Loading...
4474i ORDINANCE NO �N 0 RDINAN01 PRESCRIBING PAOVIDING INSTALLATION PERMITCODE OR.THE INSTALLAT ON OF IkRIGERATING SYSTEMS AND R SAdE,FIXING THE FEES EOF CHARGED CODETHEREFOR FORAND OTHERIPURPOSES. PENALLY FOR THE VIOLA TION BE IT ORDAINED BY THE'CITY COUNCIL OF THE CITY OF LITTLE ROOK& Section 1. PERMIT AND FEE. Before any multiple refrigerating stem as defined. in this section, shall hereafter be installed n any building in the City of Little R ek, a permit for such ?vM inspector. The installation shall be secured from the buAdobiOg fee for such permit shall be computed upon the basis of One ($1000) Dollar for each evaporator to be installed in the system. Section 2. RE- INSPECTION. The fee for re- inspection, after a certificate of approval has been issued, shal be Two X2.00 Dollars. Such re- inspection shall be made by the irANIMMg inspector or one of his assistants, whenever tkU�llation shall become a test defective and, in_the opinion of the b� inspector,, "Is necessary. Section 3. MULTIPLE REFRIGERATING SYSTEM DEFINED. The term "Multiple Refrigerating System" as used in this section shall mean and include all mechanical refrigeration systems (except public ice plants or cold storage plants installed under the supervision of a licensed engineer and maintained by a competent licensed. engineer ) in which the refrigerant used in the system is distributed from a common source to two or more separate babinttel each containing one or more evaporators. Section 4. INSPECTIONS AND APPROVALS. (a) All multiple refrigerating systems..as defined above shall be of a pattern and manufacture approved by the-National Board of Fire Underwtitera, and bearing their label of approval. (b) No multiple system shall be placed in operation until the complete installation has been tested by the'insta.11er in the presence of the authority enforcing this code. A certificate of approval shall be posted on the premises where the system is installed. The test shall be made by the contractor or person installing or repairing the system who shall furnish all instruments and material necessary to make -1- .e ,. such tests in accordance with this section of the code. Tests shall i).clude a vacuum test of the complete piping system, preferably with tj&e evaporator installed but valves thereon may be closed to prevent withdrawal of the refrigerant. Under this test a vacuum of twenty inches of mercury shall be placed upon the system and shall be held for a period of twenty minutes, with no detectable drop, after the pump has been stopped. After the vacuum test, the system of piping shall be tested by application of pressure as indicated in the table below. Refrigerant used Carbon Dioxide Amonia Methyl Chloride Sulphur Dioxide Iso- butane Butane Ethyl Chloride Methylane Chloride TES`" PRESSURES High Side Part lbs. per sq. inch 1500 300 190 135 130 75 50 15 Low Side Part lbs per sq.inch 750 150 90 50 50 35 25 15 Carbon dioxide or nitrogen shall be used for test pressures. Section 5. CAPACITY LIMITATION.(Ji) No multiple system shall contain more than 100 pounds of refrigerant. (b) Compressors shall not be located under stairways or near dumb waiter or elevator shafts; shall be located as nearly beneath the riser as practicable; shall preferably not be in a room containing storage of combustable material but shall in any case be located at least ten (10) feet from such storage; shall be located in an accessible part of the building with adequate lighting facility provided; and shall be protected against mechanical injury by a noneombustable partition, or by heavy metal netting secured to two by four inch wooden studding or two metal posts. Section 6. REFRIGERANT LINES. Refrigerant lines shall be in- i. stalled in accordance with either of the following methods; (a) Standard pipe for refrigerants requiring test pressures of three hundred (300) pounds or less and extra heavy pipe for test pressures in excess of three hundred pounds per square inch. (b) Approved annealed seamless copper tubing of not less than .034 inch wall thickness for diameters not exceeding 5 /9th inch, of corresponding (greater wall thiekn @ss for la:r-er diameter. 'There this method is -2- V. such tests in accordance with this section of the code. Tests shall i).clude a vacuum test of the complete piping system, preferably with tj&e evaporator installed but valves thereon may be closed to prevent withdrawal of the refrigerant. Under this test a vacuum of twenty inches of mercury shall be placed upon the system and shall be held for a period of twenty minutes, with no detectable drop, after the pump has been stopped. After the vacuum test, the system of piping shall be tested by application of pressure as indicated in the table below. Refrigerant used Carbon Dioxide Amonia Methyl Chloride Sulphur Dioxide Iso- butane Butane Ethyl Chloride Methylane Chloride TES`" PRESSURES High Side Part lbs. per sq. inch 1500 300 190 135 130 75 50 15 Low Side Part lbs per sq.inch 750 150 90 50 50 35 25 15 Carbon dioxide or nitrogen shall be used for test pressures. Section 5. CAPACITY LIMITATION.(Ji) No multiple system shall contain more than 100 pounds of refrigerant. (b) Compressors shall not be located under stairways or near dumb waiter or elevator shafts; shall be located as nearly beneath the riser as practicable; shall preferably not be in a room containing storage of combustable material but shall in any case be located at least ten (10) feet from such storage; shall be located in an accessible part of the building with adequate lighting facility provided; and shall be protected against mechanical injury by a noneombustable partition, or by heavy metal netting secured to two by four inch wooden studding or two metal posts. Section 6. REFRIGERANT LINES. Refrigerant lines shall be in- i. stalled in accordance with either of the following methods; (a) Standard pipe for refrigerants requiring test pressures of three hundred (300) pounds or less and extra heavy pipe for test pressures in excess of three hundred pounds per square inch. (b) Approved annealed seamless copper tubing of not less than .034 inch wall thickness for diameters not exceeding 5 /9th inch, of corresponding (greater wall thiekn @ss for la:r-er diameter. 'There this method is -2- employed tubing shall be protected from mechanical injury as follows; Flom the manifolds at the compressor, the copper tubing shall be instalied in iron or steel pipes or other metal inclosures as specified below, with suitable metal boxes for the manifold and for all other valves except those at the evaporator. Flexible metal inclosures may be used at bends or at terminals if not exceeding six feet in length and rigidly fastened to connecting pipe and/or valve boxes. Each run of pipe shall be.sealed or plugged at each junotion box inlet with a material not effected by moisture or the temperature of the line. Inclosures shall be rigidly secured to the walls or other support. Tubing shall be independently supported in such a manner as to prevent excessive vibration and strains at joints and connections. Valves, surface connections and joints ,in tubing shall be rigidly secured in suitable metal boxes at accessible points. Section 7. JOINTS. (a) Pipe joints shall have standard pipe eads;and shall be made up with material suited to the refrigerant employed. (b) If flanged fittings are used for pipe connections they shall be of recess gasket type. (c) All joints in copper tubing shall be of sweated types, except that flared joints may be used for tubing not more than 5 /8th inch in diameter and where the required test pressure does not exceed 180 pounds. (d) All joints in tubing shall be accessible. Section S. VALVES AND FITTINGS (a) All valves andifittings on the high pressure side of the system shall be of the forged type; for castings of semi -steel may be used. (b) Shut -off valves shall be linstalled at the following locations; at each surface outlet in pressure and return lines, and in each riser or manifold connection at or near the compressor. These valves shall be fitted with a hand WV wheel or other means of ready operation as an inteal part thereof. (c) Valves in service connections shall be located outside of the refrigerating; unit and at such distance above the floor as will ;provide ready accessibility. (d) Shut -off valve shall be installed in both connections to every evaporator in such a manner as to rmit the removal of the evaporator with valves attached. -3- Section 9. SERVICE CONNECTIONS (a) Not more than a single tenant shall be supplied from an outlet box on a main riser. Such outlet &box shall be located within the premises of the tenant served and so arranged as to be accessible at all times. (b) No outlet or junction box shall be permitted in any hallway, stairway or vertical shaft not cut off at each story. Elevator, dumb waiter or other shaft containing moving objects shall not be used for outlet or junction boxes, nor for tubing or piping carrying refriger- ant. (c) Every refrigerator or unit containing an evaporator shall be rigidly secured in place. Section 10. SAFETY FEATURES (a) Each compressor drive shall e provided with a device which will automatically stop the com- pressor at a pressure not in excess of the test pressure as specified by section #3. This shall not apply to air - cooled machines or to water - cooled machines having a liquid receiver capacity of ess than twelve (12) pounds of refrigerant, and which are so r1ae not to permit a pressure in excess of the test pressure. b) Where amonia or carbon dioxide is used every high pressure ide or liquid receiver which can be shut off shall be equipped ith a pressure relief device discharging into thellow pressure de of the system or to the outside of the building. Where the elief from the high pressure side is into the low pressure side he latter shall be protected by a relief device, discharging to the utside of the building or to a suitable absorber. (e) Reftigerant iping or inclosure carrying refrigerant lines shall be conspicuously narked or labeled so as to plainly.indicate its contents. Such marking hall consist of a suitable metal tag of aluminum or copper with ailed or pressed lettering of about one -half inch in height stating he.name of the refrigerant contained in the piping or conduit and the Ord "Line" underneath or beside the name of the refrigerant, or a ag equal in effect and durability as may be approved by the nspector. A sufficient number of tags shall be placed on risers and a.terals as will readily identify and distinguish such pipings or onduits from other piping used in the building. All such refrigerant ines shall be kept a sufficient distance from other piping so as ot4 _ _ . not to be interfered with through repairs to the latter. Section 11. INSTRUCTION CARD AND INSPECTION CERTIFICATE. The contractor or person installing any multiple refrigerating system shall furnish an instruction card giving a diagram of*the location of compressor and refrigerators together with the lines connecting same and all control valves in such lines. The lines and valves shall be tagged for reference, as approved by the �)`nspector, desi� nating the apartment or location to which the line leads and which valve controls such lines. The card shall contain printed instructi as to the care and maintenance of the system and what to do in an emergency. It shall state the name of the refrigerant used in the system, the amount by weight in Dounds contained in same, and the maximum pressure recommended by the manufacturer. Upon completion of the s stem and after a successful test has been made and witnesses by the inspector, or one of his assistants, and duly ap- proved by him, and after the plant has 1pen installed according to th6— ovisions of this section, the . inspector shall issue to the installer a certificate of inspection and no such multiple refrigerating system shall be used or nut in service until such certificate of inspection has been issued. Whenever any existing multiple refrigerating system or any new system herejaifteg installed, shall become defective, and upon inspection by the inspector shall be declared dangerous to use, and he shall order its use discontinued and the certificate of inspection previously issued s automatically become void, and no such multiple refrigerating system shall be used until proper rena.irs have been made and test applied a until a new certificate of inspection has been issued by thAuAk inspector. The certificate of inspection shall be properly dated, giving the street address of the building where the refrigerating system is located, the location of the compressor in the building, the name of the manufacturer, the refrigerant used, the amount in pounds contained in the system, the maximum pressure to be carried, and such other information as may be deemed necessary by -5- .1 A #,he speetor. The card of instruction and the certificate of inWection shall be placed under a sheet of glass and should be properly framed for preservation and it shall be posted at a point convenient to the compressor. Section 12. Before the City Electrician or any of his as- sistants shall issue a final inspection certificate on any building containing a multi- a refrigerating system, the certificate of inspection of the spector must have been issued upon such refrigerating system. Section 13. PENALTY. Any person, firm or corporation violati any of the provisions of this ordinance shall be deemed guilty of a misdemeanor and upon conviction therefor shall be /fined in any sum not less than Twenty Five ($25) nor more than Five Hundred ($500) Dollars. .Section 14. This ordinance shall be known as the Installations Code and shall take effect and be in force from and after its passage. Passed: August 20, 1929• Attest: Appro ity Clerk. -6-