only control device; Low voltage systems; Alarm systems and components, heat detectors, or carbon monoxide detectors;
Telephone, security, cable TV, intercoms, or other ancillary wiring that is not a part of the primary electrical distribution system; or Built-
in vacuum equipment.
Styles & Materials
ELECTRICAL SERVICE CONDUCTORS:
OVERHEAD SERVICE
COPPER
240 VOLTS
MAIN PANEL CAPACITY:
200 AMP (MAX)
FUSED PULL DISCONNECT
MAIN ELEC. PANEL MANUFACTURER:
GENERAL ELECTRIC
SUB ELEC. PANEL(S) MANUFACTURER:
MARS
MURRAY
SQUARE D
PANEL TYPES:
CIRCUIT BREAKERS
MANUAL DISCONNECT
FUSED MANUAL DISCONNECT
BRANCH WIRE 15 and 20 AMP:
COPPER
WIRING METHODS:
ROMEX
Items
5.0 SERVICE DROP
Comments:Inspected
5.1 SERVICE ENTRANCE CONDUCTORS
Comments:Inspected
5.2 SERVICE AND GROUNDING EQUIPMENT, MAIN OVERCURRENT DEVICE, MAIN AND
DISTRIBUTION PANELS
Comments:Inspected
(1) Problem(s) discovered in the main fused electrical disconnect panel located on a pole in the back
yard, such as a large knock-out missing on the side of the panel, double wiring at the main lugs for a sub
panel which provides no over current protection, signs of possible overheating of the right fuse, and any
other problems that an electrician may discover while performing repairs need correcting. Electrical
issues are a hazard until repaired. Recommend having a licensed electrician inspect further and repair or
upgrade this electrical panel as needed.
Authentic Inspection Services, Inc.Harrelson
1321 Scott Street Page 29 of 72
5.2 Item 1(Picture)5.2 Item 2(Picture)
5.2 Item 3(Picture)
(2) Problem(s) discovered in the sub electrical panel located on the pole in the back yard, such as
hole(s) in the interior cover not plugged where breakers or knock-out(s) have been removed, and any
other problems that an electrician may discover while performing repairs need correcting. Electrical
issues are a hazard until repaired. Recommend having a licensed electrician inspect further and repair or
correct as needed.
5.2 Item 4(Picture)
Authentic Inspection Services, Inc.Harrelson
1321 Scott Street Page 30 of 72
(3) Problem(s) discovered in the sub electrical panel located in the basement near the base of the stairs,
such as double wiring at a circuit breaker, one unused wiring not properly capped, and any other
problems that an electrician may discover while performing repairs need correcting. Electrical issues are
a hazard until repaired. Recommend having a licensed electrician inspect further and repair or correct as
needed.
5.2 Item 5(Picture)5.2 Item 6(Picture)
(4) Problem(s) discovered in the sub electrical panel located at the upstairs exterior air conditioning
compressor unit on the rear roof, such as melted or overheated branch wiring, the interior panel cover
missing, and any other problems that an electrician may discover while performing repairs need
correcting. Electrical issues are a hazard until repaired. Recommend having a licensed electrician inspect
further and repair or correct as needed.
5.2 Item 7(Picture)
(5) The information plate on the upstairs exterior central air conditioner compressor indicates that the
maximum amp circuit breaker for protecting the unit should be a 60 amp circuit breaker, and it is
serviced by a 70 amp circuit breaker in the sub electrical panel located near the unit. Electrical issues
are a hazard until repaired. Recommend having a licensed electrician reduce the breaker size as needed
to prevent additional damage to the unit if the unit should fail.
(6) The interior panel covers are missing from the sub electrical panels located at the upstairs air
conditioning equipment on the rear roof, and for the disconnect panel located at the downstairs exterior
air conditioning equipment. Even though these are small repairs, it is a potential safety issue.
Recommend having a qualified electrician install proper interior covers as needed.
Authentic Inspection Services, Inc.Harrelson
1321 Scott Street Page 31 of 72
(7) The electrical disconnect panel at the downstairs exterior air conditioning equipment is loose from
the wall, and needs to be properly secured. Electrical issues are a hazard until repaired. Recommend
having a licensed electrician inspect further and repair or correct as needed.
5.2 Item 8(Picture)
5.3 ARE ALL THE CIRCUITS OR FUSES LABELED CLEARLY
Comments:Inspected
Not all of the circuits in the electrical panels(s) are labeled, and should be labeled for safety reasons.
5.4 BRANCH CIRCUIT CONDUCTORS, OVERCURRENT DEVICES AND COMPATIBILITY OF THEIR
AMPERAGE AND VOLTAGE
Comments:Inspected
(1) The flexible protective electrical conduit for branch wiring entering the upstairs exterior air
conditioning compressor unit on the roof is loose, and should be repaired or corrected. Damage to the
branch wiring could occur if not corrected. Recommend having a licensed electrician inspect further and
repair or correct as needed.
5.4 Item 1(Picture)
(2) Improper electrical wiring should be repaired. There is unused, uncapped, energized branch wiring
exiting the left wall of the kitchen that needs to be placed inside a covered junction box or be removed.
Electrical issues are a hazard until repaired. Recommend having a licensed electrician repair or correct
as needed.
Authentic Inspection Services, Inc.Harrelson
1321 Scott Street Page 32 of 72
5.4 Item 2(Picture)
(3) All electrical unused wiring or connections should be made in junction boxes fitted with cover plates.
There is uncapped, energized branch wiring exiting a box located in the basement under the front left
room that needs to be properly capped, and fitted with a cover plate. While this is a small repair,
electrical issues are a hazard until repaired. Recommend having a qualified electrician install a cover
plate as needed.
5.4 Item 3(Picture)
(4) An extension cord routed through a rear window should not be used as permanent wiring at the rear
exterior of the home, to service electrical power to the irrigation system control panel. Strand wiring can
break down over time resulting in electrical hazards, because extension cord wiring was not designed for
permanent use. Recommend having a licensed electrician install an electrical outlet near the ir rigation
control panel as needed.
Authentic Inspection Services, Inc.Harrelson
1321 Scott Street Page 33 of 72
5.4 Item 4(Picture)
5.5 CONNECTED DEVICES AND FIXTURES (Observed from a representative number operation of
ceiling fans, lighting fixtures, switches and receptacles located inside the house, garage,
and on the dwelling's exterior walls. No cover plates were removed.)
Comments:Inspected
(1) The duplex three prong outlet in the right rear floor of the upstairs front center room is broken or
damaged. Electrical issues are considered a hazard until repaired. Recommend having a qualified
licensed electrician replace this outlet as needed.
5.5 Item 1(Picture)
(2) A duplex three prong outlet in the upstairs front left bedroom broken or damaged. Electrical issues
are considered a hazard until repaired. Recommend having a qualified licensed electrician replace this
outlet as needed.
Authentic Inspection Services, Inc.Harrelson
1321 Scott Street Page 34 of 72
5.5 Item 2(Picture)
(3) The duplex three prong outlet on the front wall in the upstairs front right room was not operating, or
had no electrical power to it at the time of the inspection. Electrical issues are a hazard until repaired.
Recommend having a qualified licensed electrician inspect further and repair or correct as needed.
(4) The duplex three prong outlet on the floor in the downstairs rear right room was not operating, or
had no electrical power to it at the time of the inspection. Electrical issues are considered a hazard until
repaired. Recommend having a qualified licensed electrician inspect further and repair or correct as
needed.
(5) The duplex three prong outlets on the floor in the upstairs center room was not operating, or had no
electrical power to them at the time of the inspection. Electrical issues are considered a hazard until
repaired. Recommend having a qualified licensed electrician inspect further and repair or replace as
needed.
(6) Most of the duplex three prong outlets in the downstairs rooms tested "reverse polarity" or is
incorrectly wired. Electrical issues are considered a hazard until repaired. Recommend having a qualified
licensed electrician inspect further and repair or correct as needed.
(7) The duplex three prong outlets in the upstairs rear left room tested "reverse polarity" or is incorrectly
wired. Electrical issues are considered a hazard until repaired. Recommend having a qualified licensed
electrician inspect further and repair or correct as needed.
(8) The duplex three prong outlet(s) in the upstairs front right bedroom tested "reverse polarity" or is
incorrectly wired. Electrical issues are considered a hazard until repaired. Recommend having a qualified
licensed electrician inspect further and repair or correct as needed.
(9) The duplex three prong outlets in the upstairs rear left bedroom tested "reverse polarity" or is
incorrectly wired. Electrical issues are considered a hazard until repaired. Recommend having a qualified
licensed electrician inspect further and repair or correct as needed.
(10) The wall switch to the left of the sink in the kitchen is missing a cover-plate. This is a small repair,
but electrical issues are a hazard until repaired. Recommend having a qualified electrician or person
install a cover plate for safety reasons.
Authentic Inspection Services, Inc.Harrelson
1321 Scott Street Page 35 of 72
5.5 Item 3(Picture)
(11) The duplex three prong outlet on the rear floor in center left room is loose in the floor or mounting
box, and needs to be secured. This is a small repair, but electrical issues are a hazard until repaired.
Recommend having a qualified electrician inspect further and repair or correct as needed.
(12) The light fixtures on the rear wall in the downstairs rear right room did not operate at the time of
the inspection. Try replacing the bulbs first, or have a qualified electrician inspect further and repair if
needed.
(13) The original doorbell did not operate at the time of the inspection. Recommend having a qualified
contractor repair or replace as needed.
(14) Do not store items on the upper shelves of the upstairs closets that could come in contact with the
light bulbs. A fire could result if combustible items are resting on hot bulbs. This is for your information.
(15) We were unable to determine the purpose of the light switch on the front wall of the center left
room. This is for your information.
5.6 POLARITY AND GROUNDING OF ACCESSIBLE RECEPTACLES WITHIN 6 FEET OF INTERIOR
PLUMBING FIXTURES, SERVICING MAJOR APPLIANCES, AND ACCESSIBLE RECEPTACLES IN
GARAGE, CARPORT, AND EXTERIOR WALLS OF INSPECTED STRUCTURE
Comments:Inspected
5.7 OPERATION OF GFCI (GROUND FAULT CIRCUIT INTERRUPTERS)
Comments:Inspected
(1) The outlet(s) over the kitchen countertops, and in the bathrooms are not GFCI (Ground Fault Circuit
Interrupt) protected. Even though GFCI protection may have not been required when the home was
built, and there is no requirement to upgrade, these outlet(s) should be upgraded to GFCI outlet(s) for
safety reasons. Recommend having a qualified licensed electrician upgrade as needed.
(2) There were no outlets found in the downstairs bathroom. Recommend having a duplex GFCI (Ground
Fault Circuit Interrupt) outlet installed by a licensed electrician to reduce the possible use of extension
cords from non GFCI protected outlets.
5.8 REPORT ON THE PRESENCE OF VISIBLE SOLID CONDUCTOR ALUMINUM BRANCH CIRCUIT
WIRING
Comments:Not Present
5.9 SMOKE DETECTORS
Comments:Inspected
All of the smoke detectors should be tested upon moving into the home, and twice a year thereafter.
Recommend adding smoke detectors to the bedrooms and in other appropriate areas of the home for
safety.
Authentic Inspection Services, Inc.Harrelson
1321 Scott Street Page 36 of 72
5.10 LOCATION OF MAIN AND DISTRIBUTION PANELS
Comments:Inspected
The main electrical panel box is located on a pole in the back yard. The sub panel boxes are located in
the rear center basement room, near the water heater in the basement, on a pole in the back yard,
and at the exterior air conditioning compressor units. This is for your information.
5.10 Item 1(Picture)
5.10 Item 2(Picture)
5.10 Item 3(Picture)
5.10 Item 4(Picture)
The electrical system of the home was inspected and reported on with the above information. While the inspector makes every effort to
find all areas of concern, some areas can go unnoticed. Outlets were not removed and the inspection was only visual. Any outlet not
accessible (behind the refrigerator for example) was not inspected or accessible. Please be aware that the inspector has your best
interest in mind. Any repair items mentioned in this report should be considered before purchase. It is recommended that qualified
contractors be used in your further inspection or repair issues as it relates to the comments in this inspection report.
Authentic Inspection Services, Inc.Harrelson
1321 Scott Street Page 37 of 72
6.HEATING
The home inspector shall observe permanently installed heating systems including: Heating equipment; Normal operating controls;
Chimneys, flues, and vents, where readily visible; and the presence of an installed heat source in each room. The home inspector shall
describe: Energy source; and Heating equipment and distribution type. The home inspector shall operate the systems using nor mal
operating controls. The home inspector shall open readily openable access panels provided by the manufacturer or installer for routine
homeowner maintenance. The home inspector is not required to: Operate heating systems when weather conditions or other
circumstances may cause equipment damage; Operate automatic safety controls; Ignite or extinguish pilot lights; or Observe: Units that
do not respond to normal operating controls; The interior of flues or chimneys; Heat exchangers; Humidifiers or dehumidifiers; Electronic
air filters; Solar space heating systems or The uniformity or heat supply adequacy and distribution balance to the various rooms.
Styles & Materials
HEAT TYPE:
FORCED AIR
ENERGY
SOURCE:
NATURAL
GAS
NUMBER OF HEAT SYSTEMS
(excluding wood):
TWO
CENTRAL HEAT BRAND:
HEIL
Serial # : Downstairs A044703191 MFR DATE NOV 2004 Upstairs
L980516499 ESTIMATE MFR DATE 1998
DUCTWORK:
INSULATED
METAL
FILTER TYPES:
DISPOSABLE
Items
6.0 HEATING EQUIPMENT (Our company is not required to inspect the heat exchanger
component of the unit).
Comments:Inspected
(1) The downstairs furnace is older, and we are unable to determine life remaining. There are signs of
rust staining around the burners from past air conditioning condensation leaks. This furnace operated at
the time of the inspection, but frequently cycled on and off before reaching the desired temperature set
on the thermostat. Further inspection by a qualified contractor is needed. Recommend having a licensed
HVAC contractor inspect further and repair as needed for safety reasons. You should budget to have this
furnace replaced in the future.
6.0 Item 1(Picture)
(2) The safety shut-off switch for the downstairs air handler has been secured inward with tape which
prevents the motor from shutting down when the lower access door is removed for service. This is a
safety issue that needs correction. Recommend having a qualified HVAC contractor or person inspect
further and correct as needed.
Authentic Inspection Services, Inc.Harrelson
1321 Scott Street Page 38 of 72
6.0 Item 2(Picture)
(3) The gas flex connector entering the metal casing of the downstairs furnace should be insulated
where entering the case for safety. Even though this is a small correction and may not have been
required when the unit was installed, we recommend having a qualified HVAC contractor inspect further
and correct as needed.
6.0 Item 3(Picture)
(4) The upstairs furnace is old, but did operate at time of inspection. We are unable to determine life
remaining. The average heat temperature at the registers was 105 degrees. Recommend having a
licensed HVAC contractor service as needed due to the age, and for safety reasons. You should budget
to have the furnace replaced in the near future.
(5) Our company did not inspect the operation of the aged gas wall mounted heating unit in the upstairs
bathroom. We do not recommend using this wall heater because of it's age, and for safety reasons.
6.1 NORMAL OPERATING CONTROLS
Comments:Inspected
6.2 CHIMNEYS, FLUES AND VENTS
Comments:Inspected
(1)The exhaust piping for the downstairs gas furnace in the basement is disconnected over
the furnace which is dangerous. This piping also terminates into a hole in the wall in the
basement that was a chimney that is now appears to be capped. This is a carbon monoxide,
fire, and life safety issue that needs immediate correction before the furnace is operated.
Authentic Inspection Services, Inc.Harrelson
1321 Scott Street Page 39 of 72
Recommend having a qualified licensed HVAC contractor inspect further and properly repair
or replace the exhaust vent pipe as needed for safety.
6.2 Item 1(Picture)
(2) The exhaust vent pipe for the upstairs gas furnace does not reach or terminate properly into the roof
vent piping over the furnace in the hallway HVAC closet. This can result in carbon monoxide spillage into
the home, which is a safety issue. Recommend having a qualified licensed HVAC contractor inspect
further and properly repair or replace the exhaust vent piping as needed.
6.2 Item 2(Picture)
6.3 HEAT DISTRIBUTION SYSTEMS
Comments:Inspected
There were no air return filters installed in the downstairs and upstairs air return vents at the time of the
inspection. Filters should be installed every one to three months. Damage to the HVAC components
could occur if filters are not installed, or are dirty. Recommend having a qualified licensed HVAC (Heat/
Ventilation/Air conditioning Contractor) service install filter housing, and clean the units as needed.
6.4 PRESENCE OF INSTALLED HEATING SOURCE IN EACH ROOM
Comments:Inspected
The heating system of this home was inspected and reported on with the above information. While the inspector makes every effort to
find all areas of concern, some areas can go unnoticed. The inspection is not meant to be technically exhaustive. The inspection does
not involve removal and inspection behind service door or dismantling that would otherwise reveal something only a licensed heat
contractor would discover. Please be aware that the inspector has your best interest in mind. Any repair items mentioned in this report
should be considered before purchase. It is recommended that qualified contractors be used in your further inspection or repair issues as
it relates to the comments in this inspection report.
Authentic Inspection Services, Inc.Harrelson
1321 Scott Street Page 40 of 72
7.CENTRAL AIR CONDITIONING
The home inspector shall observe: Central air conditioning and permanently installed cooling systems including: Cooling and air handling
equipment; and Normal operating controls; Distribution systems; and The presence of an installed cooling source in each room. The
home inspector shall describe: Energy sources; and Cooling method by its distinguishing characteristics. The home inspector shall
operate the systems using normal operating controls. The home inspector shall open readily openable access panels provided by the
manufacturer or installer for routine homeowner maintenance. The home inspector is not required to: Observe window air conditioners
or operate cooling systems when weather conditions or other circumstances may cause equipment damage ;Observe non-central air
conditioners or electronic air filters; or Observe the uniformity or cool-air supply adequacy and distribution balance to the various rooms.
Styles & Materials
COOLING EQUIPMENT
TYPE:
AIR CONDITIONER
UNIT
FORCED AIR
COOLING EQUIPMENT ENERGY SOURCE:
ELECTRICITY
COOLING
METHOD:
AIR
NUMBER OF A/C UNITS
(Central):
TWO
CENTRAL AIR MANUFACTURER (outdoor):
HEIL
PAYNE
Serial # : Downstairs 1616X64310 MFR DATE APRIL 2016 Upstairs
L991224918 ESTIMATE MFR DATE 1999
FILTER
LOCATION:
KITCHEN
UPSTAIRS
HALLWAY
Items
7.0 COOLING AND AIR HANDLER EQUIPMENT
Comments:Inspected, Not Inspected
(1) The air conditioning components were not tested for proper operation due to the outside air
temperature was 65 degrees or less in the last 24 hours. Damage could result if the unit was tested.
(2) The upstairs air conditioning components are old, and are nearing the end of typical life expectancy.
We are unable to determine life remaining. Recommend having a licensed HVAC contractor service as
needed due to the age. You should budget to have the air conditioning equipment replaced in the near
future.
(3) Recommend monitoring and maintaining the air conditioning condensate pump for the downstairs
unit periodically for proper operation. The drain piping for this pump is a small diameter copper line that
can become clogged easily. If the pump or line become clogged, water intrusion could occur in the
basement. Recommend having a qualified HVAC contractor evaluate further, and repair or correct as
needed.
7.0 Item 1(Picture)7.0 Item 2(Picture)
Authentic Inspection Services, Inc.Harrelson
1321 Scott Street Page 41 of 72
(4) The downstairs air conditioning suction line is missing a piece of the foam insulating sleeve over the
furnace in the basement. Recommend having a qualified HVAC contractor or person add insulation as
needed to prevent condensation from forming and dripping into the furnace components.
7.0 Item 3(Picture)
(5) The air conditioning suction lines are missing the foam insulating sleeves in areas at the exterior
compressor units. Recommend having a qualified HVAC contractor or person add insulation where
needed to prevent condensation and promote efficiency.
7.0 Item 4(Picture)7.0 Item 5(Picture)
7.1 NORMAL OPERATING CONTROLS
Comments:Not Inspected
The air conditioning components were not tested for proper operation due to the outside air
temperature was 65 degrees or less in the last 24 hours. Damage could result if the unit was tested.
7.2 DISTRIBUTION SYSTEMS
Comments:Inspected
There were no air return filters installed in the downstairs and upstairs air return vents at the time of the
inspection. Filters should be installed every one to three months. Damage to the HVAC components
could occur if filters are not installed, or are dirty. Recommend having a qualified licensed HVAC (Heat/
Ventilation/Air conditioning Contractor) service install filter housing, and clean the units as needed.
7.3 PRESENCE OF INSTALLED COOLING SOURCE IN EACH ROOM
Comments:Inspected
Authentic Inspection Services, Inc.Harrelson
1321 Scott Street Page 42 of 72
The cooling system of this home was inspected and reported on with the above information. While the inspector makes every effort to
find all areas of concern, some areas can go unnoticed. The inspection is not meant to be technically exhaustive. The inspection does
not involve removal and inspection behind service door or dismantling that would otherwise reveal something only a licensed HVAC
contractor would discover (Heating, Ventilation, and Air Conditioning). Please be aware that the inspector has your best interest in mind.
Any repair items mentioned in this report should be considered before purchase. It is recommended that qualified contractors be used in
your further inspection or repair issues as it relates to the comments in this inspection report.
Authentic Inspection Services, Inc.Harrelson
1321 Scott Street Page 43 of 72
8.INTERIORS
The home inspector shall observe: Walls, ceiling, and floors; Steps, stairways, balconies, and railings; Counters and a r epresentative
number of installed cabinets; and a representative number of doors and windows. The home inspector shall: Operate a representative
number of windows and interior doors; and Report signs of abnormal or harmful water penetration into the building or signs of abnormal
or harmful condensation on building components. The home inspector is not required to observe: Paint, wallpaper, and other finish
treatments on the interior walls, ceilings, and floors; Carpeting; or Draperies, blinds, or other window treatments, household appliances,
or recreational facilities.
Styles & Materials
CEILING MATERIALS:
DRYWALL
METAL PANELS
PLASTER
BEAD BOARD
WALL MATERIAL:
DRYWALL
PLASTER
BRICK
WALLPAPER
BEAD-PLY
BEAD BOARD
FLOOR COVERING(S):
WOOD T&G
TILE
INTERIOR DOORS:
WOOD
RAISED PANEL
POCKET DOOR(S)
WINDOW TYPES:
AGED
SINGLE PANE
WINDOW MANUFACTURER:
UNKNOWN
CABINETRY:
WOOD
COUNTERTOP:
MARBLE
Extra Info : COPPER
Items
8.0 WALLS
Comments:Inspected
(1) The drywall or plaster on the walls under the left windows in the hallway, and around the window in
the upstairs rear right bedroom reveals water stains indicating leaks still exists over these areas. A
moisture meter was used to determine that the stains had a moderate moisture content at the time of
the inspection. Leaking is occurring around these areas due to improper flashings around these dormer
windows and a chimney (SEE 3.2(1)). Recommend monitoring periodically, or have a qualified licensed
roofing contractor inspect further, and repair or correct as needed.
Authentic Inspection Services, Inc.Harrelson
1321 Scott Street Page 44 of 72
8.0 Item 1(Picture)8.0 Item 2(Picture)
8.0 Item 3(Picture)
(2) The drywall or plaster on the upper right wall in the downstairs rear right room reveals water stains
indicating leaks still exists over these area. A moisture meter was used to determine that the stains had
a moderate to moisture content. Leaking is occurring due to improper flashings around these dormer
windows and a chimney over this area (SEE 3.2(1)). Recommend monitoring periodically, or have a
qualified plumber or contractor inspect further if desired.
8.0 Item 4(Picture)8.0 Item 5(Picture)
Authentic Inspection Services, Inc.Harrelson
1321 Scott Street Page 45 of 72
(3) There is a efflorescence (powder substance) and flaking paint on the side walls in the upstairs front
center room. This indicates that moisture has been in contact with the masonry, but does not
necessarily mean that intrusion will occur. It appears that moisture has entered where the roof line
meets the sides of the look out structure walls over this area in the past. A moisture meter was used to
determine that the areas showing signs of flaking paint were in the normal range below 15% at the time
of the inspection. This should alert you to the possibility that future steps may be needed. Recommend
monitoring periodically, and or further investigation or correction by a qualified licensed contractor or
water infiltration specialist if desired.
8.0 Item 6(Picture)8.0 Item 7(Picture)
(4) The wallpaper on the upper left wall in the upstairs bathroom reveals moisture signs indicating leaks
still exists over these area. Recommend monitoring periodically, or have a qualified roofing contractor
inspect further if desired.
8.0 Item 8(Picture)
(5) The access door in the upper front wall of the upstairs rear right bedroom is painted shut, and was
not accessible at the time of the inspection. This is for your information.
8.1 CEILINGS
Comments:Inspected
(1) The drywall on the ceilings in the downstairs front and rear right rooms reveals water stains
indicating leaks did or still exist over these areas. A moisture meter was used to determine that the
materials on the front ceiling in the downstairs front right room had a moisture content of 32%
indicating active moisture intrusion. The staining on the ceilings in multiple areas of the downstairs rear
Authentic Inspection Services, Inc.Harrelson
1321 Scott Street Page 46 of 72
right room was in the normal range below 15% were tested. Leaking may have occurred around upper
windows, or could be the result of pests nesting over these areas. Recommend having have a qualified
contractor inspect further, and repair or correct any sources of leaking where needed.
8.1 Item 1(Picture)8.1 Item 2(Picture)
(2) The drywall on the rear ceiling in the upstairs rear left room reveals painted over water stains
indicating a leak did or still exists over this area. A moisture meter was used to determine that the
materials were dry at the time of the inspection. Leaking may have occurred around the chimney or
dormer over this area in the past. Recommend monitoring periodically, or have a qualified plumber or
contractor inspect further if desired.
8.1 Item 3(Picture)
(3) The drywall or plaster on the front and left ceilings in the downstairs front left room reveals flaking of
the paint and possible staining indicating leaks did or still exist over these areas. A moisture meter was
used to determine that the materials were dry at the time of the inspection. Leaking may have occurred
around the chimney or windows over this area in the past.
Authentic Inspection Services, Inc.Harrelson
1321 Scott Street Page 47 of 72
8.1 Item 4(Picture)8.1 Item 5(Picture)
(4) The drywall on the ceilings and walls in the front and rear right upstairs closet shows minor signs of
mildew. This could be a result of a roof leak above this area. Recommend having a qualified licensed
contractor evaluate further, and repair or correct the source of staining as needed.
8.1 Item 6(Picture)
(5) The wood trim is loose in the upper rear corner wall in the downstairs middle left room. Recommend
having a qualified contractor evaluate further, and repair or correct as needed.
8.1 Item 7(Picture)
Authentic Inspection Services, Inc.Harrelson
1321 Scott Street Page 48 of 72
(6) The drywall or plaster on the ceilings in some of the rooms shows signs of cracking. This is due to the
expansion and contraction of the materials that make up the ceiling structure. Recommend having a
qualified contractor evaluate further, and repair or patch the cracking as needed.
8.1 Item 8(Picture)8.1 Item 9(Picture)
8.2 FLOORS
Comments:Inspected
8.3 STEPS, STAIRWAYS, BALCONIES AND RAILINGS
Comments:Inspected
(1) The railings at the top of the stairs for the upstairs center room are lower than the standard height
according to today's standards. A fall or injury could occur. This is for your information.
(2) There are no hand rails for the stairs to the basement. Recommend having a qualified contractor
install hand rails for safety reasons because a fall or injury could occur if hand rails are not installed.
8.4 COUNTERTOPS AND A REPRESENTATIVE NUMBER OF CABINETS
Comments:Inspected
8.5 DOORS (REPRESENTATIVE NUMBER)
Comments:Inspected
(1) The front entry door for the upstairs hall bathroom from the bedroom closet is stuck shut, or would
not open at the time of the inspection. Recommend having a qualified licensed contractor inspect
further and repair or replace as needed.
(2) The rear entry door for the downstairs hall bathroom from the center left room is stuck shut, or would
not open at the time of the inspection. Recommend having a qualified licensed contractor inspect
further and repair or replace as needed.
(3) Most of the entry doors for the upstairs rooms rub the jambs when closing. Recommend adjustment
as needed by a qualified contractor or person.
(4) The entry door for the upstairs front right bedroom needs strike adjustment for the door knob to
latch properly. This is a small repair. Recommend adjustment as needed by a qualified contractor or
person.
8.6 WINDOWS (REPRESENTATIVE NUMBER)
Comments:Inspected
(1) The left window in the upstairs front left bedroom has a small hole in the upper glass pane. Damaged
glass should be replaced to prevent injury or damage. Recommend having a qualified contractor inspect
further and repair or replace as needed.
Authentic Inspection Services, Inc.Harrelson
1321 Scott Street Page 49 of 72
(2) There are cracked glass in some windows. Cracked glass should be replaced to prevent injury or
damage. Recommend having a qualified contractor repair or replace damaged glass as needed.
(3) The lower rear right basement window is missing a pane of glass, and this window has been covered
with a piece of sign on the basement side. Repairs are needed. Recommend having a qualified licensed
contractor inspect further and repair or replace the pane of glass as needed.
8.6 Item 1(Picture)
(4) One lower window sill on the front wall in the right front room show beginning signs of deterioration
on the bottom edge on the interior side. Further deterioration may occur over time if moisture intrusion
is active. Recommend having a qualified contractor or person repair, seal and paint where needed.
8.6 Item 2(Picture)
(5) Some of the wood single pane windows are stuck or painted shut in this home. Each room should
have a window with easy access to the exterior of the home in case of a fire. Recommend having a
qualified contractor repair or correct as needed for proper operation and safety.
8.7 INACCESSIBLE AREAS IN THE INTERIOR OF THE STRUCTURE
Comments:Not Inspected
We were unable to inspect behind past residence's belongings. This is for your information.
The interior of the home was inspected and reported on with the above information. While the inspector makes every effort to find all
areas of concern, some areas can go unnoticed. The inspection did not involve moving furniture and inspecting behind furniture, area
rugs or areas obstructed from view. Please be aware that the inspector has your best interest in mind. Any repair items mentioned in this
report should be considered before purchase. It is recommended that qualified contractors be used in your further inspection or repair
issues as it relates to the comments in this inspection report.
Authentic Inspection Services, Inc.Harrelson
1321 Scott Street Page 50 of 72
9.INSULATION AND VENTILATION
The home inspector shall observe: Insulation and vapor retarders in unfinished spaces; Ventilation of attics and foundation areas;
Kitchen and bathroom venting systems; and the operation of any readily accessible attic ventilation fan, and, when temperature permits,
the operation of any readily accessible thermostatic control mechanical ventilation system. The home inspector shall describe: Insulation
and vapor retarders in unfinished spaces; and Absence of insulation in unfinished space at conditioned surfaces. The home inspector is
not required to disturb insulation or vapor retarders; or Determine indoor air quality. The home inspector is not required to report on:
Concealed insulation and vapor retarders; or Venting equipment that is integral with household appliances.
Styles & Materials
ATTIC INSULATION:
NONE
FLOOR INSULATION:
BATT
FIBERGLASS
PARTIALLY INSULATED
VENTILATION:
SOFFIT VENTS
BATHROOM EXHAUST FAN TYPES:
FAN ONLY
DRYER POWER SOURCE:
22O ELECTRIC
DRYER VENT/HOSE:
METAL
VENTED INTO CRAWLSPACE
VAPOR BARRIERS ON CRAWLSPACE GROUND:
ARE PRESENT IN CRAWLSPACE
Extra Info : UNDER THE KITCHEN
Items
9.0 INSULATION AND VAPOR RETARDERS (in unfinished spaces)
Comments:Not Present
(1) There was no insulation installed in the only accessible small attic area at the rear right side of the
home. Heat loss can occur more in this area of the home, than one that is properly insulated.
Recommend having a qualified contractor add insulation where needed.
(2) The floor insulation is loose, or has fallen in several areas of the rear left crawlspace. Insulation that
has fallen to the ground needs to be secured or replaced with new insulation. Recommend having a
qualified person correct as needed.
9.1 VENTILATION OF ATTIC AND FOUNDATION AREAS
Comments:Inspected
(1) The foundation vents at the rear left corner of the home have no screens installed over them.
Rodents, reptiles or insects could enter into crawlspace. Recommend having a qualified contractor or
person repair or replace the vent screens where needed.
9.1 Item 1(Picture)
Authentic Inspection Services, Inc.Harrelson
1321 Scott Street Page 51 of 72
(2) The lower basement windows around the home are at or below ground level. Allowing leaves and
debris to collect in these areas could result in water intrusion in the basement or crawlspace areas.
Recommend monitoring these areas periodically, and clean around window wells as needed.
9.1 Item 2(Picture)
(3) The gaps around the exterior sides of basement windows should be sealed. Moisture could enter
behind the brick resulting in deterioration if not corrected. Recommend having a qualified contractor or
person seal the gaps where needed.
9.1 Item 3(Picture)
9.2 VENTING SYSTEMS / CEILING HEATERS (Bathrooms)
Comments:Inspected
9.3 VENTILATION FANS AND THERMOSTATIC CONTROLS (ATTIC)
Comments:Not Present
9.4 DRYER VENT
Comments:Inspected
The dryer vent is vented into the crawlspace under the rear porch. Recommend having a qualified
contractor install a dryer vent that extends to the exterior of the home to prevent warm moist air from
entering cool crawlspace areas. Moisture related problems could develope if not corrected.
The insulation and ventilation of the home was inspected and reported on with the above information. While the inspector makes every
effort to find all areas of concern, some areas can go unnoticed. Venting of exhaust fans or clothes dryer cannot be fully inspected and
bends or obstructions can occur without being accessible or visible (behind wall and ceiling coverings). Only insulation that is visible was
inspected. Please be aware that the inspector has your best interest in mind. Any repair items mentioned in this report should be
considered before purchase. It is recommended that qualified contractors be used in your further inspection or repair issues as it relates
to the comments in this inspection report.
Authentic Inspection Services, Inc.Harrelson
1321 Scott Street Page 52 of 72
10.FIREPLACES AND SOLID FUEL BURNING APPLIANCES
The home inspector shall observe the system components, vent systems, flues and chimneys wher e accessible. The home inspector
shall describe the fireplaces and solid burning appliances and the chimneys. The home inspector is not required to: inspect the interior of
flues and chimneys, the fire screens and doors, the seals and gaskets, the automatic fuel feed devices, the mantels and fireplace
surrounds, the combustion make-up air devices, the heat distribution assists whether gravity controlled or fan assisted; ignite or
extinguish fires or pilot lights; determine draft characteristics; or move fireplace inserts or stoves or firebox contents.
Styles & Materials
TYPE OF FIREPLACE:
AGED NON FUNCTIONAL UNIT
Extra Info : SEALED
NUMBER OF FIREPLACES:
TWO
NUMBER OF WOOD STOVES:
NONE
Items
10.0 FIREPLACE GAS OR SOLID FUEL BURNING DEVICES
Comments:Inspected
(1) Do not use gas log or heating units in the fireplaces because the top of the fire boxes, and chimney
flues are sealed, and carbon monoxide would spill into the home. This is for your information.
10.0 Item 1(Picture)
(2) We recommend installing and maintaining carbon monoxide detectors in the home, when there are
gas or wood burning appliances installed or being used.
(3) There were no keys available at the time of the inspection for the fireplace valves. Recommend
having a qualified person supply gas valve keys as needed.
10.1 CLEARANCE FROM COMBUSTIBLES AND SURROUNDS
Comments:Inspected
10.2 FIRE-BRICK WALLS OR METAL WALLS
Comments:Inspected
There is white efflorescence (powder substance) on the walls of the firebox of the firebox in the
downstairs front left room. This indicates that moisture is in contact with masonry. Leaking is occurring
around the upper chimney at some point. Recommend having a qualified chimney specialist check,
seal and repair as needed before use.
Authentic Inspection Services, Inc.Harrelson
1321 Scott Street Page 53 of 72
10.2 Item 1(Picture)
10.3 VENT SYSTEMS, FLUES AND CHIMNEYS (where visible)
Comments:Inspected, Not Inspected
The chimney was sealed off at the top of the firebox and chimney flues. We were unable to inspect the
flue or vent piping. This is for your information.
The fireplaces and solid fuel burning appliances were inspected and reported on with the above information. While the inspector makes
every effort to find all areas of concern, some areas can go unnoticed. Please be aware that the inspector has your best interest in mind.
Any repair items mentioned in this report should be considered before purchase. It is recommended that qualified contractors be used in
your further inspection or repair issues as it relates to the comments in this inspection report.
Authentic Inspection Services, Inc.Harrelson
1321 Scott Street Page 54 of 72
11.BUILT-IN KITCHEN APPLIANCES
The home inspector shall observe and operate the basic functions of the following kitchen appliances: Permanently installed dishwasher,
through its normal cycle; Range, cook top, and permanently installed oven; Trash compactor; Garbage disposal; Ventilation equipment or
range hood; and Permanently installed microwave oven. The home inspector is not required to observe: Clocks, timers, self-cleaning
oven function, or thermostats for calibration or automatic operation; Non built-in appliances; or Refrigeration units. The home inspector
is not required to operate: Appliances in use; or Any appliance that is shut down or otherwise inoperable.
Styles & Materials
DISHWASHER:
FRIGIDAIRE
RANGE/OVEN:
VULCAN
EXHAUST/RANGE HOOD:
NONE
DISPOSER:
BADGER/IN SINK ERATOR
BUILT-IN MICROWAVE:
NONE
Items
11.0 DISHWASHER
Comments:Inspected
The dishwasher drain hose does not perform a loop to create an air gap under the kitchen sink. This
can result in backflow or cross connection of waste water back into the dishwasher from the sink.
Recommend having a qualified plumber provide a proper loop to avoid possible waste water from the
sink from entering into the dishwasher.
11.0 Item 1(Picture)
11.1 RANGES/OVENS/COOKTOPS
Comments:Inspected, Not Inspected
The oven and/or range were not inspected because there was no gas service to them at the time of the
inspection. This is for your information.
11.2 RANGE HOOD
Comments:Not Present
There is no range hood installed over the gas range. Having an operating range hood over the gas
range, that vents to the exterior of the structure will help pull carbon monoxide created by the gas
range from the home. This is for your information.
11.3 TRASH COMPACTOR
Comments:Not Present
Authentic Inspection Services, Inc.Harrelson
1321 Scott Street Page 55 of 72
11.4 FOOD WASTE DISPOSER
Comments:Inspected
The disposer for the kitchen sink had obstructions inside near the blades when operated. Recommend
having a qualified contractor or person remove obstructions, or correct as needed.
11.5 BUILT IN MICROWAVE COOKING EQUIPMENT
Comments:Not Present
The built-in appliances of the home were inspected and reported on with the above information. While the inspector makes every effort
to find all areas of concern, some areas can go unnoticed. Please be aware that the inspector has your best interest in mind. Any repair
items mentioned in this report should be considered before purchase. It is recommended that qualified contractors be used in your
further inspection or repair issues as it relates to the comments in this inspection report.
Authentic Inspection Services, Inc.Harrelson
1321 Scott Street Page 56 of 72
Repair Summary
Authentic Inspection Services, Inc.
www.authentic-inspection.com
501-664-7233
Customer
Steve Harrelson
Address
1321 Scott Street
Little Rock AR 72202
Both summaries provide the overall condition of the property. It is recommended that you read
both summaries when considering the purchase of this property.
The following items or discoveries indicate that these systems or components do not function as intended or
adversely affects the habitability of the dwelling; or appear to warrant further investigation by a specialist, or
requires subsequent observation.
This summary shall not contain recommendations for routine upkeep of a system or component to keep it in
proper functioning condition or recommendations to upgrade or enhance the function, efficiency, or safety of
the home.
This summary is not the entire report. The complete report may include additional information of concern to
the customer.It is recommended that the customer read the complete report.
1.STRUCTURAL COMPONENTS
1.0 FOUNDATIONS (where visible)
Inspected
(1) There were minor visible signs of water intrusion present in the crawlspace at the time of the
inspection, from damp water and silt stains observed along the lower foundation walls in the
basement. There was also some signs of dry silt in areas. Moisture intrusion if not maintained can
lead to other problems including mold, and cause moisture build-up on the floor system that can lead
to deterioration and settlement over time. Maintain the gutters and any ground drains around the
home. Recommend further investigation or correction by a qualified licensed contractor or water
infiltration specialist if desired.
(2) There are vertical stair-step crack(s) in the brick foundation walls in the crawlspace under the left
entry doors. This is typical for a home this age, but is due to some minor settlement in these ar eas.
However since opinions vary, we recommend having a qualified licensed contractor evaluate further
if desired.
Authentic Inspection Services, Inc.Harrelson
1321 Scott Street Page 57 of 72
1.STRUCTURAL COMPONENTS
1.1 WALLS (Structural)
Inspected
(1) The plaster on the brick walls of the front entry shows signs of diagonal settlement cracking in
areas. This is due to some past settlement in this area of the home. However since opinions vary, we
recommend having a licensed structural engineer or contractor evaluate further for the cause if
desired.
1.2 COLUMNS OR PIERS
Inspected
(2) There is a wood dimensional vertical support installed under a beam in the basement below the
rear right entry into the kitchen. There is a dip and raised area in the floor over this area. This would
not be considered a proper pier according to today's standards. Recommend having a qualified
contractor evaluate further.
2.EXTERIOR
2.2 WINDOWS
Inspected
(1) There is a hole in the lower left corner of the window trim for the upper rear right window (facing
front) made by varmints. Unwanted pests or squirrels may be entering the attic or walls through the
hole. Recommend having a qualified contractor inspect further and repair or correct as needed.
2.3 DECKS, BALCONIES, STOOPS, STEPS, AREAWAYS, PORCHES AND APPLICABLE RAILINGS
Inspected
(4) The edges of the wood porch floor at the rear of the home shows signs of deterioration in areas.
Further deterioration may occur if not repaired. Recommend having a qualified licensed contractor
inspect further and repair or replace as needed.
3.ROOFING
3.0 ROOF COVERINGS
Inspected, Not Inspected
(3) The slate shingles shows signs of damage in multiple areas around the home. There is also corner
trim that is missing on the corners of the mansard roof lines in multiple areas. Damaged slate, and
missing trim should be repaired or replaced as soon as possible to prevent possible leaking and
deterioration over time. Recommend having a qualified licensed roofing contractor inspect further
and repair or replace as needed.
3.1 ROOFING DRAINAGE SYSTEMS
Inspected
(2) The gutter downspout is missing the lower section at the front left corner of the home (facing
front). Erosion can occur if not corrected, possibly leading to water intrusion under the home.
Recommend having a qualified licensed contractor inspect further and repair or replace the
downspout as needed.
3.2 FLASHINGS
Inspected, Not Inspected
(1) There is a tape material installed where the edges of the roof and walls meet around some
dormers and chimneys at the rear of the home. There are signs of active leaking in these areas (SEE
8.0(1)). This is not adequate, and proper flashings should be installed to prevent further moisture
intrusion and deterioration in the future. Recommend having a licensed roofing contractor install
proper flashings where needed.
Authentic Inspection Services, Inc.Harrelson
1321 Scott Street Page 58 of 72
4.PLUMBING SYSTEM
4.0 WATER SUPPLY AND DISTRIBUTION SYSTEMS, FIXTURES AND FAUCETS
Inspected
(1) The spray nozzle at the kitchen sink leaks at the connection to the hose. Repairs are needed.
Recommend having a qualified licensed plumber inspect further and repair or correct as needed.
(2) The faucet at the kitchen sink partially clogged, or has lower volume or pressure. The cause of a
clogged or partially clogged supply line could range from the aerator needs cleaning or a more
involved correction may be needed. Recommend having a qualified licensed plumber inspect further
and repair or correct as needed.
4.1 INTERIOR DRAIN, WASTE AND VENT SYSTEMS
Inspected
(1) The plumbing drain line shows signs of minor active leaking at the connection to the bottom of
the downstairs hall bathroom sink. Repairs are needed. Recommend having a qualified licensed
plumber inspect further and repair or correct as needed.
(2) The toilet in the upstairs hall bathroom does not re-fill properly. Repairs may be needed.
Recommend having a qualified licensed plumber inspect further and repair or correct as needed.
4.2 WATER HEATER SYSTEMS, CONTROLS, CHIMNEYS, FLUES AND EXHAUST VENTS
Inspected, Not Inspected
(2) The T&P (Temperature and Pressure) valve pipe for the water heater terminates in the right
basement room, and needs a 3/4 approved piping material to extend to the exterior of the home if
possible to prevent water intrusion in the crawlspace if the valve should open and stick. PVC piping is
also currently being used, which is not an approved material because it can melt due to super heated
water if the T&P valve opens. Melting of the PVC can result in restrictions in the piping that can
prevent proper release of pressure from the water heater and damage to the home. Recommend
having a qualified licensed plumber replace the T&P piping as needed.
(3) There was minor signs of water dripping from the water heater T&P (Temperature and Pressure)
valve pipe that exits in the basement. This indicates problems with the T&P valve, or thermal
expansion in the water system of the home. Further inspection is needed by a qualified plumber.
Recommend having a qualified licensed plumber inspect further and repair or replace as needed.
4.3 FUEL STORAGE AND DISTRIBUTION SYSTEMS (Interior fuel storage, piping, venting,
supports, leaks)
Inspected
A gas detector was used to confirm active gas leaks at a gas line elbow connection in the
basement near the furnace, and at the valve for the fireplace in the front right room
which is dangerous. Also, the mercaptan additive which adds odor to natural gas is a
health concern because it displaces the oxygen in the air. This is a life safety issue and
should be addressed as soon as possible. Recommend further inspection and repair by a
licensed plumber.
5.ELECTRICAL SYSTEMS
5.2 SERVICE AND GROUNDING EQUIPMENT, MAIN OVERCURRENT DEVICE, MAIN AND
DISTRIBUTION PANELS
Inspected
(1) Problem(s) discovered in the main fused electrical disconnect panel located on a pole in the back
yard, such as a large knock-out missing on the side of the panel, double wiring at the main lugs for a
sub panel which provides no over current protection, signs of possible overheating of the right fuse,
and any other problems that an electrician may discover while performing repairs need correcting.
Electrical issues are a hazard until repaired. Recommend having a licensed electrician inspect further
and repair or upgrade this electrical panel as needed.
Authentic Inspection Services, Inc.Harrelson
1321 Scott Street Page 59 of 72
5.ELECTRICAL SYSTEMS
(2) Problem(s) discovered in the sub electrical panel located on the pole in the back yard, such as
hole(s) in the interior cover not plugged where breakers or knock-out(s) have been removed, and any
other problems that an electrician may discover while performing repairs need correcting. Electrical
issues are a hazard until repaired. Recommend having a licensed electrician inspect further and
repair or correct as needed.
(3) Problem(s) discovered in the sub electrical panel located in the basement near the base of the
stairs, such as double wiring at a circuit breaker, one unused wiring not properly capped, and any
other problems that an electrician may discover while performing repairs need correcting. Electrical
issues are a hazard until repaired. Recommend having a licensed electrician inspect further and
repair or correct as needed.
(4) Problem(s) discovered in the sub electrical panel located at the upstairs exterior air conditioning
compressor unit on the rear roof, such as melted or overheated branch wiring, the interior panel
cover missing, and any other problems that an electrician may discover while performing repairs
need correcting. Electrical issues are a hazard until repaired. Recommend having a licensed
electrician inspect further and repair or correct as needed.
(5) The information plate on the upstairs exterior central air conditioner compressor indicates that
the maximum amp circuit breaker for protecting the unit should be a 60 amp circuit breaker, and it is
serviced by a 70 amp circuit breaker in the sub electrical panel located near the unit. Electrical issues
are a hazard until repaired. Recommend having a licensed electrician reduce the breaker size as
needed to prevent additional damage to the unit if the unit should fail.
(6) The interior panel covers are missing from the sub electrical panels located at the upstairs air
conditioning equipment on the rear roof, and for the disconnect panel located at the downstairs
exterior air conditioning equipment. Even though these are small repairs, it is a potential safety
issue. Recommend having a qualified electrician install proper interior covers as needed.
(7) The electrical disconnect panel at the downstairs exterior air conditioning equipment is loose from
the wall, and needs to be properly secured. Electrical issues are a hazard until repaired. Recommend
having a licensed electrician inspect further and repair or correct as needed.
5.4 BRANCH CIRCUIT CONDUCTORS, OVERCURRENT DEVICES AND COMPATIBILITY OF THEIR
AMPERAGE AND VOLTAGE
Inspected
(1) The flexible protective electrical conduit for branch wiring entering the upstairs exterior air
conditioning compressor unit on the roof is loose, and should be repaired or corrected. Damage to
the branch wiring could occur if not corrected. Recommend having a licensed electrician inspect
further and repair or correct as needed.
(2) Improper electrical wiring should be repaired. There is unused, uncapped, energized branch
wiring exiting the left wall of the kitchen that needs to be placed inside a covered junction box or be
removed. Electrical issues are a hazard until repaired. Recommend having a licensed electrician
repair or correct as needed.
(3) All electrical unused wiring or connections should be made in junction boxes fitted with cover
plates. There is uncapped, energized branch wiring exiting a box located in the basement under the
front left room that needs to be properly capped, and fitted with a cover plate. While this is a small
repair, electrical issues are a hazard until repaired. Recommend having a qualified electrician install a
cover plate as needed.
(4) An extension cord routed through a rear window should not be used as permanent wiring at the
rear exterior of the home, to service electrical power to the irrigation system control panel. Strand
wiring can break down over time resulting in electrical hazards, because extension cord wiring was
not designed for permanent use. Recommend having a licensed electrician install an electrical outlet
near the irrigation control panel as needed.
5.5 CONNECTED DEVICES AND FIXTURES (Observed from a representative number operation
of ceiling fans, lighting fixtures, switches and receptacles located inside the house,
garage, and on the dwelling's exterior walls. No cover plates were removed.)
Inspected
Authentic Inspection Services, Inc.Harrelson
1321 Scott Street Page 60 of 72
5.ELECTRICAL SYSTEMS
(1) The duplex three prong outlet in the right rear floor of the upstairs front center room is broken or
damaged. Electrical issues are considered a hazard until repaired. Recommend having a qualified
licensed electrician replace this outlet as needed.
(2) A duplex three prong outlet in the upstairs front left bedroom broken or damaged. Electrical
issues are considered a hazard until repaired. Recommend having a qualified licensed electrician
replace this outlet as needed.
(3) The duplex three prong outlet on the front wall in the upstairs front right room was not operating,
or had no electrical power to it at the time of the inspection. Electrical issues ar e a hazard until
repaired. Recommend having a qualified licensed electrician inspect further and repair or correct as
needed.
(4) The duplex three prong outlet on the floor in the downstairs rear right room was not operating, or
had no electrical power to it at the time of the inspection. Electrical issues ar e considered a hazard
until repaired. Recommend having a qualified licensed electrician inspect further and repair or correct
as needed.
(5) The duplex three prong outlets on the floor in the upstairs center room was not operating, or had
no electrical power to them at the time of the inspection. Electrical issues are considered a hazard
until repaired. Recommend having a qualified licensed electrician inspect further and repair or
replace as needed.
(6) Most of the duplex three prong outlets in the downstairs rooms tested "reverse polarity" or is
incorrectly wired. Electrical issues are considered a hazard until repaired. Recommend having a
qualified licensed electrician inspect further and repair or correct as needed.
(7) The duplex three prong outlets in the upstairs rear left room tested "reverse polarity" or is
incorrectly wired. Electrical issues are considered a hazard until repaired. Recommend having a
qualified licensed electrician inspect further and repair or correct as needed.
(8) The duplex three prong outlet(s) in the upstairs front right bedroom tested "reverse polarity" or is
incorrectly wired. Electrical issues are considered a hazard until repaired. Recommend having a
qualified licensed electrician inspect further and repair or correct as needed.
(9) The duplex three prong outlets in the upstairs rear left bedroom tested "reverse polarity" or is
incorrectly wired. Electrical issues are considered a hazard until repaired. Recommend having a
qualified licensed electrician inspect further and repair or correct as needed.
5.7 OPERATION OF GFCI (GROUND FAULT CIRCUIT INTERRUPTERS)
Inspected
(1) The outlet(s) over the kitchen countertops, and in the bathrooms are not GFCI (Ground Fault
Circuit Interrupt) protected. Even though GFCI protection may have not been required when the
home was built, and there is no requirement to upgrade, these outlet(s) should be upgraded to GFCI
outlet(s) for safety reasons. Recommend having a qualified licensed electrician upgrade as needed.
6.HEATING
6.0 HEATING EQUIPMENT (Our company is not required to inspect the heat exchanger
component of the unit).
Inspected
(2) The safety shut-off switch for the downstairs air handler has been secured inward with tape which
prevents the motor from shutting down when the lower access door is removed for service. This is a
safety issue that needs correction. Recommend having a qualified HVAC contractor or person inspect
further and correct as needed.
6.2 CHIMNEYS, FLUES AND VENTS
Inspected
(1)The exhaust piping for the downstairs gas furnace in the basement is disconnected
over the furnace which is dangerous. This piping also terminates into a hole in the wall in
the basement that was a chimney that is now appears to be capped. This is a carbon
Authentic Inspection Services, Inc.Harrelson
1321 Scott Street Page 61 of 72
6.HEATING
monoxide, fire, and life safety issue that needs immediate correction before the furnace
is operated. Recommend having a qualified licensed HVAC contractor inspect further and
properly repair or replace the exhaust vent pipe as needed for safety.
(2) The exhaust vent pipe for the upstairs gas furnace does not reach or terminate properly into the
roof vent piping over the furnace in the hallway HVAC closet. This can result in carbon monoxide
spillage into the home, which is a safety issue. Recommend having a qualified licensed HVAC
contractor inspect further and properly repair or replace the exhaust vent piping as needed.
6.3 HEAT DISTRIBUTION SYSTEMS
Inspected
There were no air return filters installed in the downstairs and upstairs air return vents at the time of
the inspection. Filters should be installed every one to three months. Damage to the HVAC
components could occur if filters are not installed, or are dirty. Recommend having a qualified
licensed HVAC (Heat/Ventilation/Air conditioning Contractor) service install filter housing, and clean
the units as needed.
8.INTERIORS
8.0 WALLS
Inspected
(1) The drywall or plaster on the walls under the left windows in the hallway, and around the window
in the upstairs rear right bedroom reveals water stains indicating leaks still exists over these areas. A
moisture meter was used to determine that the stains had a moderate moisture content at the time
of the inspection. Leaking is occurring around these areas due to improper flashings around these
dormer windows and a chimney (SEE 3.2(1)). Recommend monitoring periodically, or have a qualified
licensed roofing contractor inspect further, and repair or correct as needed.
(2) The drywall or plaster on the upper right wall in the downstairs rear right room reveals water
stains indicating leaks still exists over these area. A moisture meter was used to determine that the
stains had a moderate to moisture content. Leaking is occurring due to improper flashings around
these dormer windows and a chimney over this area (SEE 3.2(1)). Recommend monitoring
periodically, or have a qualified plumber or contractor inspect further if desired.
(3) There is a efflorescence (powder substance) and flaking paint on the side walls in the upstairs
front center room. This indicates that moisture has been in contact with the masonry, but does not
necessarily mean that intrusion will occur. It appears that moisture has entered where the roof line
meets the sides of the look out structure walls over this area in the past. A moisture meter was used
to determine that the areas showing signs of flaking paint were in the normal range below 15% at the
time of the inspection. This should alert you to the possibility that future steps may be needed.
Recommend monitoring periodically, and or further investigation or correction by a qualified licensed
contractor or water infiltration specialist if desired.
(4) The wallpaper on the upper left wall in the upstairs bathroom reveals moisture signs indicating
leaks still exists over these area. Recommend monitoring periodically, or have a qualified roofing
contractor inspect further if desired.
8.1 CEILINGS
Inspected
(1) The drywall on the ceilings in the downstairs front and rear right rooms reveals water stains
indicating leaks did or still exist over these areas. A moisture meter was used to determine that the
materials on the front ceiling in the downstairs front right room had a moisture content of 32%
indicating active moisture intrusion. The staining on the ceilings in multiple areas of the downstairs
rear right room was in the normal range below 15% were tested. Leaking may have occurred around
upper windows, or could be the result of pests nesting over these areas. Recommend having have a
qualified contractor inspect further, and repair or correct any sources of leaking where needed.
(2) The drywall on the rear ceiling in the upstairs rear left room reveals painted over water stains
indicating a leak did or still exists over this area. A moisture meter was used to determine that the
Authentic Inspection Services, Inc.Harrelson
1321 Scott Street Page 62 of 72
8.INTERIORS
materials were dry at the time of the inspection. Leaking may have occurred around the chimney or
dormer over this area in the past. Recommend monitoring periodically, or have a qualified plumber or
contractor inspect further if desired.
(3) The drywall or plaster on the front and left ceilings in the downstairs front left room reveals
flaking of the paint and possible staining indicating leaks did or still e xist over these areas. A
moisture meter was used to determine that the materials were dry at the time of the inspection.
Leaking may have occurred around the chimney or windows over this area in the past.
(4) The drywall on the ceilings and walls in the front and rear right upstairs closet shows minor signs
of mildew. This could be a result of a roof leak above this area. Recommend having a qualified
licensed contractor evaluate further, and repair or correct the source of staining as needed.
8.5 DOORS (REPRESENTATIVE NUMBER)
Inspected
(1) The front entry door for the upstairs hall bathroom from the bedroom closet is stuck shut, or
would not open at the time of the inspection. Recommend having a qualified licensed contractor
inspect further and repair or replace as needed.
(2) The rear entry door for the downstairs hall bathroom from the center left room is stuck shut, or
would not open at the time of the inspection. Recommend having a qualified licensed contractor
inspect further and repair or replace as needed.
8.6 WINDOWS (REPRESENTATIVE NUMBER)
Inspected
(1) The left window in the upstairs front left bedroom has a small hole in the upper glass pane.
Damaged glass should be replaced to prevent injury or damage. Recommend having a qualified
contractor inspect further and repair or replace as needed.
(2) There are cracked glass in some windows. Cracked glass should be replaced to prevent injury or
damage. Recommend having a qualified contractor repair or replace damaged glass as needed.
(3) The lower rear right basement window is missing a pane of glass, and this window has been
covered with a piece of sign on the basement side. Repairs are needed. Recommend having a
qualified licensed contractor inspect further and repair or replace the pane of glass as needed.
Home inspectors are not required to report on the following: Life expectancy of any component or system;
The causes of the need for a repair; The methods, materials, and costs of corrections; The suitability of the
property for any specialized use; Compliance or non-compliance with codes, ordinances, statutes, regulatory
requirements or restrictions; The market value of the property or its marketability; The advisability or
inadvisability of purchase of the property; Any component or system that was not observed; The presence or
absence of pests such as wood damaging organisms, rodents, or insects; or Cosmetic items, underground
items, or items not permanently installed. Home inspectors are not required to: Offer warranties or
guarantees of any kind; Calculate the strength, adequacy, or efficiency of any system or component; Enter
any area or perform any procedure that may damage the property or its components or be dangerous to the
home inspector or other persons; Operate any system or component that is shut down or otherwise
inoperable; Operate any system or component that does not respond to normal operating controls; Disturb
insulation, move personal items, panels, furniture, equipment, plant life, soil, snow, ice, or debris that
obstructs access or visibility; Determine the presence or absence of any suspected adverse environmental
condition or hazardous substance, including but not limited to mold, toxins, carcinogens, noise, contaminants
in the building or in soil, water, and air; Determine the effectiveness of any system installed to control or
remove suspected hazardous substances; Predict future condition, including but not limited to failure of
components; Since this report is provided for the specific benefit of the customer(s), secondary readers of
this information should hire a licensed inspector to perform an inspection to meet their specific needs and to
obtain current information concerning this property.
Prepared Using HomeGauge http://www.HomeGauge.com : Licensed To Wayne Pace
Authentic Inspection Services, Inc.Harrelson
1321 Scott Street Page 63 of 72
Maintenance Summary
Authentic Inspection Services, Inc.
www.authentic-inspection.com
501-664-7233
Customer
Steve Harrelson
Address
1321 Scott Street
Little Rock AR 72202
Both summaries provide the overall condition of the property. It is recommended that you read
both summaries when considering the purchase of this property.
The following items or discoveries indicate that these systems or components will need r outine or periodic
maintenance. This summary may contain recommendations for routine upkeep of a system or component to
keep it in proper functioning condition or recommendations to upgrade or enhance the function, efficiency, or
safety of the home.
This Summary is not the entire report. The complete report may include additional information of concern to
the customer.It is recommended that the customer read the complete report.
1.STRUCTURAL COMPONENTS
1.0 FOUNDATIONS (where visible)
Inspected
(3) The brick walls in the crawlspace show signs of minor deterioration or sanding of the bricks in
areas due to age. Repairs will be needed at some point to prevent further deterioration of the walls.
However, since opinions vary, we recommend having a qualified licensed contractor evaluate further,
and repair or correct as needed.
(4) The small holes in the foundation wall at the rear of the home need to be sealed. Unwanted pests
could enter the crawlspace if not corrected. Recommend having a qualified contractor or person seal
where needed.
1.1 WALLS (Structural)
Inspected
(2) The drywall and plaster on the walls shows signs of cracking over and under some windows and
doorways in the home, and on some walls in this home. This is due to some settlement or e xpansion
or contraction of the home over time. However since opinions vary, we recommend having a licensed
contractor evaluate further for cause if desired.
Authentic Inspection Services, Inc.Harrelson
1321 Scott Street Page 64 of 72
1.STRUCTURAL COMPONENTS
1.2 COLUMNS OR PIERS
Inspected
(1) Additional bracing and a beam have been added below the floor structure under the left side of
the kitchen. This is common under older homes and is done to provided additional support because
the original center pier system was insufficient, or to prevent deflection in the floor under certain
rooms. We are unsure of the long-term adequacy of the additional piers because they are made up of
dry stacked blocks that do not appear to have reinforced concrete footers under them. However since
opinions vary, we recommend having a qualified licensed structural engineer or contractor evaluate
further.
1.3 FLOORS (Structural)
Inspected
(1) There are typical signs of fungal growth present on the floor system in the center of the basement
in areas. We did not inspect, test, or determine if the mold like substances are or are not a health
hazard. This is due to increased moisture levels under the home, or improper or insufficient vapor
barriers. Recommend contacting a mold inspector or expert for investigation or correction if needed.
(2) Signs of wood destroying organisms were discovered on the floor structure members in the front
center of the basement room. This damage appears to be old. Recommend having a licensed
exterminator inspect further and repair or correct as needed.
(3) The floor structure has some minor dips or sags in areas of this home. This is typical in older
homes, but is due to settlement of the original piers and support over time. However since opinions
vary, we recommend having a qualified licensed structural engineer evaluate further if desired and
repair or correct as needed.
1.5 ROOF STRUCTURE AND ATTIC
Inspected
(1) Rodent droppings were found in the rear right lower attic. Sometimes pests can cause damage to
the home or components, and in certain cases pest entry prevention can be expensive. Recommend
having a qualified pest control contractor evaluate further and remove or correct the problem as
needed.
(2) There was no fire stop in place at the top of a wall cavity from the basement in the rear right
lower attic. A fire stop should aid in slowing the spread of fire if one should occur in the home.
Recommend having a qualified contractor install an appropriate fire stop to slow the spread of fire.
2.EXTERIOR
2.0 WALL CLADDING FLASHING AND TRIM
Inspected
(1) There are typical settlement crack(s) or separation in the brick siding over and under some of the
windows around the home. This is common for a home this age, but is due to some expansion and
contraction or settlement at least in the brick veneer. However since opinions vary, we recommend
having a qualified contractor evaluate further for cause and occurrence if desired, and repair or seal
cracking as needed.
(2) There are signs that the brick has been anchored to the wall with fasteners at the left side of the
home. Recommend having a qualified contractor evaluate further if desired.
(3) The paint on the lower exterior walls shows signs of flaking in areas. Old paint can contain lead
which can be harmful if consumed. Recommend having a qualified contractor prep and paint the
front porch where needed.
2.1 DOORS (Exterior)
Inspected
Authentic Inspection Services, Inc.Harrelson
1321 Scott Street Page 65 of 72
2.EXTERIOR
(1) The exterior entry doors, trim, and some jambs shows signs of flaking paint in areas.
Deterioration will occur over time if not corrected. Recommend having a qualified contractor prep
and paint to extend the life span of the wood materials.
(2) The locking hardware for the left side entry doors is damaged and missing parts. A replacement is
needed. Recommend having a qualified licensed contractor inspect further and repair or replace as
needed.
2.2 WINDOWS
Inspected
(2) The paint is peeling or flaking away on some window exterior frames or trim at some windows
around the home. There are also signs of minor deterioration in areas around some windows.
Recommend having a qualified contractor or person prep and paint where needed to prevent
deterioration over time.
(3) The gaps around the exterior sides of windows should be sealed, especially around some of the
upper windows. Moisture could enter behind the brick resulting in deterioration if not corrected.
Recommend having a qualified contractor or person seal the gaps where needed.
(4) The window screens are missing, or have not been installed on the home. Recommend having a
qualified contractor or person install screens where needed.
2.3 DECKS, BALCONIES, STOOPS, STEPS, AREAWAYS, PORCHES AND APPLICABLE RAILINGS
Inspected
(2) There is no hand rail for the steps at the front of the home. Recommend having a qualified
contractor install hand rails where there are 3 or more steps for safety reasons. A fall or injury could
occur if not corrected.
(3) There are gaps in the grout and between some tiles around the edges of the front porch. Moisture
intrusion and deterioration could occur over time if not corrected. Recommend having a qualified
contractor seal where needed to prevent possible moisture intrusion.
(5) The paint on the rear and left side porches show signs of flaking in areas. Old paint can contain
lead which can be harmful if consumed. Recommend having a qualified contractor prep and paint the
front porch where needed.
We did not inspect, test or determine if the paint on the interior or exterior of this home contains
lead, or if it is or is not a health hazard. Recommend you contact a specialist or expert for
investigation or correction if desired.
(6) The hand and guard rails for the rear deck are missing proper spacing between the vertical
pickets according to today's standards. Recommend having a qualified contractor install rails with a
maximum space between vertical pickets of four inches for the guardrails, and where there are 3 or
more steps. A fall or injury could occur if not corrected.
(7) The steps or porch at the left side of home show signs of separation around the edges.
Recommend having a qualified contractor inspect further and seal the gaps where needed to prevent
moisture from entering under the steps.
2.5 VEGETATION, GRADING, SURFACE DRAINAGE AND RETAINING WALLS (With respect to their
effect on the condition of the building)
Inspected
The minor negative slope or low area at the rear left sidewalk allows water to pool in this area.
Recommend having a qualified contractor regrade, or improve the drainage in this areas.
2.6 WALKWAYS, PATIOS, AND DRIVEWAYS LEADING TO DWELLING ENTRANCES
Inspected
There is typical settlement cracking in areas. Recommend having a qualified contractor or person
seal cracks to prevent further cracking over time.
Authentic Inspection Services, Inc.Harrelson
1321 Scott Street Page 66 of 72
3.ROOFING
3.0 ROOF COVERINGS
Inspected, Not Inspected
(4) Leaves and other debris on the roof covering should be removed to allow water to drain properly
from roof. Areas covered in debris were not visible.
(5) Tree limbs that are in contact with the roof, or hanging near roof should be trimmed. Recommend
having a qualified contractor or person trim limbs as needed.
(6) Recommend monitoring periodically for leaks where satellite dish mounts are secured to the rear
lower left roof. The sealer that is often applied at the fasteners can separate over time.
3.1 ROOFING DRAINAGE SYSTEMS
Inspected
(1) The gutter troughs have debris in them in most areas. Gutters that drain poorly or are clogged
can lead to many costly problems such as deterioration of fascia, soffit or roof edge. It can also cause
gutters to pull loose and lead to possible water intrusion. Recommend cleaning and maintaining the
gutters troughs and downspouts on a regular basis.
(3) The gutter downspout needs to be extended out of the flower bed at the rear left corner of the
home (facing front). Erosion can occur if not corrected, possibly leading to water intrusion under the
home. Recommend having a qualified licensed contractor inspect further and repair or replace as
needed.
3.2 FLASHINGS
Inspected, Not Inspected
(2) The upper roof coverings and components were inspected from a ladder leaned against a brick
chimney, the ground, and from binoculars. We did not walk on the upper roof because we did not lay
a ladder on the slate tiles around the edges to prevent damage. We walked the lower rear left roof.
There may be portions of the roof that were not visible. This is for your information.
4.PLUMBING SYSTEM
4.0 WATER SUPPLY AND DISTRIBUTION SYSTEMS, FIXTURES AND FAUCETS
Inspected
(3) The bathtub spout for the upstairs bathroom tub is installed inside the rim of the bathtub which is
potentially below the water line. This can result in backflow or cross connection of dirty contaminated
water back into the water supply of the home. This is for your information. Recommend having a
qualified plumber inspect further if desired.
(4) The outside water faucet at the left side of the home (facing front) has been disconnected, and is
no longer functional. This is for your information. Recommend having a qualified licensed plumber
inspect further and repair or replace if desired.
4.1 INTERIOR DRAIN, WASTE AND VENT SYSTEMS
Inspected
(3) The bathroom sink stopper is missing in the upstairs hall bathroom. Recommend having a
qualified plumber or person replace the stopper as needed.
4.2 WATER HEATER SYSTEMS, CONTROLS, CHIMNEYS, FLUES AND EXHAUST VENTS
Inspected, Not Inspected
(1) The water heater is old and past typical life expectancy. We are unable to determine life
remaining. Our company did not inspect the water heater for proper operation because there was no
electrical power to the water heater at the time of the inspection. You should budget to have this
water heater replaced in the near future.
Authentic Inspection Services, Inc.Harrelson
1321 Scott Street Page 67 of 72
5.ELECTRICAL SYSTEMS
5.3 ARE ALL THE CIRCUITS OR FUSES LABELED CLEARLY
Inspected
Not all of the circuits in the electrical panels(s) are labeled, and should be labeled for safety reasons.
5.5 CONNECTED DEVICES AND FIXTURES (Observed from a representative number operation
of ceiling fans, lighting fixtures, switches and receptacles located inside the house,
garage, and on the dwelling's exterior walls. No cover plates were removed.)
Inspected
(10) The wall switch to the left of the sink in the kitchen is missing a cover-plate. This is a small
repair, but electrical issues are a hazard until repaired. Recommend having a qualified electrician or
person install a cover plate for safety reasons.
(11) The duplex three prong outlet on the rear floor in center left room is loose in the floor or
mounting box, and needs to be secured. This is a small repair, but electrical issues are a hazard until
repaired. Recommend having a qualified electrician inspect further and repair or correct as needed.
(12) The light fixtures on the rear wall in the downstairs rear right room did not operate at the time of
the inspection. Try replacing the bulbs first, or have a qualified electrician inspect further and repair if
needed.
(13) The original doorbell did not operate at the time of the inspection. Recommend having a
qualified contractor repair or replace as needed.
(14) Do not store items on the upper shelves of the upstairs closets that could come in contact with
the light bulbs. A fire could result if combustible items are resting on hot bulbs. This is for your
information.
(15) We were unable to determine the purpose of the light switch on the front wall of the center left
room. This is for your information.
5.7 OPERATION OF GFCI (GROUND FAULT CIRCUIT INTERRUPTERS)
Inspected
(2) There were no outlets found in the downstairs bathroom. Recommend having a duplex GFCI
(Ground Fault Circuit Interrupt) outlet installed by a licensed electrician to reduce the possible use of
extension cords from non GFCI protected outlets.
5.9 SMOKE DETECTORS
Inspected
All of the smoke detectors should be tested upon moving into the home, and twice a year thereafter.
Recommend adding smoke detectors to the bedrooms and in other appropriate areas of the home for
safety.
6.HEATING
6.0 HEATING EQUIPMENT (Our company is not required to inspect the heat exchanger
component of the unit).
Inspected
(1) The downstairs furnace is older, and we are unable to determine life remaining. There are signs of
rust staining around the burners from past air conditioning condensation leaks. This furnace operated
at the time of the inspection, but frequently cycled on and off before reaching the desired
temperature set on the thermostat. Further inspection by a qualified contractor is needed.
Recommend having a licensed HVAC contractor inspect further and repair as needed for safety
reasons. You should budget to have this furnace replaced in the future.
(3) The gas flex connector entering the metal casing of the downstairs furnace should be insulated
where entering the case for safety. Even though this is a small correction and may not have been
required when the unit was installed, we recommend having a qualified HVAC contractor inspect
further and correct as needed.
Authentic Inspection Services, Inc.Harrelson
1321 Scott Street Page 68 of 72
6.HEATING
(5) Our company did not inspect the operation of the aged gas wall mounted heating unit in the
upstairs bathroom. We do not recommend using this wall heater because of it's age, and for safety
reasons.
7.CENTRAL AIR CONDITIONING
7.0 COOLING AND AIR HANDLER EQUIPMENT
Inspected, Not Inspected
(2) The upstairs air conditioning components are old, and are nearing the end of typical life
expectancy. We are unable to determine life remaining. Recommend having a licensed HVAC
contractor service as needed due to the age. You should budget to have the air conditioning
equipment replaced in the near future.
(3) Recommend monitoring and maintaining the air conditioning condensate pump for the downstairs
unit periodically for proper operation. The drain piping for this pump is a small diameter copper line
that can become clogged easily. If the pump or line become clogged, water intrusion could occur in
the basement. Recommend having a qualified HVAC contractor evaluate further, and repair or correct
as needed.
(4) The downstairs air conditioning suction line is missing a piece of the foam insulating sleeve over
the furnace in the basement. Recommend having a qualified HVAC contractor or person add
insulation as needed to prevent condensation from forming and dripping into the furnace
components.
(5) The air conditioning suction lines are missing the foam insulating sleeves in areas at the exterior
compressor units. Recommend having a qualified HVAC contractor or person add insulation where
needed to prevent condensation and promote efficiency.
7.2 DISTRIBUTION SYSTEMS
Inspected
There were no air return filters installed in the downstairs and upstairs air return vents at the time of
the inspection. Filters should be installed every one to three months. Damage to the HVAC
components could occur if filters are not installed, or are dirty. Recommend having a qualified
licensed HVAC (Heat/Ventilation/Air conditioning Contractor) service install filter housing, and clean
the units as needed.
8.INTERIORS
8.0 WALLS
Inspected
(5) The access door in the upper front wall of the upstairs rear right bedroom is painted shut, and
was not accessible at the time of the inspection. This is for your information.
8.1 CEILINGS
Inspected
(5) The wood trim is loose in the upper rear corner wall in the downstairs middle left room.
Recommend having a qualified contractor evaluate further, and repair or correct as needed.
(6) The drywall or plaster on the ceilings in some of the rooms shows signs of cracking. This is due to
the expansion and contraction of the materials that make up the ceiling structure. Recommend
having a qualified contractor evaluate further, and repair or patch the cracking as needed.
8.3 STEPS, STAIRWAYS, BALCONIES AND RAILINGS
Inspected
(1) The railings at the top of the stairs for the upstairs center room are lower than the standard
height according to today's standards. A fall or injury could occur. This is for your information.
Authentic Inspection Services, Inc.Harrelson
1321 Scott Street Page 69 of 72
8.INTERIORS
(2) There are no hand rails for the stairs to the basement. Recommend having a qualified contractor
install hand rails for safety reasons because a fall or injury could occur if hand rails are not installed.
8.5 DOORS (REPRESENTATIVE NUMBER)
Inspected
(3) Most of the entry doors for the upstairs rooms rub the jambs when closing. Recommend
adjustment as needed by a qualified contractor or person.
(4) The entry door for the upstairs front right bedroom needs strike adjustment for the door knob to
latch properly. This is a small repair. Recommend adjustment as needed by a qualified contractor or
person.
8.6 WINDOWS (REPRESENTATIVE NUMBER)
Inspected
(4) One lower window sill on the front wall in the right front room show beginning signs of
deterioration on the bottom edge on the interior side. Further deterioration may occur over time if
moisture intrusion is active. Recommend having a qualified contractor or person repair, seal and
paint where needed.
(5) Some of the wood single pane windows are stuck or painted shut in this home. Each room should
have a window with easy access to the exterior of the home in case of a fire. Recommend having a
qualified contractor repair or correct as needed for proper operation and safety.
9.INSULATION AND VENTILATION
9.0 INSULATION AND VAPOR RETARDERS (in unfinished spaces)
Not Present
(1) There was no insulation installed in the only accessible small attic area at the rear right side of
the home. Heat loss can occur more in this area of the home, than one that is properly insulated.
Recommend having a qualified contractor add insulation where needed.
(2) The floor insulation is loose, or has fallen in several areas of the rear left crawlspace. Insulation
that has fallen to the ground needs to be secured or replaced with new insulation. Recommend
having a qualified person correct as needed.
9.1 VENTILATION OF ATTIC AND FOUNDATION AREAS
Inspected
(1) The foundation vents at the rear left corner of the home have no screens installed over them.
Rodents, reptiles or insects could enter into crawlspace. Recommend having a qualified contractor or
person repair or replace the vent screens where needed.
(2) The lower basement windows around the home are at or below ground level. Allowing leaves and
debris to collect in these areas could result in water intrusion in the basement or crawlspace areas.
Recommend monitoring these areas periodically, and clean around window wells as needed.
(3) The gaps around the exterior sides of basement windows should be sealed. Moisture could enter
behind the brick resulting in deterioration if not corrected. Recommend having a qualified contractor
or person seal the gaps where needed.
9.4 DRYER VENT
Inspected
The dryer vent is vented into the crawlspace under the rear porch. Recommend having a qualified
contractor install a dryer vent that extends to the exterior of the home to prevent warm moist air
from entering cool crawlspace areas. Moisture related problems could develope if not corrected.
10.FIREPLACES AND SOLID FUEL BURNING APPLIANCES
10.0 FIREPLACE GAS OR SOLID FUEL BURNING DEVICES
Authentic Inspection Services, Inc.Harrelson
1321 Scott Street Page 70 of 72
10.FIREPLACES AND SOLID FUEL BURNING APPLIANCES
Inspected
(1) Do not use gas log or heating units in the fireplaces because the top of the fire boxes, and
chimney flues are sealed, and carbon monoxide would spill into the home. This is for your
information.
(2) We recommend installing and maintaining carbon monoxide detectors in the home, when there
are gas or wood burning appliances installed or being used.
(3) There were no keys available at the time of the inspection for the fireplace valves. Recommend
having a qualified person supply gas valve keys as needed.
10.2 FIRE-BRICK WALLS OR METAL WALLS
Inspected
There is white efflorescence (powder substance) on the walls of the firebox of the firebox in the
downstairs front left room. This indicates that moisture is in contact with masonry. Leaking is
occurring around the upper chimney at some point. Recommend having a qualified chimney
specialist check, seal and repair as needed before use.
11.BUILT-IN KITCHEN APPLIANCES
11.0 DISHWASHER
Inspected
The dishwasher drain hose does not perform a loop to create an air gap under the kitchen sink. This
can result in backflow or cross connection of waste water back into the dishwasher from the sink.
Recommend having a qualified plumber provide a proper loop to avoid possible waste water from the
sink from entering into the dishwasher.
11.1 RANGES/OVENS/COOKTOPS
Inspected, Not Inspected
The oven and/or range were not inspected because there was no gas service to them at the time of
the inspection. This is for your information.
11.2 RANGE HOOD
Not Present
There is no range hood installed over the gas range. Having an operating range hood over the gas
range, that vents to the exterior of the structure will help pull carbon monoxide created by the gas
range from the home. This is for your information.
11.4 FOOD WASTE DISPOSER
Inspected
The disposer for the kitchen sink had obstructions inside near the blades when operated.
Recommend having a qualified contractor or person remove obstructions, or correct as needed.
Home inspectors are not required to report on the following: Life expectancy of any component or system;
The causes of the need for a repair; The methods, materials, and costs of corrections; The suitability of the
property for any specialized use; Compliance or non-compliance with codes, ordinances, statutes, regulatory
requirements or restrictions; The market value of the property or its marketability; The advisability or
inadvisability of purchase of the property; Any component or system that was not observed; The presence or
absence of pests such as wood damaging organisms, rodents, or insects; or Cosmetic items, underground
items, or items not permanently installed. Home inspectors are not required to: Offer warranties or
guarantees of any kind; Calculate the strength, adequacy, or efficiency of any system or component; Enter
any area or perform any procedure that may damage the property or its components or be dangerous to the
home inspector or other persons; Operate any system or component that is shut down or otherwise
inoperable; Operate any system or component that does not respond to normal operating controls; Disturb
insulation, move personal items, panels, furniture, equipment, plant life, soil, snow, ice, or debris that
Authentic Inspection Services, Inc.Harrelson
1321 Scott Street Page 71 of 72
obstructs access or visibility; Determine the presence or absence of any suspected adverse environmental
condition or hazardous substance, including but not limited to mold, toxins, carcinogens, noise, contaminants
in the building or in soil, water, and air; Determine the effectiveness of any system installed to control or
remove suspected hazardous substances; Predict future condition, including but not limited to failure of
components; Since this report is provided for the specific benefit of the customer(s), secondary readers of
this information should hire a licensed inspector to perform an inspection to meet their specific needs and to
obtain current information concerning this property.
Prepared Using HomeGauge http://www.HomeGauge.com : Licensed To Wayne Pace
Authentic Inspection Services, Inc.Harrelson
1321 Scott Street Page 72 of 72